W
ORKS
Second Edition -SEP 2020
4.3.7.9
Storage on the Site of the Works
Aggregates of different nominal sizes shall be stored separately and in such a manner as to prevent
segregation, contamination, and intermixing of different materials. Aggregates from different sources
shall not be mixed nor stored in the same pile.
Aggregate stockpiles shall be on hard, clean surfaces with not more than 5 % slope. Stockpiles shall
be built and removed in layers not exceeding 1 m in thickness and the centre of the storage area
shall be free of excess moisture. Aggregate that has become segregated or contaminated with
foreign matter during storage or handling shall be rejected, removed, and reprocessed or replaced
with material of acceptable quality. Aggregates shall be stored in sufficient quantity to ensure that
no interruption of concreting work occurs.
Aggregates exposed in coastal regions with marine salty air shall be covered to protect them from
salt contamination.
4.3.8
Water for Concrete Mixing and Curing
Unless otherwise authorised in writing by the Engineer, only water from a municipal potable water
supply system shall be used for mixing concrete and other products containing cementitious material.
Similarly, only potable water may be used for curing concrete and cementitious material products
during the first 24 hours after pouring. Later, fresh water, Sulaibiyah, including recycled sanitary-
effluent water, or other water containing not more than 4,000 ppm dissolved solids, of which not
more than 1,200 ppm may be chlorides, may be used for curing. All water for use with cementitious
material shall be free from detrimental concentrations of acids, alkalis, salts, sugar, and other organic
or chemical substances that could impair the durability and strength of the concrete or the imbedded
steel.
Water shall enter the mixers at as low a temperature as possible. Every effort shall be made to
protect water pipes and tanks from the sun, such as burying, shading, insulating, or painting pipes
white.
4.3.8.1
Tests and Acceptance
Water used shall be sampled, tested, and in compliance with AASHTO T 26. If the water contains
substances that cause discolouration, unusual or objectionable smell or taste, or other suspicious
content, the Engineer may require that the Contractor provide test results that document the
acceptability of the water per these Standard Specifications and requirements of Table 4-15.
Water used in concrete works shall have a pH between 5.0 and 8.0.
Table 4-15: Chemical limits for mix water
Contaminant
Test method
Maximum concentration
(ppm)
Chloride (Cl)
Prestressed concrete
Bridge decks and superstructure
All other concrete
ASTM D512
500
500
1,000
Sulfate (SO
4
)
ASTM D516
1,000
Alkalis (Na
2
O + 0.658K
2
O)
ASTM D4191 and
ASTM D4192
600
Total solids
AASHTO T 26
50,000
Water used to mix and cure white hydraulic cement shall be free of iron and impurities that may
cause staining or discolouration.