11.16 U: MONITORS
◆ U2: FAULT
No.
Name
Description
MFAO Signal Level
(Hex.)
U2-01
Current Fault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0080)
Shows the fault that the drive has when viewing the monitor.
U2-02
Previous Fault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0081)
Shows the fault that occurred most recently.
V/f
OLV OLV/PM AOLV/PM EZOLV
U2-03
FreqRef@PrevFault
No signal output available
(0082)
Shows the frequency reference at the fault that occurred most recently.
Use U1-01 [Frequency Reference] to monitor the actual frequency reference value.
Unit: 0.01 Hz
U2-04
OutFreq@PrevFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0083)
Shows the output frequency at the fault that occurred most recently.
Use U1-02 [Output Frequency] to monitor the actual output frequency.
Unit: 0.01 Hz
V/f
OLV OLV/PM AOLV/PM EZOLV
U2-05
OutCurr@PrevFault
No signal output available
(0084)
Shows the output current at the fault that occurred most recently.
Use U1-03 [Output Current] to monitor the actual output current. The keypad shows the value of
U1-03 in amperes (A).
When looking at the monitor through Modbus communications, the current is “8192 = drive rated
current (A)”. Calculate the current from the monitor value that is in at Modbus communications
using “Numerals being displayed / 8192 × drive rated current (A).
Unit: When the drive model changes, the display units for this parameter also change.
•
0.01 A units: 2001 to 2042, B001 to B018, 4001 to 4023
•
0.1A units: 2056 to 2082, 4031 to 4060
U2-06
MotorSpd@PrevFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0085)
Shows the motor speed at the fault that occurred most recently.
Use U1-05 [Motor Speed] to monitor the actual motor speed.
Unit: 0.01 Hz
U2-07
OutVolt@PrevFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0086)
Shows the output voltage reference at the fault that occurred most recently.
Use U1-06 [Output Voltage Ref] to monitor the actual output voltage reference.
Unit: 0.1 V
U2-08
DCBusVolt@PrevFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0087)
Shows the DC bus voltage at the fault that occurred most recently.
Use U1-07 [DC Bus Voltage] to monitor the actual DC bus voltage.
Unit: 1 V
U2-09
OutPow@PrevFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0088)
Shows the output power at the fault that occurred most recently.
Use U1-08 [Output Power] to monitor the actual output power.
Unit: 0.1 kW
U2-10
TrqRef@PrevFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0089)
Shows the torque reference at the fault that occurred most recently as a percentage of the motor
rated torque.
Use U1-09 [Torque Reference] to monitor the actual torque reference.
Unit: 0.1%
U2-11
InStat@PrevFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(008A)
Shows the status of the MFDI terminals at the most recent fault where
= ON and
= OFF.
For example, U2-11 shows
when terminals DI1 and DI3 are ON.
Use U1-10 [In Terminal Status] to monitor the actual MFDI terminal status.
bit0 : Terminal DI1
bit1 : Terminal DI2
bit2 : Terminal DI3
bit3 : Terminal DI4
bit4 : Terminal DI5
bit5 : Terminal DI6
bit6 : Terminal DI7
bit7 : Not used (normal value of [
]).
394
11.16 U: MONITORS
No.
Name
Description
MFAO Signal Level
(Hex.)
U2-12
OutStat@PrevFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(008B)
Shows the status of the MFDO terminals at the most recent fault where
= ON and
= OFF.
For example, U2-12 shows
when terminals NO and DO2 are ON.
Use U1-11 [Out Terminal Status] to monitor the actual MFDO terminal status.
bit0 : Terminal NO/NC-CM
bit1 : Terminal DO1-O1C
bit2 : Terminal DO2-O2C
bit3 : Not used (normal value of [
]).
bit4 : Not used (normal value of [
]).
bit5 : Not used (normal value of [
]).
bit6 : Not used (normal value of [
]).
bit7 : Not used (normal value of [
]).
U2-13
DrvStat@PrevFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(008C)
Shows the status of the MFDO terminals at the most recent fault where
= ON and
= OFF.
For example, U2-13 shows
during run.
Use U1-12 [Drive Status] to monitor the actual MFDO terminal status.
bit0 : During Run
bit1 : During zero-speed
bit2 : During reverse
bit3 : During fault reset signal input
bit4 : During speed agreement
bit5 : Drive Ready
bit6 : During minor fault detection
bit7 : During fault detection
U2-14
OpeTime@PreFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(008D)
Shows the cumulative operation time of the drive at the fault that occurred most recently.
Use U4-01 [Cumulative OpeTime] to monitor the actual cumulative operation time.
Unit: 1 h
U2-15
SFSFreq@PrevFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07E0)
Shows the output frequency after soft start at the fault that occurred most recently.
Use U1-16 [SFS Output Frequency] to monitor the actual output frequency after soft start.
Unit: 0.01 Hz
V/f
OLV OLV/PM AOLV/PM EZOLV
U2-16
qCurrent@PrevFault
No signal output available
(07E1)
Shows the q-axis current of the motor at the fault that occurred most recently.
Use U6-01 [Iq Sec Current] to monitor the actual q-Axis current of the motor.
Unit: 0.1 %
U2-17
dCurrent@PreFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07E2)
Shows the d-axis current of the motor at the fault that occurred most recently.
Use U6-02 [Id ExcCurrent] to monitor the actual d-Axis current of the motor.
Unit: 0.1 %
V/f
OLV OLV/PM AOLV/PM EZOLV
U2-19
RotorDev@PrevFault
No signal output available
(07E4)
Shows the amount of control axis deviation (Δθ) at the fault that occurred most recently.
Use U6-10 [ContAxisDeviation] to monitor the actual amount of control axis deviation (Δθ).
Unit: 0.1 °
U2-20
DrvTemp@PreFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(008E)
Shows the heatsink temperature at the fault that occurred most recently.
Use U4-08 [Heatsink Temperature] to monitor the actual temperature of the heatsink.
Unit: 1 °C
U2-21
STPoSt@PrevFault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(1166)
Monitors conditions to detect STPo [Motor Step-Out Detected] faults. The bit for each condition
Expert
is shown as
= ON or
= OFF.
For example, U2-21 shows
when the drive detects excessive current.
bit0 : Excessive current
bit1 : Induced voltage deviation
bit2 : d-axis current deviation
bit3 : Motor lock at startup
bit4 : Acceleration stall continue
bit5 : Acceleration stall repeat
bit6 : Not used (normal value of [
]).
bit7 : Not used (normal value of [
]).
11
395
11.16 U: MONITORS
◆ U3: FAULT HISTORY
No.
Name
Description
MFAO Signal Level
(Hex.)
U3-01 to U3-04
1st to 4th Newest Fault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0090 - 0093)
Shows the fault history of the first to fourth most recent faults.
(0800 - 0803)
Note:
The drive saves the U3-01 to U3-04 [1st to 4th Newest Fault] fault histories to two types of
registers at the same time for the Modbus communications.
U3-05 to U3-10
5th to 10th Newest Fault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0804 - 0809)
Shows the fault history of the fifth to tenth most recent faults.
V/f
OLV OLV/PM AOLV/PM EZOLV
U3-11 to U3-14
1st to 4th NewstFlt Timing
No signal output available
(0094 - 0097)
Shows the cumulative operation time when the first to fourth most recent faults occurred.
(080A - 080D)
Unit: 1 h
Note:
The drive saves the U3-11 to U3-14 [1st to 4th NewstFlt Timing] the cumulative operation
time to two types of registers at the same time for the Modbus communications.
U3-15 to U3-20
1st to 10th NewstFlt Timing
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(080E - 0813)
Shows the cumulative operation time when the fifth to tenth most recent faults occurred.
Unit: 1 h
◆ U4: MAINTENANCE
No.
Name
Description
MFAO Signal Level
(Hex.)
U4-01
Cumulative OpeTime
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: 99999 h
(004C)
Shows the cumulative operation time of the drive.
Use parameter o4-01 [Cum.Oper TimeSetting] to reset this monitor. Use parameter o4-02 [Cum.
Oper TimeSelect] to select the cumulative operation times from:
• The time from when the drive is energized until it is de-energized.
• The time at which the Run command is turned ON.
The maximum value that the monitor will show is 99999. After this value is more than 99999, the
drive automatically resets it and starts to count from 0 again.
Unit: 1 h
Note:
The Modbus communication data is shown in 10 h units. Use register 0099H for data in 1 h
units.
V/f
OLV OLV/PM AOLV/PM EZOLV
U4-02
Num of Run Commands
10 V: 65535 times
(0075)
Shows how many times that the drive has received a Run command.
Use parameter o4-13 [NumOfRunCom Init Counter] to reset this monitor. The maximum value
that the monitor will show is 65535. After this value is more than 65535, the drive automatically
resets it and starts to count from 0 again.
Unit: 1
U4-03
Fan Oper.Time
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: 99999 h
(0067)
Shows the cumulative operation time of the cooling fans.
Use parameter o4-03 [Fan.Oper Setting] to reset this monitor. The maximum value that the
monitor will show is 99999. After this value is more than 99999, the drive automatically resets it
and starts to count from 0 again.
Unit: 1 h
Note:
The Modbus communication data is shown in 10 h units. Use register 009BH for data in 1 h
units.
V/f
OLV OLV/PM AOLV/PM EZOLV
U4-04
Cool Fan Maintenance
10 V: 100%
(007E)
Shows the cumulative operation time of the cooling fans as a percentage of the replacement life of
the cooling fans.
Use parameter o4-03 [Fan.Oper Setting] to reset this monitor.
Unit: 1%
Note:
Replace the cooling fans when this monitor is 90%.
U4-05
Capacitor Maintenance
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: 100%
(007C)
Shows the operation time of the electrolytic capacitors for the main circuit and control circuit as a
percentage of the replacement life of the electrolytic capacitors.
Use parameter o4-05 [Cap.Maint.Setting] to reset this monitor.
Unit: 1%
Note:
Replace the electrolytic capacitor when this monitor is 90%.
396
11.16 U: MONITORS
No.
Name
Description
MFAO Signal Level
(Hex.)
U4-06
SoftChgRelay Maint
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: 100%
(07D6)
Shows the operation time of the soft charge bypass relay as a percentage of the replacement life of
the soft charge bypass relay.
Use parameter o4-07 [PreChgRly Preset Maintenance Cnt] to reset this monitor.
Unit: 1%
Note:
Replace the drive when this monitor is 90%.
U4-07
IGBT Maintenance
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: 100%
(07D7)
Shows the operation time of the IGBTs as a percentage of the replacement life of the IGBTs.
Set parameter o4-09 [IGBT Preset Maintenance Cnt] to reset this monitor.
Unit: 1%
Note:
Replace the drive when this monitor is 90%.
U4-08
Heatsink Temperature
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: 100 °C
(0068)
Shows the heatsink temperature of the drive.
Unit: 1 °C
U4-09
LED Check
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(005E)
Turns on all of the keypad LEDs to make sure that the LEDs operate correctly.
1.
With U4-09 displayed, press
All LEDs on the keypad will turn on.
Note:
When Safety input 2 CH is open (STo), READY will flash.
V/f
OLV OLV/PM AOLV/PM EZOLV
U4-10
kWh Lower 4Digits
No signal output available
(005C)
Displays the lower 4 digits of the watt hour value for the drive.
Unit: 1 kWh
Note:
The watt hour is displayed in 9 digits. Monitor U4-11 [kWh Upper 5Digits] shows the upper 5
digits and U4-10 shows the lower 4 digits.
Example for 12345678.9 kWh:
U4-10: 678.9 kWh
U4-11: 12345 MWh
U4-11
kWh Upper 5Digits
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(005D)
Shows the upper 5 digits of the watt hour value for the drive.
Unit: 1 MWh
Note:
Monitor U4-11 shows the upper 5 digits and U4-10 [kWh Lower 4Digits] shows the lower 4
digits.
Example for 12345678.9 kWh:
U4-10: 678.9 kWh
U4-11: 12345 MWh
U4-13
Peak Hold Current
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07CF)
Shows the hold value of the peak value (rms) for the drive output current.
Use U4-14 [PeakHold OutFreq] to show the drive output frequency at the time that the drive
holds the output current.
The drive will hold the peak hold current at the next start up and restart of the power supply. The
drive keeps the value that was under hold during baseblock (during stop).
The keypad shows the value of U4-13 in amperes (A). When looking at the monitor through
Modbus communications, the current is “8192 = drive rated current (A)”. Calculate the current
from the monitor value that is in at Modbus communications using “Numerals being displayed /
8192 × drive rated current (A).
Unit: When the drive model changes, the display units for this parameter also change.
•
0.01 A units: 2001 to 2042, B001 to B018, 4001 to 4023
•
0.1A units: 2056 to 2082, 4031 to 4060
U4-14
PeakHold OutFreq
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07D0)
Displays the output frequency at which the peak value (rms) of the drive output current is held.
The peak hold current can be monitored by U4-13 [Peak Hold Current].
The peak hold output frequency will be cleared at the next startup and restart of the power supply.
The drive keeps the value that was under hold during baseblock (during stop).
Unit: 0.01 Hz
U4-16
MotorOLEstimate (oL1)
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: 100%
(07D8)
Shows the integrated value of oL1 [Motor Overload] as a percentage of oL1 detection level.
Unit: 0.1%
11
397
11.16 U: MONITORS
No.
Name
Description
MFAO Signal Level
(Hex.)
U4-18
FRef Source Selected
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07DA)
Shows the selected frequency reference source.
The keypad shows the frequency reference source as “XY-nn” as specified by these rules:
X: Ext Ref 1/2 [H1-xx = 9] selection status
•
1: b1-01 [Freq. Ref. Sel. 1]
•
2: b1-15 [Freq. Ref. Sel. 2]
Y-nn: Frequency reference source
•
0-01: Keypad (d1-01 [Reference 1])
•
1-00: Analog input (unassigned)
•
1-01: MFAI terminal AI1
•
1-02: MFAI terminal AI2
•
2-02 to 2-17: Multi-step speed reference (d1-02 to d1-17 [Reference 2 to Reference 16, Jog
Reference])
•
3-01: Modbus communications
•
4-01: Communication option card
•
5-01: Pulse train input
•
7-01: Q2pack
•
9-01: Up/Down command
U4-19
Mbus FreqReference Value
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V = Maximum
frequency (-10 V to +10 V)
(07DB)
Shows the frequency reference sent to the drive from the Modbus communications as a decimal.
Unit: 0.01%
U4-20
Option FreqReference
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V = Maximum
Value
frequency (-10 V to +10 V)
(07DC)
Shows the frequency reference sent to the drive from the communication option as a decimal.
U4-21
Run Source Selected
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output The
keypad shows the Run
(07DD)
Shows the selected Run command source.
command source as "XY-
The keypad shows the Run command source as “XY-nn” as specified by these rules:
nn" as specified by these
X: Ext Ref 1/2 [H1-xx = 9] selection status
rules: available
•
1: b1-02 [Run Comm. Sel 1]
•
2: b1-16 [Run Comm. Sel 2]
Y: Run command source
•
0: Keypad
•
1: Control circuit terminal
•
3: Modbus communications
•
4: Communication option card
•
7: Q2pack
nn: Run command limit status data
•
00: No limit status.
•
01: The Run command was left ON when the drive stopped in the Programming Mode.
•
02: The Run command was left ON when switching from LOCAL Mode to REMOTE Mode.
•
03: The Run command is in standby after the drive was energized until the soft charge bypass
contactor turns ON.
Note:
The drive will detect Uv1 [DC Bus Undervoltage] or Uv [Undervoltage] if the soft charge
bypass contactor does not turn ON after 10 s.
•
04: Restart after run stop is prohibited.
•
05: Fast stop has been executed using the MFDI terminal. Or, the motor has ramped to stop by
pressing the STOP key on the keypad.
•
06: b1-17 = 1 [RUN@PowerUp Selection = Disregard RUN] is set.
•
07: During baseblock while coast to stop with timer.
•
08: Frequency reference is below E1-09 [Min Output Frequency] during baseblock.
•
09: Waiting for the Enter command from PLC.
398
11.16 U: MONITORS
No.
Name
Description
MFAO Signal Level
(Hex.)
U4-22
Mbus CmdWord Value
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07DE)
Shows the operation signal (register 0001H) sent to the drive from Modbus communications as a
4-digit hexadecimal number (zero suppress).
The keypad shows the operation signal as specified by these rules:
bit 0 : Forward run/Stop
bit 1 : Reverse run/Stop
bit 2 : External fault
bit 3 : Fault Reset Procedure
bit 4 : Multi-function input 1
bit 5 : Multi-function input 2
bit 6 : Multi-function input 3
bit 7 : Multi-function input 4
bit 8 : Multi-function input 5
bit 9 : Multi-function input 6
bit A : Multi-function input 7
bit B : Not used (normal value of 0).
bit C : Not used (normal value of 0).
bit D : Not used (normal value of 0).
bit E : Not used (normal value of 0).
bit F : Not used (normal value of 0).
U4-23
Option CmdWord Value
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07DF)
Shows the operation signal (register 0001H) sent to the drive from Modbus communications as a
4-digit hexadecimal number.
The keypad shows the operation signal as specified by these rules:
bit 0 : Forward run/Stop
bit 1 : Reverse run/Stop
bit 2 : External fault
bit 3 : Fault Reset Procedure
bit 4 : Multi-function input 1
bit 5 : Multi-function input 2
bit 6 : Multi-function input 3
bit 7 : Multi-function input 4
bit 8 : Multi-function input 5
bit 9 : Multi-function input 6
bit A : Multi-function input 7
bit B : Not used (normal value of 0).
bit C : Not used (normal value of 0).
bit D : Not used (normal value of 0).
bit E : Not used (normal value of 0).
bit F : Not used (normal value of 0).
U4-24
No of Travels(L)
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07E6)
Shows the lower 4 digits of the drive run count.
Note:
The drive run count appears as an 8-digit number. Monitor U4-25 [No of Travels(H)] shows
the upper 4 digits and U4-24 shows the lower 4 digits.
U4-25
No of Travels(H)
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07E7)
Shows the lower 4 digits of the drive run count.
Note:
The drive run count appears as an 8-digit number. Monitor U4-25 shows the upper 4 digits
and U4-24 [No of Travels(L)] shows the lower 4 digits.
U4-52
Torque Ref from Comm
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V = 100% (-10 V to +10
V)
(1592)
Displays the torque reference given to the drive via a serial communication option card or via
Modbus communications as a decimal number.
Unit: 0.1%
◆ U5: PID
No.
Name
Description
MFAO Signal Level
(Hex.)
U5-01
PID Feedback
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V = Maximum
frequency (-10 V to +10 V)
(0057)
Shows the PID control feedback value. Parameter b5-20 [PID Unit Selection] sets the display
units.
Unit: 0.01%
V/f
OLV OLV/PM AOLV/PM EZOLV
11
U5-02
PID Input
10 V = Maximum
frequency (-10 V to +10 V)
(0063)
Shows the change between the PID setpoint and PID feedback (the quantity of PID input) as a
percentage of the maximum output frequency.
Unit: 0.01%
399
11.16 U: MONITORS
No.
Name
Description
MFAO Signal Level
(Hex.)
U5-03
PID Output
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V = Maximum
frequency (-10 V to +10 V)
(0064)
Shows the PID control output as a percentage of the maximum output frequency.
Unit: 0.01%
V/f
OLV OLV/PM AOLV/PM EZOLV
U5-04
PID Setpoint
10 V = Maximum
frequency (-10 V to +10 V)
(0065)
Shows the PID setpoint. Parameter b5-20 [PID Unit Selection] sets the display units.
Unit: 0.01%
U5-05
PID Diff.Feedbk
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: Maximum frequency
(-10 V to +10 V)
(07D2)
Shows the PID differential feedback value as a percentage of the maximum output frequency.
This monitor is available after you set H3-02 or H3-10 = 11 [AI1 Function Selection or AI2
Function Selection = Diff PIDFbk].
Unit: 0.01%
U5-06
PID AdjustFeedback
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: Maximum frequency
(-10 V to +10 V)
(07D3)
Shows the difference from calculating U5-05 - U5-01 [PID Diff.Feedbk] - [PID Feedback].
Unit: 0.01%
Note:
U5-01 [PID Feedback] = U5-06 when H3-02 or H3-10 ≠ 11 [AI1 Function Selection or AI2
Function Selection ≠ Diff PIDFbk].
U5-21
Energy Save Ki Coeff
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0872)
Shows the energy-saving coefficient Ki value for PM.
Expert
Unit: 0.01
U5-22
Energy Save Kt Coeff
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0873)
Shows the energy-saving coefficient Kt value for PM.
Expert
Unit: 0.01
U5-99
PID Setpoint Command
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V = Maximum
frequency (-10 V to +10 V)
(1599)
Shows the PID setpoint command. Parameter b5-20 [PID Unit Selection] sets the display units.
Unit: 0.01%
◆ U6: ADVANCED
No.
Name
Description
MFAO Signal Level
(Hex.)
U6-01
Iq Sec Current
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V = Motor secondary
rated current (-10 V to +10
(0051)
Shows the value calculated for the motor secondary current (q axis) as a percentage of the motor
V)
rated secondary current.
Unit: 0.1%
U6-02
Id ExcCurrent
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V = Motor secondary
rated current (-10 V to +10
(0052)
Shows the value calculated for the motor excitation current (d axis) as a percentage of the motor
V)
rated secondary current.
Unit: 0.1%
U6-03
ASR Input
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V = Maximum
frequency (-10 V to +10 V)
(0054)
Shows the ASR input value as a percentage of the maximum frequency.
Unit: 0.01%
U6-04
ASR Output
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V = Motor secondary
rated current (-10 V to +10
(0055)
Shows the ASR output value as a percentage of the motor rated secondary current.
V)
Unit: 0.01%
U6-05
Vq OutputVoltRef
V/f
OLV OLV/PM AOLV/PM EZOLV
200 V class: 10 V = 200
Vrms
(0059)
Shows the drive internal voltage reference for motor secondary current control (q axis).
400 V class: 10 V = 400
Unit: 0.1 V
Vrms
(-10 V to +10 V)
U6-06
Vd OutputVoltRef
V/f
OLV OLV/PM AOLV/PM EZOLV
200 V class: 10 V = 200
Vrms
(005A)
Shows the drive internal voltage reference for motor excitation current control (d axis).
400 V class: 10 V = 400
Unit: 0.1 V
Vrms
(-10 V to +10 V)
U6-07
q-Axis ACR Output
V/f
OLV OLV/PM AOLV/PM EZOLV
200 V class: 10 V = 200
Vrms
(005F)
Shows the output value for current control related to motor secondary current (q axis).
400 V class: 10 V = 400
Expert
Unit: 0.1%
Vrms
(-10 V to +10 V)
U6-08
d-Axis ACR Output
V/f
OLV OLV/PM AOLV/PM EZOLV
200 V class: 10 V = 200
Vrms
(0060)
Shows the output value for current control related to motor excitation current (d axis).
400 V class: 10 V = 400
Expert
Unit: 0.1%
Vrms
(-10 V to +10 V)
400
11.16 U: MONITORS
No.
Name
Description
MFAO Signal Level
(Hex.)
U6-09
AdvPhase Compen
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: 180 ° (-10 V to +10
V)
(07C0)
Displays the data on forward phase compensation for the calculation results of the amount of
control axis deviation.
Expert
Unit: 1 °
U6-10
ContAxisDeviation
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: 180 ° (-10 V to +10
(07C1)
Shows the deviation between the γδ-Axis used for motor control and the dq-Axis.
V)
Expert
Unit: 0.1 °
U6-14
MagPolePos (Obs)
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: 180 ° (-10 V to +10
V)
(07CB)
Shows the value of the flux position estimation.
Expert
Unit: 0.1 °
U6-17
Energy Save Coeff
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07D1)
Shows the total time of direction of motor rotation detections for Speed Estimation Speed
Searches. This value adjusts b3-26 [Dir. Determ. Level].
Expert
Note:
Upper limit is +32767 and lower limit is -32767.
U6-20
FRef Bias (UpDw2)
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: Maximum Frequency
(07D4)
Shows the bias value used to adjust the frequency reference.
Unit: 0.1%
U6-21
Offset Frequency
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V: Maximum Frequency
(07D5)
Shows the total value of d7-01 to d7-03 [Offset Frq 1 to Offset Frq 3] selected with Offset Frq 1
to Offset Frq 3[H1-xx = F to 10].
Unit: 0.1%
U6-31
Trq Detect Monitor
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V:100%
(007B)
Monitors the torque reference or the output current after applying the filter set to L6-07 [Trq
Detect Filter Time].
Unit: 0.1%
U6-36
Comm Err n-IO
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0720)
Shows the number of inter-CPU communication errors. De-energizing the drive sets this number
to 0.
Expert
U6-37
Comm Err n-PWM
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(0721)
Shows the number of inter-CPU communication errors. De-energizing the drive sets this number
to 0.
Expert
U6-57
PoleDis IdDifVal
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07C4)
Shows the change from the integrated current when finding the polarity.
Unit: 1
Note:
If the change from the integrated current is less than 819, increase n8-84 [Polarity Det
Current]. U6-57 = 8192 is equivalent to the motor rated current.
U6-80 to U6-83
OPT IP ADR1 to 4
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07B0 - 07B3)
Shows the currently available local IP Address.
• U6-80: 1st octet
• U6-81: 2nd octet
• U6-82: 3rd octet
• U6-83: 4th octet
U6-84 to U6-87
Online Subnet 1 to 4
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07B4 - 07B7)
Shows the currently available subnet mask.
• U6-84: 1st octet
• U6-85: 2nd octet
• U6-86: 3rd octet
• U6-87: 4th octet
U6-88 to U6-91
Online Gateway 1 to 4
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07B8, 07B9,
Shows the currently available gateway address.
07F0, 07F1)
• U6-88: 1st octet
• U6-89: 2nd octet
• U6-90: 3rd octet
• U6-91: 4th octet
U6-92
Online Speed
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07F2)
Shows the currently available communications speed.
10: 10 Mbps
100: 100 Mbps
U6-93
Online Duplex
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
11
(07F3)
Shows the currently available Duplex setting.
401
11.16 U: MONITORS
No.
Name
Description
MFAO Signal Level
(Hex.)
U6-98
First Fault
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(07F8)
Shows the contents of the most recent communication options fault (DeviceNet, Modbus TCP/IP,
EtherNet/IP).
V/f
OLV OLV/PM AOLV/PM EZOLV
U6-99
Current Fault
No signal output available
(07F9)
Shows the contents of current fault from communication options (DeviceNet, Modbus TCP/IP,
EtherNet/IP).
◆ U8: Q2PACK MONITORS
No.
Name
Description
MFAO Signal Level
(Hex.)
V/f
OLV OLV/PM AOLV/PM EZOLV
U8-01 to U8-10
Q2pack Mon 1 to 10
10 V = 100%
(1950 - 1959)
Shows Q2pack Monitors 1 to 10.
Unit: 0.01%
U8-11 to U8-13
Q2pack Ver 1 to 3
V/f
OLV OLV/PM AOLV/PM EZOLV
No signal output available
(195A - 195C)
When you open the setting screen by clicking the setting button on the PC tool title bar, the user
ID can be confirmed with the ID display of the primary user.
U8-11 displays the upper, U8-12 the lower three digits of the user ID.
U8-13 displays the software ID.
V/f
OLV OLV/PM AOLV/PM EZOLV
U8-18
Q2pack Base Platform
No signal output available
(1961)
Shows the Q2pack platform version.
U8-21 to U8-25
Q2pack Mon 21 to 25
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V = 100%
(1964 - 1968)
Shows Q2pack Monitors 21 to 25.
Unit: 0.01%
U8-31 to U8-40
Q2pack Mon 31 to 40
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V = 100%
(196E - 1977)
Shows Q2pack Monitors 31 to 40.
Unit: 0.01%
U8-51 to U8-55
Q2pack Mon 51 to 55
V/f
OLV OLV/PM AOLV/PM EZOLV
10 V = 100%
(1982 - 1986)
Shows Q2pack Monitors 51 to 55.
Unit: 0.01%
402
11.17 Parameters that Change from the Default Settings with A1-02 [Control Method]
11.17
Parameters that Change from the Default Settings with
A1-02 [Control Method]
The values for the parameters in these tables depend on the values for parameter A1-02. When you change the
setting for A1-02, the default settings will change.
Table
11.1 A1-02 = 0, 2 [V/f Control, OLVector]
Control Method (A1-02 Setting)
No.
Name
Range
Unit
V/f
OLV
(0)
(2)
b2-01
ZSpd/DCI Threshold
0.0
- 10.0
0.1 Hz
0.5
0.5
b2-04
DCInj Time@Stop
0.00
- 10.00
0.01 s
0.50
0.50
b3-01
SpSrch@Start Selection
0-1
1
0
0
SpSrch Deactivation
b3-02
0 - 200
1%
120
100
Current
Speed ACR PGain for
b3-08
0.00
- 6.00
0.01
0.50 *1
0.50 *1
Estimation
Speed ACR ITime for
b3-09
0.0
- 1000.0
0.1 ms
2.0
2.0
Estimation
Speed Bi-Directional
b3-14
0-1
1
0
0
Search
b5-15
Sleep Start Level
0.0
- 400.0
0.1 Hz
0.0
0.0
b6-01
Dwell Ref.@Start
0.0
- 400.0
0.1 Hz
0.0
0.0
b6-03
Dwell Ref@Stop
0.0
- 400.0
0.1 Hz
0.0
0.0
b8-02
eSave Ctrl Gain
0.0
- 10.0
0.1
-
0.7
b8-03
eSave Filter Time
0.00
- 10.00
0.01 s
-
0.50
b8-19
eSave Search Frequency
10 - 300
1 Hz
100
100
C1-11
Ac/Dec Switch Frequency
0.0
- 400.0
0.1 Hz
0.0
0.0
C2-01
Jerk@Start of Accel
0.00
- 10.00
0.01 s
0.20
0.20
C3-01
Slip Comp Gain
0.0
- 2.5
0.1
0.0
1.0
C3-02
Slip Comp Delay Time
0 - 10000
1 ms
2000
200
C4-01
Trq Comp Gain
0.00
- 2.50
0.01
1.00
1.00
C4-02
Trq Comp Delay Time
0 - 10000
1 ms
200
20
C5-01
ASR PGain 1
0.00
- 300.00
0.01
-
-
C5-02
ASR ITime 1
0.000
- 60.000
0.001 s
-
-
C5-03
ASR PGain 2
0.00
- 300.00
0.01
-
-
C5-04
AASR ITime 2
0.000
- 10.000
0.001 s
-
-
C5-06
ASR Delay Time
0.000
- 0.500
0.001 s
-
-
ASR Gain Switch
C5-07
0.0
- 400.0
0.1 Hz
0.0Hz
0.0Hz
Frequency
Carrier Frequency
C6-02
1-F
1
1 *2
1 *2
Selection
d3-01
Jump Frequency 1
0.0
- 400.0
0.1 Hz
0.0
0.0
d3-02
Jump Frequency 2
0.0
- 400.0
0.1 Hz
0.0
0.0
d3-03
Jump Frequency 3
0.0
- 400.0
0.1 Hz
0.0
0.0
d3-04
Jump Frequency Width
0.0
- 20.0
0.1 Hz
1.0
1.0
E1-04
Max Output Frequency
40.0 - 400.0 *2 *3
0.1 Hz
60.0 *4
60.0
E1-05
Max Output Voltage
0.0 - 255.0 *5
0.1 V
200.0 *4
200.0
E1-06
Base Frequency
0.0 - 400.0 *3
0.1 Hz
60.0 *4
60.0
11
E1-07
Mid A Frequency
0.0 - 400.0 *3
0.1 Hz
3.0 *4
3.0
E1-08
Mid A Voltage
0.0 - 255.0 *5
0.1 V
15.0 *4
11.0
E1-09
Min Output Frequency
0.0 - 400.0 *3
0.1 Hz
1.5 *4
0.5
403
11.17
Parameters that Change from the Default Settings with A1-02
[Control Method]
Control Method (A1-02 Setting)
No.
Name
Range
Unit
V/f
OLV
(0)
(2)
E1-10
Min Output Voltage
0.0 - 255.0 *5
0.1 V
9.0 *4
2.0
F1-09
Overspeed Delay Time
0.0
- 2.0
0.1 s
-
-
Motor Cool Type for OL1
L1-01
0-4
1
1
1
Calc
L2-31
KEB StartV Offset Level
0 - 100 *5
1V
0
0
L3-05
StallP@RUN Enable
0-3
1
1
1
L3-20
DCBus VoltAdj Gain
0.00
- 5.00
0.01
1.00
0.30
L3-21
OVSup Acc/Dec Gain
0.10
- 10.00
0.01
1.00
1.00
L3-36
VibSup Gain@Accel
0.0
- 100.0
0.1
10.0
20.0
L4-01
SpAgree Det.Level
0.0 - 400.0 *6
0.1
0.0 Hz
0.0 Hz
L4-02
SpAgree Det.Width
0.0
- 20.0
0.1
2.0 Hz
2.0 Hz
L4-03
SpAgree Det.Level(+/-)
-400.0 - +400.0 *7
0.1
0.0 Hz
0.0 Hz
L4-04
SpAgree Det.Width(+/-)
0.0
- 20.0
0.1
2.0 Hz
2.0 Hz
Carrier Red Off-Delay
L8-40
0.00
- 2.00
0.01 s
0.50
0.50
Time
L8-90
STPo Detect Level
0 - 5000
1
-
-
n5-04
Speed Response Frequency
0.00
- 500.00
0.00 Hz
-
-
n8-35
InitRotorPos Selection
0-2
1
-
-
n8-51
Ac/Dec Pull-In Current
0 - 200%
1
0
0
o1-03
FrqDisplay Unit Selection
0-3
1
0
0
V/f Pattern Unit for
o1-04
0-1
1
-
-
Display
*1
The default setting changes when the setting for o2-04 [Drive KVA Selection] changes.
*2
The default setting changes when the setting of C6-01 [ND/HD Duty Selection] changes.
*3
The setting range changes when the setting of E5-01 [PM Mot Code Selection] changes when A1-02 = 5 [PM OLVector].
*4
The default setting changes when the drive model and E1-03 [V/f Pattern Selection] change.
*5
This is the value for 200 V class drives. Double the value for 400 V class drives.
*6
When A1-02 = 5 [PM OLVector], the maximum value of the setting range is 100.0.
*7
When A1-02 = 5 [PM OLVector], the setting range is -100.0 to +100.0.
Table 11.2 A1-02 = 5, 6, 8 [PM OLVector, PM AOLVector, EZ Vector]
Control Method (A1-02 Setting)
No.
Name
Range
Unit
OLV/PM
AOLV/PM
EZOLV
(5)
(6)
(8)
b2-01
ZSpd/DCI Threshold
0.0
- 10.0
0.1
0.5 Hz
1.0%
0.5Hz
b2-04
DCInj Time@Stop
0.00
- 10.00
0.01 s
0.00
0.00
0.00
b3-01
SpSrch@Start Selection
0-1
1
0
0
0
SpSrch Deactivation
b3-02
0 - 200
1%
-
-
-
Current
Speed ACR PGain for
b3-08
0.00
- 6.00
0.01
0.30
0.30
0.30
Estimation
Speed ACR ITime for
b3-09
0.0
- 1000.0
0.1 ms
4.0
4.0
4.0
Estimation
Speed Bi-Directional
b3-14
0-1
1
-
-
0
Search
b5-15
Sleep Start Level
0.0 - 400.0 *1
0.1
0.0 Hz
0.0%
0.0%
b6-01
Dwell Ref.@Start
0.0 - 400.0 *1
0.1
0.0 Hz
0.0%
0.0%
b6-03
Dwell Ref@Stop
0.0 - 400.0 *1
0.1
0.0 Hz
0.0%
0.0%
b8-02
eSave Ctrl Gain
0.0
- 10.0
0.1
-
-
-
b8-03
eSave Filter Time
0.00
- 10.00
0.01 s
-
-
-
b8-19
eSave Search Frequency
10 - 300
1 Hz
100
100
20
C1-11
Ac/Dec Switch Frequency
0.0 - 400.0 *1
0.1
0.0 Hz
0.0%
0.0%
404
11.17 Parameters that Change from the Default Settings with A1-02 [Control Method]
Control Method (A1-02 Setting)
No.
Name
Range
Unit
OLV/PM
AOLV/PM
EZOLV
(5)
(6)
(8)
C2-01
Jerk@Start of Accel
0.00
- 10.00
0.01 s
1.00
0.20
1.00
C3-01
Slip Comp Gain
0.0
- 2.5
0.1
-
-
0
C3-02
Slip Comp Delay Time
0 - 10000
1 ms
-
-
200
C4-01
Trq Comp Gain
0.00
- 2.50
0.01
0.00
-
0.00
C4-02
Trq Comp Delay Time
0 - 10000
1 ms
100
-
100
C5-01
ASR PGain 1
0.00
- 300.00
0.01
10.00
10.00
10.00
C5-02
ASR ITime 1
0.000
- 60.000
0.001 s
0.500
0.500
0.500
C5-03
ASR PGain 2
0.00
- 300.00
0.01
-
10.00
10.00
C5-04
AASR ITime 2
0.000
- 10.000
0.001 s
-
0.500
0.500
C5-06
ASR Delay Time
0.000
- 0.500
0.001 s
-
0.016
0.004
ASR Gain Switch
C5-07
0.0 - 400.0 *1
0.1
0.0Hz
0.0%
0.0%
Frequency
Carrier Frequency
C6-02
1-F
1
2
2
2
Selection
d3-01
Jump Frequency 1
0.0 - 400.0 *1
0.1
0.0 Hz
0.0%
0.0%
d3-02
Jump Frequency 2
0.0 - 400.0 *1
0.1
0.0 Hz
0.0%
0.0%
d3-03
Jump Frequency 3
0.0 - 400.0 *1
0.1
0.0 Hz
0.0 %
0.0 %
d3-04
Jump Frequency Width
0.0 - 20.0 *2
0.1
1.0 Hz
1.0 %
1.0 %
E1-04
Max Output Frequency
40.0 - 400.0 *3
0.1 Hz
Determined by E5-01
Determined by E5-01
Determined by E5-01
E1-05
Max Output Voltage
0.0 - 255.0 *4
0.1 V
Determined by E5-01
Determined by E5-01
Determined by E5-01
E1-06
Base Frequency
0.0
- 400.0
0.1 Hz
Determined by E5-01
Determined by E5-01
Determined by E5-01
E1-07
Mid A Frequency
0.0
- 400.0
0.1 Hz
-
-
-
E1-08
Mid A Voltage
0.0 - 255.0 *4
0.1 V
-
-
-
E1-09
Min Output Frequency
0.0
- 400.0
0.1 Hz
Determined by E5-01
Determined by E5-01
Determined by E5-01
E1-10
Min Output Voltage
0.0 - 255.0 *4
0.1 V
-
-
-
F1-09
Overspeed Delay Time
0.0
- 2.0
0.1 s
-
0.0
-
Motor Cool Type for OL1
L1-01
0-4
1
4
4
Determined by E9-01
Calc
L2-31
KEB StartV Offset Level
0 - 100 *4
1V
50
50
50
L3-05
StallP@RUN Enable
0-3
1
1
-
3
L3-20
DCBus VoltAdj Gain
0.00
- 5.00
0.01
0.65
0.65
0.65
L3-21
OVSup Acc/Dec Gain
0.10
- 10.00
0.01
1.00
1.00
1.00
L3-36
VibSup Gain@Accel
0.0
- 100.0
0.1
-
-
-
L4-01
SpAgree Det.Level
0.0 - 400.0 *1
0.1
0.0 Hz
0.0%
0.0%
L4-02
SpAgree Det.Width
0.0 - 20.0 *2
0.1
2.0 Hz
4.0%
4.0%
L4-03
SpAgree Det.Level(+/-)
-400.0 - +400.0 *5
0.1
0.0 Hz
0.0%
0.0%
L4-04
SpAgree Det.Width(+/-)
0.0 - 20.0 *2
0.1
2.0 Hz
4.0%
4.0%
Carrier Red Off-Delay
L8-40
0.00
- 2.00
0.01 s
0.00
0.00
0.00
Time
L8-90
STPo Detect Level
0 - 5000
1
0
80
-
Speed Response
n5-04
0.00
- 500.00
0.00 Hz
-
20.00
-
Frequency
n8-35
InitRotorPos Selection
0-2
1
0
1
-
n8-51
Ac/Dec Pull-In Current
0 - 200%
1
50%
0
80%
11
o1-03
FrqDisplay Unit Selection
0-3
1
0
1
1
V/f Pattern Unit for
o1-04
0-1
1
-
1
-
Display
*1
The setting range is 0.0 to 100.0 when A1-02 = 6 [PM AOLVector].
*2
The setting range is 0.0 to 40.0 when A1-02 = 6 [PM AOLVector].
405
11.17 Parameters that Change from the Default Settings with A1-02 [Control Method]
*3
The default setting changes when the setting for C6-01 [ND/HD Duty Selection] changes.
*4
This is the value for 200 V class drives. Double the value for 400 V class drives.
*5
The setting range is -100.0 to +100.0 when A1-02 = 6 [PM AOLVector].
406
11.18 Parameters that Change from the Default Settings with E3-01 [M2 Control Method Selection]
11.18
Parameters that Change from the Default Settings with
E3-01 [M2 Control Method Selection]
The values for the parameters in these tables depend on the values for parameter E3-01. When you change the
setting for E3-01, the default settings will change.
Motor 2 Control Method (setting value of E3-01)
No.
Name
Range
Unit
V/f
OLV
(0)
(2)
C3-21
M2 Slip Comp Gain
0.0
- 2.50
0.1
0.0
1.0
C3-22
M2 Slip Comp DelayTime
0 - 10000
1 ms
2000
200
E3-04
M2 Max Out Frequency
40.0
- 590.0
0.1 Hz
60.0
60.0
0.0
- 255.0
E3-05
M2 Max Out Voltage
0.1 V
200.0
200.0
*1
E3-06
M2 Base Frequency
0.0
- 590.0
0.1 Hz
60.0
60.0
E3-07
M2 Mid A Frequency
0.0
- 590.0
0.1 Hz
3.0
3.0
0.0
- 255.0
E3-08
M2 Mid A Voltage
0.1 V
15.0
11.0
*1
E3-09
M2 Min Out Frequency
0.0
- 590.0
0.1 Hz
1.5
0.5
0.0
- 255.0
E3-10
M2 Min Out Voltage
0.1 V
9.0
2.0
*1
E3-11
M2 Mid B Frequency
0.0
- 590.0
Determined by o1-04
0.0
0.0
0.0
- 255.0
E3-12
M2 Min Out Voltage
0.1 V
0.0
0.0
*1
0.0
- 255.0
E3-13
M2 Base Voltage
0.1 V
0.0
0.0
*1
*1
This is the value for 200 V class drives. Double the value for 400 V class drives.
11
407
11.19 Parameters Changed by E1-03 [V/f Pattern Selection]
11.19
Parameters Changed by E1-03 [V/f Pattern Selection]
The values for parameters A1-02 [Control Method] and E1-03 [V/f Pattern Selection] change the default settings
for the parameters in these tables.
Table 11.3 Parameters Changed by E1-03 (2001 to 2021, B001 to B018, and 4001 to 4012)
Control Method (A1-
No.
Setting Value
02 Setting)
Unit
OLV/
AOL
F
OLV
E1-03
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
PM
V/PM
*1
(2)
(5)
(6)
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
50.0
50.0
*2
*2
E1-05
V
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
*2
*2
*3
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
50.0
50.0
*2
*2
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
2.5
3.0
-
-
E1-08
V
16.0
16.0
16.0
16.0
35.0
50.0
35.0
50.0
19.0
24.0
19.0
24.0
16.0
16.0
16.0
16.0
14.4
-
-
*3
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.3
0.5
*2
*2
E1-10
V
12.0
12.0
12.0
12.0
8.0
9.0
8.0
9.0
12.0
13.0
12.0
15.0
12.0
12.0
12.0
12.0
3.0
-
-
*3
*1
These values are the default settings for E1-04 to E1-10 and E3-04 to E3-10 [V/f Pattern for Motor 2]. These settings are the same as
those for the V/f pattern when E1-03 = 0 [CT_50-50Hzmax].
*2
The default setting varies depending on the setting of E5-01 [PM Mot Code Selection].
*3
This is the value for 200 V class drives. Double the value for 400 V class drives.
Table 11.4 Parameters Changed by E1-03 (2030 to 2082 and 4018 to 4060)
Control Method (A1-
No.
Setting Value
02 Setting)
Unit
OLV/
AOL
F
OLV
E1-03
0
1
2
3
4
5
6
7
8
9
A
B
C
D
E
PM
V/PM
*1
(2)
(5)
(6)
E1-04
Hz
50.0
60.0
60.0
72.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
90.0
120.0
180.0
50.0
50.0
*2
*2
E1-05
V
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
200.0
*2
*2
*3
E1-06
Hz
50.0
60.0
50.0
60.0
50.0
50.0
60.0
60.0
50.0
50.0
60.0
60.0
60.0
60.0
60.0
50.0
50.0
*2
*2
E1-07
Hz
2.5
3.0
3.0
3.0
25.0
25.0
30.0
30.0
2.5
2.5
3.0
3.0
3.0
3.0
3.0
2.5
3.0
-
-
E1-08
V
14.0
14.0
14.0
14.0
35.0
50.0
35.0
50.0
18.0
23.0
18.0
23.0
14.0
14.0
14.0
14.0
13.2
-
-
*3
E1-09
Hz
1.3
1.5
1.5
1.5
1.3
1.3
1.5
1.5
1.3
1.3
1.5
1.5
1.5
1.5
1.5
1.3
0.5
*2
*2
E1-10
V
7.0
7.0
7.0
7.0
6.0
7.0
6.0
7.0
9.0
11.0
9.0
13.0
7.0
7.0
7.0
7.0
2.4
-
-
*3
*1
These values are the default settings for E1-04 to E1-10 and E3-04 to E3-10 [V/f Pattern for Motor 2]. These settings are the same as
those for the V/f pattern when E1-03 = 0 [CT_50-50Hzmax].
*2
The default setting varies depending on the setting of E5-01 [PM Mot Code Selection].
*3
This is the value for 200 V class drives. Double the value for 400 V class drives.
408
11.20 Defaults by Drive Model and Duty Rating ND/HD
11.20
Defaults by Drive Model and Duty Rating ND/HD
The values for the parameters in these tables depend on the values for parameters o2-04 and C6-01. Changing the
settings for o2-04 and C6-01 will change the default settings.
◆ Three-Phase
200 V Class
No. *1
Name
Unit
Default
-
Drive Model
-
2001
2002
2004
2006
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
60
61
62
63
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
0.1
0.2
0.2
0.4
0.4
0.75
0.75
1.1
Power (kW)
02)
SpSrch V/F
b3-04
%
100
100
100
100
100
100
100
100
Gain
Speed Curr
b3-06
Lev1 for
-
1
1
1
1
1
1
0.5
0.5
Estimation
Speed ACR
b3-08
PGain for
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Estimation
Dir. Determ.
b3-26
-
1000
1000
1000
1000
1000
1000
1000
1000
Level
eSave Filter
b8-03
s
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Time
eSave Coef.
b8-04
-
481.7
356.9
356.9
288.2
288.2
223.7
223.7
196.6
Value
Carrier
C6-02
Frequency
-
4
7
4
7
4
7
4
7
Selection
E2-01
Mot Rated
A
0.6
1.1
1.1
1.9
1.9
3.3
3.3
4.9
(E4-01)
Current (FLA)
E2-02
Mot Rated
Hz
2.5
2.6
2.6
2.9
2.9
2.5
2.5
2.6
(E4-02)
Slip
E2-03
Mot No-Load
A
0.4
0.8
0.8
1.2
1.2
1.8
1.8
2.3
(E4-03)
Current
E2-05
Motor L-L
Ω
35.98
20.56
20.56
9.842
9.842
5.156
5.156
3.577
(E4-05)
Resistance
E2-06
Motor Leak
%
21.6
20.1
20.1
18.2
18.2
13.8
13.8
18.5
(E4-06)
Inductance
E2-10
Motor Iron
W
6
11
11
14
14
26
26
38
(E4-10)
Loss
PM Mot Code
E5-01
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
Selection
RideThrough
L2-02
Time@Power
s
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
Loss
Min Baseblck
L2-03
s
0.2
0.3
0.2
0.3
0.2
0.3
0.3
0.4
Time
Powloss
Ramp
L2-04
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
Time@recov
ery
UV Detection
L2-05
-
190
190
190
190
190
190
190
190
Lvl (Uv1)
StallP
L3-02
%
150
120
150
120
150
120
150
120
Level@Accel
11
StallP
L3-06
%
150
120
150
120
150
120
150
120
Level@Run
Acc@Rated
L3-24
s
0.178
0.178
0.178
0.178
0.178
0.142
0.142
0.142
Torque
Overheat Alm
L8-02
°C
115
115
115
115
115
115
120
120
Level
409
11.20 Defaults by Drive Model and Duty Rating ND/HD
No. *1
Name
Unit
Default
-
Drive Model
-
2001
2002
2004
2006
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
60
61
62
63
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
0.1
0.2
0.2
0.4
0.4
0.75
0.75
1.1
Power (kW)
02)
Ground Fault
L8-09
-
0
0
0
0
0
0
0
0
Selection
HuntPrev
n1-03
ms
10
10
10
10
10
10
10
10
Time Constant
HSB CurrLim
n3-02
1
150
120
150
120
150
120
150
120
Level
Mot Inertia
n5-02
Acceleration
s
0.178
0.178
0.178
0.142
0.178
0.142
0.142
0.142
Time
*1
Parameters within parentheses are for motor 2.
No. *1
Name
Unit
Default
-
Drive Model
-
2008
2010
2012
2018
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
64
65
66
67
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
1.1
1.5
1.5
2.2
2.2
3.0
3.0
3.7
Power (kW)
02)
SpSrch V/F
b3-04
%
100
100
100
100
100
100
100
100
Gain
Speed Curr
b3-06
Lev1 for
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Estimation
Speed ACR
b3-08
PGain for
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Estimation
Dir. Determ.
b3-26
-
1000
1000
1000
1000
1000
1000
1000
1000
Level
eSave Filter
b8-03
s
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Time
eSave Coef.
b8-04
-
196.6
169.4
169.4
156.8
156.8
136.4
136.4
122.9
Value
Carrier
C6-02
Frequency
-
3
7
3
7
3
7
3
7
Selection
E2-01
Mot Rated
A
4.9
6.2
6.2
8.5
8.5
11.4
11.4
14
(E4-01)
Current (FLA)
E2-02
Mot Rated
Hz
2.6
2.6
2.6
2.9
2.9
2.7
2.7
2.73
(E4-02)
Slip
E2-03
Mot No-Load
A
2.3
2.8
2.8
3
3
3.7
3.7
4.5
(E4-03)
Current
E2-05
Motor L-L
Ω
3.577
1.997
1.997
1.601
1.601
1.034
1.034
0.771
(E4-05)
Resistance
E2-06
Motor Leak
%
18.5
18.5
18.5
18.4
18.4
19
19
19.6
(E4-06)
Inductance
E2-10
Motor Iron
W
38
53
53
77
77
91
91
112
(E4-10)
Loss
PM Mot Code
E5-01
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
Selection
RideThrough
L2-02
Time@Power
s
0.3
0.3
0.3
0.3
0.5
0.5
1
1
Loss
Min Baseblck
L2-03
s
0.4
0.4
0.4
0.5
0.5
0.5
0.5
0.6
Time
410
11.20 Defaults by Drive Model and Duty Rating ND/HD
No. *1
Name
Unit
Default
-
Drive Model
-
2008
2010
2012
2018
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
64
65
66
67
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
1.1
1.5
1.5
2.2
2.2
3.0
3.0
3.7
Power (kW)
02)
Powloss
Ramp
L2-04
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
Time@recov
ery
UV Detection
L2-05
-
190
190
190
190
190
190
190
190
Lvl (Uv1)
StallP
L3-02
%
150
120
150
120
150
120
150
120
Level@Accel
StallP
L3-06
%
150
120
150
120
150
120
150
120
Level@Run
Acc@Rated
L3-24
s
0.142
0.166
0.166
0.145
0.145
0.145
0.145
0.154
Torque
Overheat Alm
L8-02
°C
110
110
110
110
110
110
115
115
Level
Ground Fault
L8-09
-
0
0
0
0
0
0
0
0
Selection
HuntPrev
n1-03
ms
10
10
10
10
10
10
10
10
Time Constant
HSB CurrLim
n3-02
1
150
120
150
120
150
120
150
120
Level
Mot Inertia
n5-02
Acceleration
s
0.142
0.166
0.166
0.145
0.145
0.145
0.145
0.154
Time
*1
Parameters within parentheses are for motor 2.
No. *1
Name
Unit
Default
-
Drive Model
-
2021
2030
2042
2056
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
68
6A
6B
6D
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
3.7
5.5
5.5
7.5
7.5
11
11
15
Power (kW)
02)
SpSrch V/F
b3-04
%
100
100
100
100
100
100
100
100
Gain
Speed Curr
b3-06
Lev1 for
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Estimation
Speed ACR
b3-08
PGain for
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Estimation
Dir. Determ.
b3-26
-
1000
1000
1000
1000
1000
1000
1000
1000
Level
eSave Filter
b8-03
s
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Time
eSave Coef.
b8-04
-
122.9
94.75
94.75
72.69
72.69
70.44
70.44
63.13
Value
Carrier
C6-02
Frequency
-
3
7
3
7
3
7
3
7
Selection
E2-01
Mot Rated
A
14
19.6
19.6
26.6
26.6
39.7
39.7
53
(E4-01)
Current (FLA)
11
E2-02
Mot Rated
Hz
2.73
1.5
1.5
1.3
1.3
1.7
1.7
1.6
(E4-02)
Slip
E2-03
Mot No-Load
A
4.5
5.1
5.1
8
8
11.2
11.2
15.2
(E4-03)
Current
411
11.20 Defaults by Drive Model and Duty Rating ND/HD
No. *1
Name
Unit
Default
-
Drive Model
-
2021
2030
2042
2056
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
68
6A
6B
6D
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
3.7
5.5
5.5
7.5
7.5
11
11
15
Power (kW)
02)
E2-05
Motor L-L
Ω
0.771
0.399
0.399
0.288
0.288
0.23
0.23
0.138
(E4-05)
Resistance
E2-06
Motor Leak
%
19.6
18.2
18.2
15.5
15.5
19.5
19.5
17.2
(E4-06)
Inductance
E2-10
Motor Iron
W
112
172
172
262
262
245
245
272
(E4-10)
Loss
PM Mot Code
E5-01
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
Selection
RideThrough
L2-02
Time@Power
s
1
1
1
1
1
1
2
2
Loss
Min Baseblck
L2-03
s
0.6
0.7
0.7
0.8
0.8
0.9
0.9
1
Time
Powloss
Ramp
L2-04
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.6
Time@recov
ery
UV Detection
L2-05
-
190
190
190
190
190
190
190
190
Lvl (Uv1)
StallP
L3-02
%
150
120
150
120
150
120
150
120
Level@Accel
StallP
L3-06
%
150
120
150
120
150
120
150
120
Level@Run
Acc@Rated
L3-24
s
0.154
0.168
0.168
0.175
0.175
0.265
0.265
0.244
Torque
Overheat Alm
L8-02
°C
115
115
105
105
115
115
125
125
Level
Ground Fault
L8-09
-
0
0
1
1
1
1
1
1
Selection
HuntPrev
n1-03
ms
10
10
10
10
10
10
10
10
Time Constant
HSB CurrLim
n3-02
1
150
120
150
120
150
120
150
120
Level
Mot Inertia
n5-02
Acceleration
s
0.154
0.168
0.168
0.175
0.175
0.265
0.265
0.244
Time
*1
Parameters within parentheses are for motor
2.
No. *1
Name
Unit
Default
-
Drive Model
-
2070
2082
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
o2-04
Drive KVA Selection
Hex.
6E
6F
E2-11
Motor Rated Power
kW
15
18.5
18.5
22
(E4-11, E5-02)
(kW)
b3-04
SpSrch V/F Gain
%
100
100
100
100
Speed Curr Lev1 for
b3-06
-
0.5
0.5
0.5
0.5
Estimation
Speed ACR PGain for
b3-08
-
0.5
0.5
0.5
0.5
Estimation
b3-26
Dir. Determ. Level
-
1000
1000
1000
1000
b8-03
eSave Filter Time
s
0.5
0.5
0.5
0.5
b8-04
eSave Coef. Value
-
63.13
57.87
57.87
51.79
412
11.20
Defaults by Drive Model and Duty Rating ND/HD
No. *1
Name
Unit
Default
-
Drive Model
-
2070
2082
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
o2-04
Drive KVA Selection
Hex.
6E
6F
E2-11
Motor Rated Power
kW
15
18.5
18.5
22
(E4-11, E5-02)
(kW)
Carrier Frequency
C6-02
-
3
7
3
7
Selection
E2-01
Mot Rated Current
A
53
65.8
65.8
77.2
(E4-01)
(FLA)
E2-02
Mot Rated Slip
Hz
1.6
1.67
1.67
1.7
(E4-02)
E2-03
Mot No-Load Current
A
15.2
15.7
15.7
18.5
(E4-03)
E2-05
Motor L-L Resistance
Ω
0.138
0.101
0.101
0.079
(E4-05)
E2-06
Motor Leak Inductance
%
17.2
15.7
20.1
19.5
(E4-06)
E2-10
Motor Iron Loss
W
272
505
505
538
(E4-10)
PM Mot Code
E5-01
-
FFFF
FFFF
FFFF
FFFF
Selection
RideThrough
L2-02
s
2
2
2
2
Time@Power Loss
L2-03
Min Baseblck Time
s
1
1
1
1
Powloss Ramp
L2-04
s
0.6
0.6
0.6
0.6
Time@recovery
UV Detection Lvl
L2-05
-
190
190
190
190
(Uv1)
L3-02
StallP Level@Accel
%
150
120
150
120
L3-06
StallP Level@Run
%
150
120
150
120
L3-24
Acc@Rated Torque
s
0.244
0.317
0.317
0.355
L8-02
Overheat Alm Level
°C
120
120
135
135
L8-09
Ground Fault Selection
-
1
1
1
1
HuntPrev Time
n1-03
ms
10
10
10
10
Constant
n3-02
HSB CurrLim Level
%
150
120
150
120
Mot Inertia
n5-02
s
0.244
0.317
0.317
0.355
Acceleration Time
*1
Parameters within parentheses are for motor 2.
◆ Single-Phase 200 V Class
No. *1
Name
Unit
Default
-
Drive Model
-
B001
B002
B004
B006
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
30
31
32
33
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
0.1
0.2
0.2
0.4
0.4
0.75
0.75
1.1
Power (kW)
02)
11
SpSrch V/F
b3-04
%
100
100
100
100
100
100
100
100
Gain
Speed Curr
b3-06
Lev1 for
-
1
1
1
1
1
1
0.5
0.5
Estimation
413
11.20 Defaults by Drive Model and Duty Rating ND/HD
No. *1
Name
Unit
Default
-
Drive Model
-
B001
B002
B004
B006
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
30
31
32
33
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
0.1
0.2
0.2
0.4
0.4
0.75
0.75
1.1
Power (kW)
02)
Speed ACR
b3-08
PGain for
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Estimation
Dir. Determ.
b3-26
-
1000
1000
1000
1000
1000
1000
1000
1000
Level
eSave Filter
b8-03
s
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Time
eSave Coef.
b8-04
-
481.7
356.9
356.9
288.2
288.2
223.7
223.7
196.6
Value
Carrier
C6-02
Frequency
-
4
7
4
7
4
7
4
7
Selection
E2-01
Mot Rated
A
0.6
1.1
1.1
1.9
1.9
3.3
3.3
6.2
(E4-01)
Current (FLA)
E2-02
Mot Rated
Hz
2.5
2.6
2.6
2.9
2.9
2.5
2.5
2.6
(E4-02)
Slip
E2-03
Mot No-Load
A
0.4
0.8
0.8
1.2
1.2
1.8
1.8
2.8
(E4-03)
Current
E2-05
Motor L-L
Ω
35.98
20.56
20.56
9.842
9.842
5.156
5.156
1.997
(E4-05)
Resistance
E2-06
Motor Leak
%
21.6
20.1
20.1
18.2
18.2
13.8
13.8
18.5
(E4-06)
Inductance
E2-10
Motor Iron
W
6
11
11
14
14
26
26
53
(E4-10)
Loss
PM Mot Code
E5-01
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
Selection
RideThrough
L2-02
Time@Power
s
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
Loss
Min Baseblck
L2-03
s
0.2
0.3
0.2
0.3
0.2
0.3
0.3
0.4
Time
Powloss
Ramp
L2-04
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
Time@recov
ery
UV Detection
L2-05
-
160
160
160
160
160
160
160
160
Lvl (Uv1)
StallP
L3-02
%
150
120
150
120
150
120
150
120
Level@Accel
StallP
L3-06
%
150
120
150
120
150
120
150
120
Level@Run
Acc@Rated
L3-24
s
0.178
0.178
0.178
0.178
0.178
0.142
0.142
0.142
Torque
Overheat Alm
L8-02
°C
105
105
105
105
115
115
115
115
Level
Ground Fault
L8-09
-
0
0
0
0
0
0
0
0
Selection
HuntPrev
n1-03
ms
10
10
10
10
10
10
10
10
Time Constant
HSB CurrLim
n3-02
%
150
120
150
120
150
120
150
120
Level
Mot Inertia
n5-02
Acceleration
s
0.178
0.178
0.178
0.142
0.178
0.142
0.142
0.142
Time
*1
Parameters within parentheses are for motor
2.
414
11.20
Defaults by Drive Model and Duty Rating ND/HD
No. *1
Name
Unit
Default
-
Drive Model
-
B010
B012
B018
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
34
35
37
Selection
E2-11
Motor Rated
kW
1.5
2.2
2.2
3.0
3.7
5.5
(E4-11, E5-02)
Power (kW)
b3-04
SpSrch V/F Gain
%
100
100
100
100
100
100
Speed Curr Lev1
b3-06
-
0.5
0.5
0.5
0.5
0.5
0.5
for Estimation
Speed ACR
b3-08
PGain for
-
0.5
0.5
0.5
0.5
0.5
0.5
Estimation
Dir. Determ.
b3-26
-
1000
1000
1000
1000
1000
1000
Level
b8-03
eSave Filter Time
s
0.5
0.5
0.5
0.5
0.5
0.5
eSave Coef.
b8-04
-
169.4
156.8
156.8
136.4
122.9
94.75
Value
Carrier Frequency
C6-02
-
3
7
3
7
3
7
Selection
E2-01
Mot Rated
A
6.2
8.5
8.5
11.4
14
19.6
(E4-01)
Current (FLA)
E2-02
Mot Rated Slip
Hz
2.6
2.9
2.9
2.7
2.73
1.5
(E4-02)
E2-03
Mot No-Load
A
2.8
3
3
3.7
4.5
5.1
(E4-03)
Current
E2-05
Motor L-L
Ω
1.997
1.601
1.601
1.034
0.771
0.399
(E4-05)
Resistance
E2-06
Motor Leak
%
18.5
18.4
18.4
19
19.6
18.2
(E4-06)
Inductance
E2-10
Motor Iron Loss
W
53
77
77
91
112
172
(E4-10)
PM Mot Code
E5-01
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
Selection
RideThrough
L2-02
Time@Power
s
0.3
0.3
0.5
0.5
1
1
Loss
Min Baseblck
L2-03
s
0.4
0.5
0.5
0.5
0.6
0.7
Time
Powloss Ramp
L2-04
s
0.3
0.3
0.3
0.3
0.3
0.3
Time@recovery
UV Detection Lvl
L2-05
-
160
160
160
160
160
160
(Uv1)
StallP
L3-02
%
150
120
150
120
150
120
Level@Accel
StallP
L3-06
%
150
120
150
120
150
120
Level@Run
Acc@Rated
L3-24
s
0.166
0.145
0.145
0.145
0.154
0.168
Torque
Overheat Alm
L8-02
°C
105
105
110
110
115
115
Level
Ground Fault
L8-09
-
0
0
0
0
0
0
Selection
HuntPrev Time
n1-03
ms
10
10
10
10
10
10
Constant
HSB CurrLim
n3-02
%
150
120
150
120
150
120
Level
Mot Inertia
n5-02
Acceleration
s
0.166
0.145
0.145
0.145
0.154
0.168
11
Time
*1
Parameters within parentheses are for motor 2.
415
11.20 Defaults by Drive Model and Duty Rating ND/HD
◆ Three-Phase
400
V Class
No. *1
Name
Unit
Default
-
Drive Model
-
4001
4002
4004
4005
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
91
92
93
94
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
0.2
0.4
0.4
0.75
0.75
1.5
1.5
2.2
Power (kW)
02)
SpSrch V/F
b3-04
%
100
100
100
100
100
100
100
100
Gain
Speed Curr
b3-06
Lev1 for
-
1.0
1.0
0.5
0.5
0.5
0.5
0.5
0.5
Estimation
Speed ACR
b3-08
PGain for
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Estimation
Dir. Determ.
b3-26
-
1000
1000
1000
1000
1000
1000
1000
1000
Level
eSave Filter
b8-03
s
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Time
eSave Coef.
b8-04
-
713.8
576.4
576.4
447.4
447.4
338.8
338.8
313.6
Value
Carrier
C6-02
Frequency
-
3
7
3
7
3
7
3
7
Selection
E2-01
Mot Rated
A
0.6
1
1
1.6
1.6
3.1
3.1
4.2
(E4-01)
Current (FLA)
E2-02
Mot Rated
Hz
2.5
2.9
2.9
2.6
2.6
2.5
2.5
3
(E4-02)
Slip
E2-03
Mot No-Load
A
0.4
0.6
0.6
0.8
0.8
1.4
1.4
1.5
(E4-03)
Current
E2-05
Motor L-L
Ω
83.94
38.198
38.198
22.459
22.459
10.1
10.1
6.495
(E4-05)
Resistance
E2-06
Motor Leak
%
21.9
18.2
18.2
14.3
14.3
18.3
18.3
18.7
(E4-06)
Inductance
E2-10
Motor Iron
W
12
14
14
26
26
53
53
77
(E4-10)
Loss
PM Mot Code
E5-01
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
Selection
RideThrough
L2-02
Time@Power
s
0.1
0.1
0.1
0.1
0.2
0.2
0.3
0.3
Loss
Min Baseblck
L2-03
s
0.2
0.2
0.2
0.3
0.3
0.4
0.4
0.5
Time
Powloss
Ramp
L2-04
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
Time@recov
ery
UV Detection
L2-05
-
380
380
380
380
380
380
380
380
Lvl (Uv1)
StallP
L3-02
%
150
120
150
120
150
120
150
120
Level@Accel
StallP
L3-06
%
150
120
150
120
150
120
150
120
Level@Run
Acc@Rated
L3-24
s
0.178
0.178
0.178
0.142
0.142
0.166
0.166
0.145
Torque
Overheat Alm
L8-02
°C
120
120
120
120
105
105
90
90
Level
Ground Fault
L8-09
-
0
0
0
0
0
0
0
0
Selection
HuntPrev
n1-03
ms
10
10
10
10
10
10
10
10
Time Constant
416
11.20 Defaults by Drive Model and Duty Rating ND/HD
No. *1
Name
Unit
Default
-
Drive Model
-
4001
4002
4004
4005
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
91
92
93
94
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
0.2
0.4
0.4
0.75
0.75
1.5
1.5
2.2
Power (kW)
02)
HSB CurrLim
n3-02
%
150
120
150
120
150
120
150
120
Level
Mot Inertia
n5-02
Acceleration
s
0.178
0.178
0.178
0.142
0.142
0.166
0.166
0.145
Time
*1
Parameters within parentheses are for motor 2.
No. *1
Name
Unit
Default
-
Drive Model
-
4007
4009
4012
4018
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
95
96
97
99
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
2.2
3.0
3.0
3.7
4.0
5.5
5.5
7.5
Power (kW)
02)
SpSrch V/F
b3-04
%
100
100
100
100
100
100
100
100
Gain
Speed Curr
b3-06
Lev1 for
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Estimation
Speed ACR
b3-08
PGain for
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Estimation
Dir. Determ.
b3-26
-
1000
1000
1000
1000
1000
1000
1000
1000
Level
eSave Filter
b8-03
s
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Time
eSave Coef.
b8-04
-
313.6
265.7
265.7
245.8
245.8
189.5
189.5
145.38
Value
Carrier
C6-02
Frequency
-
3
7
3
7
3
7
3
7
Selection
E2-01
Mot Rated
A
4.2
5.7
5.7
7
7
9.8
9.8
13.3
(E4-01)
Current (FLA)
E2-02
Mot Rated
Hz
3
2.7
2.7
2.7
2.7
1.5
1.5
1.3
(E4-02)
Slip
E2-03
Mot No-Load
A
1.5
1.9
1.9
2.3
2.3
2.6
2.6
4
(E4-03)
Current
E2-05
Motor L-L
Ω
6.495
4.36
4.36
3.333
3.333
1.595
1.595
1.152
(E4-05)
Resistance
E2-06
Motor Leak
%
18.7
19
19
19.3
19.3
18.2
18.2
15.5
(E4-06)
Inductance
E2-10
Motor Iron
W
77
105
105
130
130
193
193
263
(E4-10)
Loss
PM Mot Code
E5-01
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
Selection
RideThrough
L2-02
Time@Power
s
0.5
0.5
0.5
0.5
0.5
0.5
0.8
0.8
Loss
Min Baseblck
11
L2-03
s
0.5
0.5
0.5
0.6
0.6
0.7
0.7
0.8
Time
Powloss
Ramp
L2-04
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
Time@recov
ery
417
11.20 Defaults by Drive Model and Duty Rating ND/HD
No. *1
Name
Unit
Default
-
Drive Model
-
4007
4009
4012
4018
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
95
96
97
99
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
2.2
3.0
3.0
3.7
4.0
5.5
5.5
7.5
Power (kW)
02)
UV Detection
L2-05
-
380
380
380
380
380
380
380
380
Lvl (Uv1)
StallP
L3-02
%
150
120
150
120
150
120
150
120
Level@Accel
StallP
L3-06
%
150
120
150
120
150
120
150
120
Level@Run
Acc@Rated
L3-24
s
0.145
0.145
0.145
0.154
0.154
0.168
0.168
0.175
Torque
Overheat Alm
L8-02
°C
90
90
115
115
110
110
120
120
Level
Ground Fault
L8-09
-
0
0
0
0
0
0
0
0
Selection
HuntPrev
n1-03
ms
10
10
10
10
10
10
10
10
Time Constant
HSB CurrLim
n3-02
%
150
120
150
120
150
120
150
120
Level
Mot Inertia
n5-02
Acceleration
s
0.145
0.145
0.145
0.154
0.154
0.168
0.168
0.175
Time
*1
Parameters within parentheses are for motor 2.
No. *1
Name
Unit
Default
-
Drive Model
-
4023
4031
4038
4044
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
9A
9C
9D
9E
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
7.5
11
11
15
15
18.5
18.5
22
Power (kW)
02)
SpSrch V/F
b3-04
%
100
100
100
100
100
100
100
100
Gain
Speed Curr
b3-06
Lev1 for
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Estimation
Speed ACR
b3-08
PGain for
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Estimation
Dir. Determ.
b3-26
-
1000
1000
1000
1000
1000
1000
1000
1000
Level
eSave Filter
b8-03
s
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
Time
eSave Coef.
b8-04
-
145.38
140.88
140.88
126.26
126.26
115.74
115.74
103.58
Value
Carrier
C6-02
Frequency
-
3
7
3
7
3
7
3
7
Selection
E2-01
Mot Rated
A
13.3
19.9
19.9
26.5
26.5
32.9
32.9
38.6
(E4-01)
Current (FLA)
E2-02
Mot Rated
Hz
1.3
1.7
1.7
1.6
1.6
1.67
1.67
1.7
(E4-02)
Slip
E2-03
Mot No-Load
A
4
5.6
5.6
7.6
7.6
7.8
7.8
9.2
(E4-03)
Current
E2-05
Motor L-L
Ω
1.152
0.922
0.922
0.55
0.55
0.403
0.403
0.316
(E4-05)
Resistance
418
11.20
Defaults by Drive Model and Duty Rating ND/HD
No. *1
Name
Unit
Default
-
Drive Model
-
4023
4031
4038
4044
HD
ND
HD
ND
HD
ND
HD
ND
ND/HD Duty
C6-01
-
Selection
0
1
0
1
0
1
0
1
Drive KVA
o2-04
Hex.
9A
9C
9D
9E
Selection
E2-11
Motor Rated
(E4-11, E5-
kW
7.5
11
11
15
15
18.5
18.5
22
Power (kW)
02)
E2-06
Motor Leak
%
15.5
19.6
19.6
17.2
17.2
20.1
20.1
23.5
(E4-06)
Inductance
E2-10
Motor Iron
W
263
385
385
440
440
508
508
586
(E4-10)
Loss
PM Mot Code
E5-01
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
Selection
RideThrough
L2-02
Time@Power
s
1
1
2
2
2
2
2
2
Loss
Min Baseblck
L2-03
s
0.8
0.9
0.9
1
1
1
1
1
Time
Powloss
Ramp
L2-04
s
0.3
0.3
0.3
0.6
0.6
0.6
0.6
0.6
Time@recov
ery
UV Detection
L2-05
-
380
380
380
380
380
380
380
380
Lvl (Uv1)
StallP
L3-02
%
150
120
150
120
150
120
150
120
Level@Accel
StallP
L3-06
%
150
120
150
120
150
120
150
120
Level@Run
Acc@Rated
L3-24
s
0.175
0.265
0.265
0.244
0.244
0.317
0.317
0.355
Torque
Overheat Alm
L8-02
°C
120
120
120
120
120
120
125
125
Level
Ground Fault
L8-09
-
0
0
1
1
1
1
1
1
Selection
HuntPrev
n1-03
ms
10
10
10
10
10
10
10
10
Time Constant
HSB CurrLim
n3-02
%
150
120
150
120
150
120
150
120
Level
Mot Inertia
n5-02
Acceleration
s
0.175
0.265
0.265
0.244
0.244
0.317
0.317
0.355
Time
*1
Parameters within parentheses are for motor 2.
No. *1
Name
Unit
Default
-
Drive Model
-
4060
HD
ND
C6-01
ND/HD Duty Selection
-
0
1
o2-04
Drive KVA Selection
Hex.
9F
E2-11
Motor Rated Power (kW)
kW
22
30
(E4-11, E5-02)
b3-04
SpSrch V/F Gain
%
100
100
b3-06
Speed Curr Lev1 for Estimation
-
0.5
0.5
b3-08
Speed ACR PGain for Estimation
-
0.5
0.5
b3-26
Dir. Determ. Level
-
1000
1000
b8-03
eSave Filter Time
s
0.5
0.5
b8-04
eSave Coef. Value
-
103.58
92.54
11
C6-02
Carrier Frequency Selection
-
3
7
E2-01
Mot Rated Current (FLA)
A
38.6
52.3
(E4-01)
419
11.20 Defaults by Drive Model and Duty Rating ND/HD
No. *1
Name
Unit
Default
-
Drive Model
-
4060
HD
ND
C6-01
ND/HD Duty Selection
-
0
1
o2-04
Drive KVA Selection
Hex.
9F
E2-11
Motor Rated Power (kW)
kW
22
30
(E4-11, E5-02)
E2-02
Mot Rated Slip
Hz
1.7
1.8
(E4-02)
E2-03
Mot No-Load Current
A
9.2
10.9
(E4-03)
E2-05
Motor L-L Resistance
Ω
0.316
0.269
(E4-05)
E2-06
Motor Leak Inductance
%
23.5
20.7
(E4-06)
E2-10
Motor Iron Loss
W
586
750
(E4-10)
E5-01
PM Mot Code Selection
-
FFFF
FFFF
L2-02
RideThrough Time@Power Loss
s
2
2
L2-03
Min Baseblck Time
s
1
1.1
L2-04
Powloss Ramp Time@recovery
s
0.6
0.6
L2-05
UV Detection Lvl (Uv1)
-
380
380
L3-02
StallP Level@Accel
%
150
120
L3-06
StallP Level@Run
%
150
120
L3-24
Acc@Rated Torque
s
0.355
0.323
L8-02
Overheat Alm Level
°C
115
115
L8-09
Ground Fault Selection
-
1
1
n1-03
HuntPrev Time Constant
ms
10
10
n3-02
HSB CurrLim Level
%
150
120
n5-02
Mot Inertia Acceleration Time
s
0.355
0.323
*1
Parameters within parentheses are for motor 2.
420
11.21 Parameters Changed by PM Motor Code Selection
11.21
Parameters Changed by PM Motor Code Selection
Note:
The motor codes listed in these tables are the only correct setting values.
◆ Yaskawa SMRA Series SPM Motors
Table 11.5 SMRA Series Motor Code Setting for Specification of 200 V at 1800 min-1 (r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
0002
0003
0005
0006
0008
Voltage Class
V
200
200
200
200
200
E5-01
Capacity
kW
0.4
0.75
1.5
2.2
3.7
Motor Rotation Speed
min-1
1800
1800
1800
1800
1800
E5-02
PM Mot Rated Power (kW)
kW
0.4
0.75
1.5
2.2
3.7
PM Mot Rated Current
E5-03
A
2.1
4.0
6.9
10.8
17.4
(FLA)
E5-04
PM Mot Pole Count
-
8
8
8
8
8
PM Mot Resistance (Ohms/
E5-05
Ω
2.47
1.02
0.679
0.291
0.169
Phase)
PM d-Axis Inductance (mH/
E5-06
mH
12.7
4.8
3.9
3.6
2.5
Phase)
PM q-Axis Inductance (mH/
E5-07
mH
12.7
4.8
3.9
3.6
2.5
Phase)
PM BackEMF Vpeak (mV/
E5-09
mVs/rad
0
0
0
0
0
(rad/ s))
PM BackEMF L-L Vrms
E5-24
mV/min-1
62.0
64.1
73.4
69.6
72.2
(mV/rpm)
E1-04
Max Output Frequency
Hz
120
120
120
120
120
E1-05
Max Output Voltage
V
200.0
200.0
200.0
200.0
200.0
E1-06
Base Frequency
Hz
120
120
120
120
120
E1-09
Min Output Frequency
Hz
6
6
6
6
6
L3-24
Acc@Rated Torque
s
0.064
0.066
0.049
0.051
0.044
Mot Inertia Acceleration
n5-02
s
0.064
0.066
0.049
0.051
0.044
Time
n8-49
Heavy Load Id Current
%
0
0
0
0
0
Table 11.6 SMRA Series Motor Code Setting for Specification of 200 V at 3600
min-1 (r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
0103
0105
0106
0108
Voltage Class
V
200
200
200
200
E5-01
Capacity
kW
0.75
1.5
2.2
3.7
Motor Rotation Speed
min-1
3600
3600
3600
3600
E5-02
PM Mot Rated Power (kW)
kW
0.75
1.5
2.2
3.7
PM Mot Rated Current
E5-03
A
4.1
8.0
10.5
16.5
(FLA)
E5-04
PM Mot Pole Count
-
8
8
8
8
PM Mot Resistance (Ohms/
E5-05
Ω
0.538
0.20
0.15
0.097
Phase)
PM d-Axis Inductance (mH/
E5-06
mH
3.2
1.3
1.1
1.1
Phase)
PM q-Axis Inductance (mH/
E5-07
mH
3.2
1.3
1.1
1.1
Phase)
PM BackEMF Vpeak (mV/
E5-09
mVs/rad
0
0
0
0
(rad/ s))
11
PM BackEMF L-L Vrms
E5-24
mV/min-1
32.4
32.7
36.7
39.7
(mV/rpm)
E1-04
Max Output Frequency
Hz
240
240
240
240
E1-05
Max Output Voltage
V
200.0
200.0
200.0
200.0
421
11.21 Parameters Changed by PM Motor Code Selection
No.
Name
Unit
Motor Code (setting value of E5-01)
E1-06
Base Frequency
Hz
240
240
240
240
E1-09
Min Output Frequency
Hz
12
12
12
12
L3-24
Acc@Rated Torque
s
0.137
0.132
0.132
0.122
Mot Inertia Acceleration
n5-02
s
0.137
0.132
0.132
0.122
Time
n8-49
Heavy Load Id Current
%
0
0
0
0
◆ Yaskawa SMRD Series SPM Motors
Table 11.7 SMRD Series Motor Code Setting for Specification of 200 V at 1800 min-1 (r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
3000
3001
3002
Voltage Class
V
200
200
200
E5-01
Capacity
kW
0.1
0.2
0.4
Motor Rotation Speed
min-1
1800
1800
1800
E5-02
PM Mot Rated Power (kW)
kW
0.1
0.2
0.4
E5-03
PM Mot Rated Current (FLA)
A
0.64
1
1.9
E5-04
PM Mot Pole Count
-
6
6
6
E5-05
PM Mot Resistance (Ohms/Phase)
Ω
17.200
9.960
3.590
E5-06
PM d-Axis Inductance (mH/Phase)
mH
33.20
19.40
11.90
E5-07
PM q-Axis Inductance (mH/Phase)
mH
33.20
19.40
11.90
E5-09
PM BackEMF Vpeak (mV/(rad/ s))
mVs/rad
0.0
0.0
0.0
E5-24
PM BackEMF L-L Vrms (mV/rpm)
mV/min-1
59.1
69.8
75.9
E1-04
Max Output Frequency
Hz
90.0
90.0
90.0
E1-05
Max Output Voltage
V
200.0
200.0
200.0
E1-06
Base Frequency
Hz
90.0
90.0
90.0
E1-09
Min Output Frequency
Hz
9.0
9.0
9.0
L3-24
Acc@Rated Torque
s
0.100
0.100
0.100
n5-02
Mot Inertia Acceleration Time
s
0.100
0.100
0.100
n8-49
Heavy Load Id Current
%
0.0
0.0
0.0
Table 11.8 SMRD Series Motor Code Setting for Specification of 200 V at 3600 min-1 (r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
3101
3102
3103
Voltage Class
V
200
200
200
E5-01
Capacity
kW
0.2
0.4
0.75
Motor Rotation Speed
min-1
3600
3600
3600
E5-02
PM Mot Rated Power (kW)
kW
0.20
0.40
0.75
E5-03
PM Mot Rated Current (FLA)
A
1.50
2.60
4.20
E5-04
PM Mot Pole Count
-
6
6
6
E5-05
PM Mot Resistance (Ohms/Phase)
Ω
3.340
1.560
0.541
E5-06
PM d-Axis Inductance (mH/Phase)
mH
6.58
3.82
2.24
E5-07
PM q-Axis Inductance (mH/Phase)
mH
6.58
3.82
2.24
PM BackEMF Vpeak (mV/(rad/
0.0
0.0
0.0
E5-09
mVs/rad
s))
PM BackEMF L-L Vrms (mV/
26.3
31.0
32.9
E5-24
mV/min-1
rpm)
E1-04
Max Output Frequency
Hz
180.0
180.0
180.0
E1-05
Max Output Voltage
V
200.0
200.0
200.0
E1-06
Base Frequency
Hz
180.0
180.0
180.0
422
11.21 Parameters Changed by PM Motor Code Selection
No.
Name
Unit
Motor Code (setting value of E5-01)
E1-09
Min Output Frequency
Hz
18.0
18.0
18.0
L3-24
Acc@Rated Torque
s
0.100
0.100
0.100
n5-02
Mot Inertia Acceleration Time
s
0.100
0.100
0.100
n8-49
Heavy Load Id Current
%
0.0
0.0
0.0
◆ Yaskawa SSR1 Series IPM Motors (Derated Torque)
Table 11.9 SSR1 Series Motor Code Setting for Specification of 200 V at 1750 min-1 (r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
1202
1203
1205
1206
1208
120A
Voltage Class
V
200
200
200
200
200
200
E5-01
Capacity
kW
0.4
0.75
1.5
2.2
3.7
5.5
Motor Rotation Speed
min-1
1750
1750
1750
1750
1750
1750
E5-02
PM Mot Rated Power (kW)
kW
0.4
0.75
1.5
2.2
3.7
5.5
E5-03
PM Mot Rated Current (FLA)
A
1.77
3.13
5.73
8.44
13.96
20.63
E5-04
PM Mot Pole Count
-
6
6
6
6
6
6
PM Mot Resistance (Ohms/
E5-05
Ω
8.233
2.284
1.470
0.827
0.455
0.246
Phase)
PM d-Axis Inductance (mH/
E5-06
mH
54.84
23.02
17.22
8.61
7.20
4.86
Phase)
PM q-Axis Inductance (mH/
E5-07
mH
64.10
29.89
20.41
13.50
10.02
7.43
Phase)
PM BackEMF Vpeak (mV/
E5-09
mVs/rad
223.7
220.3
240.8
238.0
238.7
239.6
(rad/ s))
PM BackEMF L-L Vrms
E5-24
mV/min-1
0.0
0.0
0.0
0.0
0.0
0.0
(mV/rpm)
E1-04
Max Output Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Max Output Voltage
V
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Min Output Frequency
Hz
4.4
4.4
4.4
4.4
4.4
4.4
L3-24
Acc@Rated Torque
s
0.092
0.076
0.051
0.066
0.075
0.083
*1
Mot Inertia Acceleration
n5-02
s
0.092
0.076
0.051
0.066
0.075
0.083
Time
n8-49
Heavy Load Id Current
%
-7.6
-11.5
-9.1
-19.0
-18.7
-23.4
*1
The default setting changes when the setting for o2-04 [Drive KVA Selection] changes.
Table 11.10 SSR1 Series Motor Code Setting for Specification of 200 V at 1750
min
-1
(r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
120B
120D
120E
120F
1210
Voltage Class
V
200
200
200
200
200
E5-01
Capacity
kW
7.5
11
15
18.5
22
Motor Rotation Speed
min-1
1750
1750
1750
1750
1750
E5-02
PM Mot Rated Power (kW)
kW
7.5
11.0
15.00
18.50
22.00
E5-03
PM Mot Rated Current (FLA)
A
28.13
41.4
55.4
68.2
80.6
E5-04
PM Mot Pole Count
-
6
6
6
6
6
PM Mot Resistance (Ohms/
E5-05
Ω
0.198
0.094
0.066
0.051
0.037
Phase)
PM d-Axis Inductance (mH/
E5-06
mH
4.15
3.40
2.45
2.18
1.71
Phase)
11
PM q-Axis Inductance (mH/
E5-07
mH
5.91
3.91
3.11
2.55
2.05
Phase)
PM BackEMF Vpeak (mV/(rad/
E5-09
mVs/rad
258.2
239.3
248.1
253.6
250.0
s))
423
11.21 Parameters Changed by PM Motor Code Selection
No.
Name
Unit
Motor Code (setting value of E5-01)
PM BackEMF L-L Vrms (mV/
E5-24
mV/min-1
0.0
0.0
0.0
0.0
0.0
rpm)
E1-04
Max Output Frequency
Hz
87.5
87.5
87.5
87.5
87.5
E1-05
Max Output Voltage
V
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
E1-09
Min Output Frequency
Hz
4.4
4.4
4.4
4.4
4.4
L3-24
Acc@Rated Torque
s
0.077
0.084
0.102
0.101
0.098
*1
n5-02
Mot Inertia Acceleration Time
s
0.077
0.084
0.102
0.101
0.098
n8-49
Heavy Load Id Current
%
-18.5
-10.9
-16.5
-11.3
-12.8
*1
The default setting changes when the setting for o2-04 [Drive KVA Selection] changes.
Table 11.11 SSR1 Series Motor Code Setting for Specification of 400 V at 1750 min-1 (r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
1232
1233
1235
1236
1238
123A
Voltage Class
V
400
400
400
400
400
400
E5-01
Capacity
kW
0.4
0.75
1.5
2.2
3.7
5.5
Motor Rotation Speed
min-1
1750
1750
1750
1750
1750
1750
E5-02
PM Mot Rated Power (kW)
kW
0.4
0.75
1.5
2.2
3.7
5.5
E5-03
PM Mot Rated Current (FLA)
A
0.89
1.56
2.81
4.27
7.08
10.31
E5-04
PM Mot Pole Count
-
6
6
6
6
6
6
PM Mot Resistance (Ohms/
E5-05
Ω
25.370
9.136
6.010
3.297
1.798
0.982
Phase)
PM d-Axis Inductance (mH/
E5-06
mH
169.00
92.08
67.71
34.40
32.93
22.7
Phase)
PM q-Axis Inductance (mH/
E5-07
mH
197.50
119.56
81.71
54.00
37.70
26.80
Phase)
PM BackEMF Vpeak (mV/
E5-09
mVs/rad
392.6
440.6
478.3
466.3
478.8
478.1
(rad/ s))
PM BackEMF L-L Vrms
E5-24
mV/min-1
0.0
0.0
0.0
0.0
0.0
0.0
(mV/rpm)
E1-04
Max Output Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Max Output Voltage
V
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Min Output Frequency
Hz
4.4
4.4
4.4
4.4
4.4
4.4
L3-24
Acc@Rated Torque
s
0.092
0.076
0.051
0.066
0.075
0.083
*1
Mot Inertia Acceleration
n5-02
s
0.092
0.076
0.051
0.066
0.075
0.083
Time
n8-49
Heavy Load Id Current
%
-8.6
-11.5
-10.3
-19.8
-8.5
-11.0
*1
The default setting changes when the setting for o2-04 [Drive KVA Selection] changes.
Table 11.12 SSR1 Series Motor Code Setting for Specification of 400
V at 1750 min
-1
(r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
123B
123D
123E
123F
1240
1242
Voltage Class
V
400
400
400
400
400
400
E5-01
Capacity
kW
7.5
11
15
18.5
22
30
Motor Rotation Speed
min-1
1750
1750
1750
1750
1750
1750
E5-02
PM Mot Rated Power (kW)
kW
7.5
11.0
15
18.50
22.00
30.00
E5-03
PM Mot Rated Current (FLA)
A
13.65
20.7
27.5
33.4
39.8
52.0
E5-04
PM Mot Pole Count
-
6
6
6
6
6
6
PM Mot Resistance (Ohms/
E5-05
Ω
0.786
0.349
0.272
0.207
0.148
0.235
Phase)
424
11.21 Parameters Changed by PM Motor Code Selection
No.
Name
Unit
Motor Code (setting value of E5-01)
PM d-Axis Inductance (mH/
E5-06
mH
16.49
13.17
10.30
8.72
6.81
5.4
Phase)
PM q-Axis Inductance (mH/
E5-07
mH
23.46
15.60
12.77
11.22
8.47
7.26
Phase)
PM BackEMF Vpeak (mV/
E5-09
mVs/rad
520.0
481.5
498.8
509.5
503.9
561.7
(rad/ s))
PM BackEMF L-L Vrms
E5-24
mV/min-1
0.0
0.0
0.0
0.0
0.0
0.0
(mV/rpm)
E1-04
Max Output Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Max Output Voltage
V
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Min Output Frequency
Hz
4.4
4.4
4.4
4.4
4.4
4.4
L3-24
Acc@Rated Torque
s
0.077
0.084
0.102
0.101
0.098
0.130
*1
Mot Inertia Acceleration
n5-02
s
0.077
0.084
0.102
0.101
0.098
0.130
Time
n8-49
Heavy Load Id Current
%
-18.6
-12.5
-15.5
-17.9
-15.1
-16.8
*1
The default setting changes when the setting for o2-04 [Drive KVA Selection] changes.
Table 11.13 SSR1 Series Motor Code Setting for Specification of 200 V at 1450 min-1 (r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
1302
1303
1305
1306
1308
130A
Voltage Class
V
200
200
200
200
200
200
E5-01
Capacity
kW
0.4
0.75
1.5
2.2
3.7
5.5
Motor Rotation Speed
min-1
1450
1450
1450
1450
1450
1450
E5-02
PM Mot Rated Power (kW)
kW
0.4
0.75
1.5
2.2
3.7
5.5
E5-03
PM Mot Rated Current (FLA)
A
1.88
3.13
5.63
8.33
14.17
20.63
E5-04
PM Mot Pole Count
-
6
6
6
6
6
6
PM Mot Resistance (Ohms/
E5-05
Ω
3.190
1.940
1.206
0.665
0.341
0.252
Phase)
PM d-Axis Inductance (mH/
E5-06
mH
32.15
26.12
14.72
12.27
8.27
6.49
Phase)
PM q-Axis Inductance (mH/
E5-07
mH
41.74
34.30
20.15
14.77
9.81
7.74
Phase)
PM BackEMF Vpeak (mV/
E5-09
mVs/rad
264.3
269.6
284.3
287.1
284.5
298.0
(rad/ s))
PM BackEMF L-L Vrms
E5-24
mV/min-1
0.0
0.0
0.0
0.0
0.0
0.0
(mV/rpm)
E1-04
Max Output Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Max Output Voltage
V
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Min Output Frequency
Hz
3.6
3.6
3.6
3.6
3.6
3.6
L3-24
Acc@Rated Torque
s
0.098
0.071
0.066
0.087
0.085
0.072
*1
Mot Inertia Acceleration
n5-02
s
0.098
0.071
0.066
0.087
0.085
0.072
Time
n8-49
Heavy Load Id Current
%
-6.6
-10.9
-13.5
-9.0
-9.5
-10.1
*1
The default setting changes when the setting for o2-04 [Drive KVA Selection] changes.
Table 11.14 SSR1 Series Motor Code Setting for Specification of 200 V at 1450
min
-1
(r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
130B
130D
130E
130F
1310
11
Voltage Class
V
200
200
200
200
200
E5-01
Capacity
kW
7.5
11
15
18.5
22
Motor Rotation Speed
min-1
1450
1450
1450
1450
1450
E5-02
PM Mot Rated Power (kW)
kW
7.5
11.0
15.00
18.50
22.00
425
11.21 Parameters Changed by PM Motor Code Selection
No.
Name
Unit
Motor Code (setting value of E5-01)
E5-03
PM Mot Rated Current (FLA)
A
27.71
39.6
55.5
65.6
75.1
E5-04
PM Mot Pole Count
-
6
6
6
6
6
PM Mot Resistance (Ohms/
E5-05
Ω
0.184
0.099
0.075
0.057
0.041
Phase)
PM d-Axis Inductance (mH/
E5-06
mH
6.91
4.07
3.29
2.53
1.98
Phase)
PM q-Axis Inductance (mH/
E5-07
mH
7.66
4.65
3.84
3.01
2.60
Phase)
PM BackEMF Vpeak (mV/(rad/
E5-09
mVs/rad
335.0
303.9
311.2
300.9
327.7
s))
PM BackEMF L-L Vrms (mV/
E5-24
mV/min-1
0.0
0.0
0.0
0.0
0.0
rpm)
E1-04
Max Output Frequency
Hz
72.5
72.5
72.5
72.5
72.5
E1-05
Max Output Voltage
V
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
E1-09
Min Output Frequency
Hz
3.6
3.6
3.6
3.6
3.6
L3-24
Acc@Rated Torque
s
0.084
0.096
0.085
0.080
0.122
*1
n5-02
Mot Inertia Acceleration Time
s
0.084
0.096
0.085
0.080
0.122
n8-49
Heavy Load Id Current
%
-6.0
-9.3
-10.7
-13.2
-15.7
*1
The default setting changes when the setting for o2-04 [Drive KVA Selection] changes.
Table 11.15 SSR1 Series Motor Code Setting for Specification of 400 V at 1450 min-1 (r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
1332
1333
1335
1336
1338
133A
Voltage Class
V
400
400
400
400
400
400
E5-01
Capacity
kW
0.4
0.75
1.5
2.2
3.7
5.5
Motor Rotation Speed
min-1
1450
1450
1450
1450
1450
1450
E5-02
PM Mot Rated Power (kW)
kW
0.4
0.75
1.5
2.2
3.7
5.5
E5-03
PM Mot Rated Current (FLA)
A
0.94
1.56
2.81
4.27
6.98
10.21
E5-04
PM Mot Pole Count
-
6
6
6
6
6
6
PM Mot Resistance (Ohms/
E5-05
Ω
12.760
7.421
4.825
2.656
1.353
0.999
Phase)
PM d-Axis Inductance (mH/
E5-06
mH
128.60
85.11
58.87
46.42
31.73
26.20
Phase)
PM q-Axis Inductance (mH/
E5-07
mH
166.96
113.19
80.59
60.32
40.45
30.94
Phase)
PM BackEMF Vpeak (mV/
E5-09
mVs/rad
528.6
544.2
568.5
572.8
562.9
587.6
(rad/ s))
PM BackEMF L-L Vrms
E5-24
mV/min-1
0.0
0.0
0.0
0.0
0.0
0.0
(mV/rpm)
E1-04
Max Output Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Max Output Voltage
V
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Min Output Frequency
Hz
3.6
3.6
3.6
3.6
3.6
3.6
L3-24
Acc@Rated Torque
s
0.098
0.071
0.066
0.087
0.085
0.072
*1
Mot Inertia Acceleration
n5-02
s
0.098
0.071
0.066
0.087
0.085
0.072
Time
n8-49
Heavy Load Id Current
%
-6.6
-9.2
-13.5
-12.1
-13.7
-10.1
*1
The default setting changes when the setting for o2-04 [Drive KVA Selection] changes.
426
11.21 Parameters Changed by PM Motor Code Selection
Table 11.16 SSR1 Series Motor Code Setting for Specification of 400 V at 1450 min-1 (r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
133B
133D
133E
133F
1340
1342
Voltage Class
V
400
400
400
400
400
400
E5-01
Capacity
kW
7.5
11
15
18.5
22
30
Motor Rotation Speed
min-1
1450
1450
1450
1450
1450
1450
E5-02
PM Mot Rated Power (kW)
kW
7.5
11.0
15
18.50
22.00
30.00
E5-03
PM Mot Rated Current (FLA)
A
13.85
19.5
27.4
32.9
37.6
52.5
E5-04
PM Mot Pole Count
-
6
6
6
6
6
6
PM Mot Resistance (Ohms/
E5-05
Ω
0.713
0.393
0.295
0.223
0.164
0.137
Phase)
PM d-Axis Inductance (mH/
E5-06
mH
27.06
15.51
12.65
9.87
7.90
7.01
Phase)
PM q-Axis Inductance (mH/
E5-07
mH
33.45
19.63
15.87
12.40
10.38
8.68
Phase)
PM BackEMF Vpeak (mV/
E5-09
mVs/rad
670.1
612.7
624.6
610.4
655.4
708.4
(rad/ s))
PM BackEMF L-L Vrms
E5-24
mV/min-1
0.0
0.0
0.0
0.0
0.0
0.0
(mV/rpm)
E1-04
Max Output Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
E1-05
Max Output Voltage
V
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
72.5
72.5
72.5
72.5
72.5
72.5
E1-09
Min Output Frequency
Hz
3.6
3.6
3.6
3.6
3.6
3.6
L3-24
Acc@Rated Torque
s
0.084
0.096
0.085
0.080
0.122
0.108
*1
Mot Inertia Acceleration
n5-02
s
0.084
0.096
0.085
0.080
0.122
0.108
Time
n8-49
Heavy Load Id Current
%
-12.2
-15.5
-15.1
-16.0
-15.7
-11.5
*1
The default setting changes when the setting for o2-04 [Drive KVA Selection] changes.
-1
Table 11.17 SSR1 Series Motor Code Setting for Specification of 200
V at 1150 min
(r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
1402
1403
1405
1406
1408
140A
Voltage Class
V
200
200
200
200
200
200
E5-01
Capacity
kW
0.4
0.75
1.5
2.2
3.7
5.5
Motor Rotation Speed
min-1
1150
1150
1150
1150
1150
1150
E5-02
PM Mot Rated Power (kW)
kW
0.4
0.75
1.5
2.2
3.7
5.5
E5-03
PM Mot Rated Current (FLA)
A
1.88
3.02
6.00
8.85
14.27
20.21
E5-04
PM Mot Pole Count
-
6
6
6
6
6
6
PM Mot Resistance (Ohms/
E5-05
Ω
4.832
2.704
1.114
0.511
0.412
0.303
Phase)
PM d-Axis Inductance (mH/
E5-06
mH
48.68
32.31
19.22
12.15
7.94
11.13
Phase)
PM q-Axis Inductance (mH/
E5-07
mH
63.21
40.24
24.38
15.35
11.86
14.06
Phase)
PM BackEMF Vpeak (mV/
E5-09
mVs/rad
320.4
327.1
364.4
344.4
357.5
430.8
(rad/ s))
PM BackEMF L-L Vrms
E5-24
mV/min-1
0.0
0.0
0.0
0.0
0.0
0.0
(mV/rpm)
E1-04
Max Output Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Max Output Voltage
V
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
11
E1-09
Min Output Frequency
Hz
2.9
2.9
2.9
2.9
2.9
2.9
L3-24
Acc@Rated Torque
s
0.062
0.044
0.080
0.090
0.067
0.072
*1
427
11.21 Parameters Changed by PM Motor Code Selection
No.
Name
Unit
Motor Code (setting value of E5-01)
Mot Inertia Acceleration
n5-02
s
0.062
0.044
0.080
0.090
0.067
0.072
Time
n8-49
Heavy Load Id Current
%
-8.8
-9.9
-9.3
-10.0
-17.7
-12.3
*1
The default setting changes when the setting for o2-04 [Drive KVA Selection] changes.
Table 11.18 SSR1 Series Motor Code Setting for Specification of
200 V at 1150 min-1 (r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
140B
140D
140E
140F
1410
Voltage Class
V
200
200
200
200
200
E5-01
Capacity
kW
7.5
11
15
18.5
22
Motor Rotation Speed
min-1
1150
1150
1150
1150
1150
E5-02
PM Mot Rated Power (kW)
kW
7.5
11.0
15
18.50
22.00
E5-03
PM Mot Rated Current (FLA)
A
26.67
39.9
55.6
63.5
74.4
E5-04
PM Mot Pole Count
-
6
6
6
6
6
PM Mot Resistance (Ohms/
E5-05
Ω
0.165
0.113
0.084
0.066
0.048
Phase)
PM d-Axis Inductance (mH/
E5-06
mH
6.59
4.96
3.83
3.33
2.38
Phase)
PM q-Axis Inductance (mH/
E5-07
mH
8.55
6.12
4.65
4.50
3.15
Phase)
PM BackEMF Vpeak (mV/(rad/
E5-09
mVs/rad
391.5
384.4
372.1
421.3
410.9
s))
PM BackEMF L-L Vrms (mV/
E5-24
mV/min-1
0.0
0.0
0.0
0.0
0.0
rpm)
E1-04
Max Output Frequency
Hz
57.5
57.5
57.5
57.5
57.5
E1-05
Max Output Voltage
V
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
E1-09
Min Output Frequency
Hz
2.9
2.9
2.9
2.9
2.9
L3-24
Acc@Rated Torque
s
0.088
0.073
0.062
0.091
0.092
*1
n5-02
Mot Inertia Acceleration Time
s
0.088
0.073
0.062
0.091
0.092
n8-49
Heavy Load Id Current
%
-15.3
-13.9
-14.4
-17.9
-15.9
*1
The default setting changes when the setting for o2-04 [Drive KVA Selection] changes.
Table 11.19 SSR1 Series Motor Code Setting for Specification of 400 V at 1150
min-1 (r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
1432
1433
1435
1436
1438
143A
Voltage Class
V
400
400
400
400
400
400
E5-01
Capacity
kW
0.4
0.75
1.5
2.2
3.7
5.5
Motor Rotation Speed
min-1
1150
1150
1150
1150
1150
1150
E5-02
PM Mot Rated Power (kW)
kW
0.4
0.75
1.5
2.2
3.7
5.5
E5-03
PM Mot Rated Current (FLA)
A
0.94
1.51
3.00
4.43
7.08
10.10
E5-04
PM Mot Pole Count
-
6
6
6
6
6
6
PM Mot Resistance (Ohms/
E5-05
Ω
19.320
10.800
4.456
2.044
1.483
1.215
Phase)
PM d-Axis Inductance (mH/
E5-06
mH
194.70
129.20
76.88
48.60
37.58
44.54
Phase)
PM q-Axis Inductance (mH/
E5-07
mH
252.84
160.90
97.52
61.40
47.65
56.26
Phase)
PM BackEMF Vpeak (mV/
E5-09
mVs/rad
640.9
654.1
728.8
688.9
702.0
861.5
(rad/ s))
PM BackEMF L-L Vrms
E5-24
mV/min-1
0.0
0.0
0.0
0.0
0.0
0.0
(mV/rpm)
E1-04
Max Output Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Max Output Voltage
V
380.0
380.0
380.0
380.0
380.0
380.0
428
11.21 Parameters Changed by PM Motor Code Selection
No.
Name
Unit
Motor Code (setting value of E5-01)
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Min Output Frequency
Hz
2.9
2.9
2.9
2.9
2.9
2.9
L3-24
Acc@Rated Torque
s
0.062
0.044
0.080
0.090
0.067
0.072
*1
Mot Inertia Acceleration
n5-02
s
0.062
0.044
0.080
0.090
0.067
0.072
Time
n8-49
Heavy Load Id Current
%
-8.8
-9.9
-9.3
-10.0
-12.8
-12.3
*1
The default setting changes when the setting for o2-04 [Drive KVA Selection] changes.
Table 11.20 SSR1 Series Motor Code Setting for Specification of 400 V at 1150 min-1 (r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
PM Mot Code Selection
-
143B
143D
143E
143F
1440
1442
Voltage Class
V
400
400
400
400
400
400
E5-01
Capacity
kW
7.5
11
15
18.5
22
30
Motor Rotation Speed
min-1
1150
1150
1150
1150
1150
1150
E5-02
PM Mot Rated Power (kW)
kW
7.5
11.0
15
18.50
22.00
30.00
E5-03
PM Mot Rated Current (FLA)
A
13.33
19.9
27.8
31.8
37.2
52.1
E5-04
PM Mot Pole Count
-
6
6
6
6
6
6
PM Mot Resistance (Ohms/
E5-05
Ω
0.660
0.443
0.331
0.264
0.192
0.140
Phase)
PM d-Axis Inductance (mH/
E5-06
mH
26.36
19.10
15.09
13.32
9.52
8.16
Phase)
PM q-Axis Inductance (mH/
E5-07
mH
34.20
24.67
18.56
18.00
12.60
11.40
Phase)
PM BackEMF Vpeak (mV/
E5-09
mVs/rad
783.0
762.2
749.6
842.7
821.8
872.3
(rad/ s))
PM BackEMF L-L Vrms
E5-24
mV/min-1
0.0
0.0
0.0
0.0
0.0
0.0
(mV/rpm)
E1-04
Max Output Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
E1-05
Max Output Voltage
V
380.0
380.0
380.0
380.0
380.0
380.0
E1-06
Base Frequency
Hz
57.5
57.5
57.5
57.5
57.5
57.5
E1-09
Min Output Frequency
Hz
2.9
2.9
2.9
2.9
2.9
2.9
L3-24
Acc@Rated Torque
s
0.088
0.073
0.062
0.091
0.092
0.125
*1
Mot Inertia Acceleration
n5-02
s
0.088
0.073
0.062
0.091
0.092
0.125
Time
n8-49
Heavy Load Id Current
%
-15.3
-16.7
-14.9
-17.9
-15.9
-17.7
*1
The default setting changes when the setting for o2-04 [Drive KVA Selection] changes.
11
429
11.21 Parameters Changed by PM Motor Code Selection
430
12
Parameter Details
12.1
A: INITIALIZATION
432
12.2
b: APPLICATION
444
12.3
C: TUNING
488
12.4
d: REFERENCE
508
12.5
E: MOTOR
524
12.6
F: OPTIONS
544
12.7
H: TERMINALS
566
12.8
L: PROTECTION
632
12.9
n: SPECIAL
676
12.10 o: KEYPAD
695
12.11 T: AUTOTUNING
716
431
12.1 A: INITIALIZATION
12.1
A: INITIALIZATION
Parameters of group A: INITIALIZATION set the operating environment and operating conditions for the drive.
◆ A1: INITIALIZATION
A1 parameters set the operating environment and operating conditions for the drive. For example, these
parameters set the keypad language, the control method, and the parameter access level for the drive.
■ A1-00: Language Selection
No.
Default
Name
Description
(Hex.)
(Range)
V/f
OLV OLV/PM AOLV/PM EZOLV
A1-00
Language Selection
0
(0100)
Sets the language for the LCD keypad.
(0 - 12)
RUN
Note:
• This parameter is only available when you use an LCD keypad or a Bluetooth LCD Keypad.
• When you use A1-03 [Init Parameters] to initialize the drive, the drive will not set this parameter to factory default.
0 : English
1 : Japanese
2 : German
3 : French
4 : Italian
5 : Spanish
6 : Portuguese
7 : Chinese
8 : Czech
9 : Russian
10 : Turkish
11 : Polish
12 : Greek
■ A1-01: Access Level
No.
Default
Name
Description
(Hex.)
(Range)
A1-01
Access Level
V/f
OLV OLV/PM AOLV/PM EZOLV
2
(0101)
Sets user access to parameters. The access level controls which parameters the keypad will
(0 - 3)
display, and which parameters the user can set.
RUN
0 : Monitor only
Access to A1-00, A1-01, A1-04 [Password Input], and the U Monitors.
1 : Manual Setup
Access to A1-00, A1-01, A1-04, and parameters registered to A2-01 to A2-32 [MAN1 Param1 to MAN3
Param12].
2 : Standard Parameters
Access to all parameters, but not Expert Mode parameters.
3 : Expert Parameters
Access to all parameters including Expert Mode parameters.
Table 12.1 shows which keypad screens are available for each A1-01 settings.
432
|
||
|
|
|