Page 8-14
Erosion Control and Water Pollution Control
If trenching is not feasible due to rocky soils or not advisable due to proximity to a
downslope sensitive area, a different sediment control device that does not require
trenching shall be used in place of silt fence.
Backup support is needed for silt fence in areas where extra strength may be required,
such as the toe of steep cut or fill slopes or areas where equipment may push excessive
soils toward the fence. When backup support is used, wire shall have a maximum mesh
spacing of 2 inches, and the plastic mesh shall be as resistant to ultraviolet radiation as
the geotextile it supports. The strength of the wire or plastic mesh shall be equivalent to
or greater than as required in
Section 9-33.2(1)
, Table 6, for unsupported geotextile (i.e.,
180 lbs. grab tensile strength in the machine direction). Post spacing and attachments
shall be as shown in the Standard Plans.
8-01.3(9)A3 High Visibility Silt Fence
High visibility silt fence (HVSF) shall be orange in color and only be used for the dual
purpose of demarcating site preservation lines and a sediment control device in a location
where high visibility mesh fence and black silt fence would otherwise be used together
at same location. If use of HVSF is allowed the geotextile material shall meet the material
requirements of
Section 9-33.2(1)
, Table 6. Post spacing and attachments shall be as
shown in the Standard Plans.
Backup support is needed for high visibility silt fence (HVSF) in areas where extra strength
may be required, such as the toe of steep cut or fill slopes or areas where equipment may
push excessive soils toward the sensitive or protected areas. When backup support is
used, wire shall have a maximum mesh spacing of 2 inches, and the plastic mesh shall be
as resistant to ultraviolet radiation as the geotextile it supports. The strength of the wire
or plastic mesh shall be equivalent to or greater than as required in
Section 9-33.2(1)
,
Table 6, for unsupported geotextile (i.e., 180 lbs. grab tensile strength in the machine
direction). Post spacing shall be as shown in the Standard Plans.
When sediment deposits reach approximately ⅓ the height of the silt fence, or 8 inches
whichever is lower the deposits shall be removed and stabilized in accordance with
Section 8-01.3(15)
.
8-01.3(9)B
Gravel Filter, Wood Chip, or Compost Berm
Filter berms shall retain sediment and direct flows. The gravel filter berm shall be a
minimum of 1 foot in height and shall be maintained at this height for the entire time
they are in use. Rock material used for filter berms shall meet the grading requirements
in
Section 9-03.9(2)
, but shall not include any recycled materials as outlined in
Section 9-03.21
.
The wood chip berm shall be a minimum of 2 feet in height and shall be maintained at this
height for the entire time they are in use.
The Compost Berm shall be constructed in accordance with the detail in the Plans.
Compost shall be Medium Compost.