Page 9-226
Illumination, Signal, Electrical
A means of disconnecting all wiring entering the panel shall be provided. The
disconnect shall include a means to jumper detection calls when the display
panel is disconnected. All switches on the panel shall be marked with its
associated Plan detector number. All markers shall be permanent.
8. Insulated terminal blocks of sufficient number to provide a termination for all field
wiring. A minimum of 12 spare terminals shall be provided. Field wire connection
terminal blocks shall be 600 volt, heavy duty, barrier type, except loop detector lead-
ins, which may be 300 volt. The 600 volt type terminal strips shall be provided with
a field-side and a control-side connector separated by a marker strip. The 300 volt
type shall have a marker strip, installed on the right side of vertical terminal strips
or below horizontal terminal strips. The marker strip shall bear the circuit number
indicated in the Plans and shall be engraved. Each connector shall be a screw type
with No. 8 post capable of accepting no less than three 12 AWG wires fitted with
spade tips.
9. A vent fan with adjustable thermostat. The minimum CFM rating of the fan shall
exceed three times the cabinet volume.
10. All wiring within the cabinet, exclusive of wiring installed by the signal controller
manufacturer, shall have insulation conforming to the requirements of
Section
9-29.3
. Cabinet wiring shall be trimmed to eliminate all slack and shall be laced or
bound together with nylon wraps or equivalent. All terminals, shall be numbered and
permanently identified with PVC or polyolefin wire marking sleeve consistent with
the cabinet wiring diagram provided by the signal controller manufacturer and the
Contract. The cabinet will be completely wired so that the only requirement to make
a field location completely operational is to attach field power and ground wiring.
Internal cabinet wiring shall not utilize the field side connections of the terminal strip
intended for termination of field wires.
11. Cabinet wiring diagram and component wiring diagrams meeting the requirements
of
Section 9-29.13(7)
shall be furnished with each cabinet. Each cabinet shall
be equipped with a, shelf mounted roll out drawer mounted directly below the
controller to house one or more cabinet wiring diagrams. The cabinet wiring diagram
shall indicate and identify all wire terminations, all plug connectors, and the locations
of all equipment in the cabinet. Included in the diagram shall be an intersection
sketch identifying all heads, detectors, and push buttons; and a phase diagram.
12. Each vehicle detector amplifier, video detection output channel pedestrian call
isolation unit, phase selector, discriminator, and load switch shall be identified with
semi-permanent stick-on type label. The following information shall be included:
a. Vehicle Detector Amplifier Channel
i. Loop number
ii. Assigned phase(s)
b. Ped Call Isolation Unit
i. Push button number
ii. Assigned phase(s)