Standard Specifications for Road, Bridge, and Municipal Construction 2020 (M 41-10) - page 39

 

  Главная      Manuals     Standard Specifications for Road, Bridge, and Municipal Construction 2020 (M 41-10)

 

Search            copyright infringement  

 

 

 

 

 

 

 

 

 

 

 

Content      ..     37      38      39      40     ..

 

 

 

Standard Specifications for Road, Bridge, and Municipal Construction 2020 (M 41-10) - page 39

 

 

Structural Earth Walls  

6-13

6-13 

Structural Earth Walls

6-13.1 Description

This Work consists of constructing structural earth walls (SEW).

6-13.2 Materials

Materials shall meet the requirements of the following sections:
 Cement 

9-01

 

Aggregates for Concrete 

9-03.1

 

Gravel Borrow for Structural Earth Walls 

9-03.14(4) 

Premolded Joint Filler 

9-04.1(2)

 

Steel Reinforcing Bar 

9-07.2

 

Epoxy-Coated Steel Reinforcing Bar 

9-07.3

 

Mortar 

9-20.4 

Concrete Curing Materials and Admixtures 

9-23

 

Fly Ash 

9-23.9

 

Water 

9-25

Other materials required shall be as specified in the Special Provisions.

6-13.3 

Construction Requirements

Proprietary structural earth wall systems shall be as specified in the Special Provisions.

6-13.3(1)  Quality Assurance

The structural earth wall manufacturer shall provide a qualified and experienced 
representative to resolve wall construction problems. The structural earth wall 
manufacturer’s representative shall be present at the beginning of wall construction 
activities, and at other times as needed throughout construction. Recommendations 
made by the structural earth wall manufacturer’s representative shall be followed by 
the Contractor.

The completed wall shall meet the following tolerances:
1.  Deviation from the design batter and horizontal alignment, when measured along a 

10-foot straightedge, shall not exceed the following:
a.  Welded wire faced structural earth wall: 2 inches
b.  Precast concrete panel and concrete block faced structural earth wall: ¾ inch

2.  Deviation from the overall design batter of the wall shall not exceed the following 

per 10 feet of wall height:
a.  Welded wire faced structural earth wall: 1½ inches
b.  Precast concrete panel and concrete block faced structural earth wall: ½ inch

Page 6-278 

Structural Earth Walls

3.  The maximum outward bulge of the face between welded wire faced structural earth 

wall reinforcement layers shall not exceed 2 inches. The maximum allowable offset 
in any precast concrete facing panel joint shall be ¾ inch. The maximum allowable 
offset in any concrete block joint shall be ¾ inch.

4.  The base of the structural earth wall excavation shall be within 3 inches of the staked 

elevations, unless otherwise accepted or specified by the Engineer.

5.  The external structural earth wall dimensions shall be placed within 2 inches of that 

staked on the ground.

6.  The backfill reinforcement layers shall be located horizontally and vertically within 

1 inch of the locations shown in the structural earth wall Working Drawings.

At least 5 working days prior to the Contractor beginning any structural earth wall Work 
at the site, a structural earth wall preconstruction conference shall be held to discuss 
construction procedures, personnel, and equipment to be used, and other elements of 
structural earth wall construction. Those attending shall include:
1.  (representing the Contractor) The superintendent, on site supervisors, and all 

foremen in charge of excavation, leveling pad placement, concrete block and 
soil reinforcement placement, and structural earth wall backfill placement and 
compaction.

2.  (representing the Structural Earth Wall Manufacturer) The qualified and experienced 

representative of the structural earth wall manufacturer as specified at the beginning 
of this section.

3.  (representing the Contracting Agency) The Engineer, key inspection personnel, and 

representatives from the WSDOT Construction Office and Materials Laboratory 
Geotechnical Services Branch.

6-13.3(2) Submittals

The Contractor, or the supplier as the Contractor’s agent, shall furnish a Manufacturer’s 
Certificate of Compliance certifying that the structural earth wall materials conform to the 
specified material requirements. This includes providing a Manufacturer’s Certificate of 
Compliance for all concrete admixtures, cement, fly ash, steel reinforcing bars, reinforcing 
strips, reinforcing mesh, tie strips, fasteners, welded wire mats, backing mats, construction 
geotextile for wall facing, drainage geosynthetic fabric, block connectors, and joint 
materials. The Manufacturer’s Certificate of Compliance for geogrid reinforcement shall 
include the information specified in 

Section 9-33.4(4)

 for each geogrid roll, and shall 

specify the geogrid polymer types for each geogrid roll.

A Type 1 Working Drawing of all test results performed by the Contractor or the 
Contractor’s supplier, which are necessary to ensure compliance with the specifications, 
shall be submitted along with each Manufacturer’s Certificate of Compliance. 

Before fabrication, the Contractor shall submit a Type 1 Working Drawing consisting 
of the field construction manual for the structural earth walls, prepared by the wall 
manufacturer. This manual shall provide step-by-step directions for construction of the 
wall system. 

Structural Earth Walls  

6-13

The Contractor, through the license/patent holder for the structural earth wall system, 
shall submit Type 2E Working Drawings consisting of detailed design calculations and 
details. If not prepared by the license/patent holder for the structural earth system, the 
design calculation and working drawing submittal shall include documentation that the 
design calculation and working drawing submittal has been reviewed by, and received the 
concurrence of, the headquarters organization of the structural earth wall manufacturer 
as identified in the Special Provisions. Review and concurrence by a sales representative 
office is not acceptable.

6-13.3(2)A 

Design Calculation Content Requirements

The design calculation submittal shall include detailed design calculations based on the 
wall geometry and design parameters specified in the Plans and Special Provisions. The 
calculations shall include detailed explanations of any symbols, design input, materials 
property values, and computer programs used in the design of the walls. All computer 
output submitted shall be accompanied by supporting hand calculations detailing the 
calculation process. If MSEW 3.0, or a later version, is used for the wall design, hand 
calculations supporting MSEW are not required.

The design calculations shall be based on the current AASHTO LRFD Bridge Design 
Specifications
, including current interims, the current WSDOT 

Bridge Design Manual

 

LRFD (BDM), and the WSDOT 

Geotechnical Design Manual

 (GDM), and also based 

on the following:
1.  The wall design calculations shall address all aspects of wall internal stability for the 

service, strength, and extreme event limit states.

2.  The wall surcharge conditions (backfill slope) shown in the Plans. 
3.  If a highway is adjacent to and on top of the wall, a 2-foot surcharge shall be used in 

the design. 

4.  If the Plans detail an SEW traffic barrier or SEW pedestrian barrier on top of the 

wall, the barrier shall be designed for a minimum TL-4 impact load, unless otherwise 
specified in the Plans or Special Provisions. 

5.  If the Plans detail an SEW traffic barrier or SEW pedestrian barrier on top of the wall, 

the wall shall be designed for the impact load transferred from the barrier to the wall. 

6.  The geotechnical design parameters for the wall shall be as specified in the Special 

Provisions.

7.  The soil reinforcement length shall be as shown in the Plans. If the Plans do not 

show a length, the length shall be either 6 feet or 0.7 times the wall design height H, 
whichever is greater.

If there are differences in design requirements between the AASHTO LRFD Bridge Design 
Specifications
 and the BDM or GDM, the BDM and GDM requirements shall govern.

Page 6-280 

Structural Earth Walls

6-13.3(2)B 

Working Drawing Content Requirements

All design details shown in the working drawings shall be selected from the design 
details and products specified for the specific structural earth wall manufacturer in the 
Preapproved Wall Appendix in the current WSDOT 

Geotechnical Design Manual

 (GDM). 

Geosynthetic reinforcement shown in the working drawings shall be selected from 
the products listed in the current WSDOT Qualified Products List (QPL). Substitution 
of design details and products not listed in the current WSDOT GDM or QPL will not 
be allowed.

The working drawing submittal shall include all details, dimensions, quantities, and 
cross sections necessary to construct the wall based on the wall geometry and design 
parameters specified in the Plans and Special Provisions, and shall include, but not be 
limited to, the following items:
1.  A plan and elevation sheet or sheets for each wall, containing the following:

a.  An elevation view of the wall that includes the following:

i.  The elevation at the top of the wall, at all horizontal and vertical break 

points, and at least every 50 feet along the wall;

ii.  Elevations at the base of welded wire mats or the top of leveling pads and 

foundations, and the distance along the face of the wall to all steps in the 
welded wire mats, foundations, and leveling pads; 

iii.  The designation as to the type of panel, block, or module; 
iv.  The length, size, and number of geogrids or mesh or strips, and the distance 

along the face of the wall to where changes in length of the geogrids or 
mesh or strips occur; or

v.  The length, size, and wire sizes and spacing of the welded wire mats and 

backing mats, and the distance along the face of the wall to where changes 
in length, size, and wire sizes and spacing of the welded wire mats and 
backing mats occur; and

vi.  The location of the original and final ground line. 

b.  A plan view of the wall that indicates the offset from the construction 

centerline to the face of the wall at all changes in horizontal alignment; the 
limit of the widest module, geogrid, mesh, strip, or welded wire mat, and the 
centerline of any drainage structure or drainage pipe that is behind or passes 
under or through the wall. 

c.  General notes, if any, required for design and construction of the wall.
d.  All horizontal and vertical curve data affecting wall construction. 
e.  A listing of the summary of quantities provided on the elevation sheet of each 

wall for all items, including incidental items.

Structural Earth Walls  

6-13

f. 

A cross section showing limits of construction. In fill sections, the cross section 
shall show the limits and extent of select granular backfill material placed above 
original ground.

g.  Limits and extent of reinforced soil volume.

2.  All details, including steel reinforcing bar bending details. Bar bending details shall be 

in accordance with 

Section 9-07.1

.

3.  All details for foundations and leveling pads, including details for steps in the 

foundations or leveling pads. 

4.  All modules and facing elements shall be detailed. The details shall show all 

dimensions necessary to construct the element, all steel reinforcing bars in the 
element, and the location of reinforcement element attachment devices embedded 
in the precast concrete facing panel or concrete block. 

5.  All details for construction of the wall around drainage facilities, sign, signal, 

luminaire, and noise barrier wall foundations, and structural abutment and 
foundation elements shall be clearly shown. 

6.  All details for connections to SEW traffic or pedestrian barriers, coping, parapets, 

noise barrier walls, and attached lighting shall be shown. 

7.  All details for the SEW traffic or pedestrian barrier attached to the top of the wall 

(if shown in the Plans), including interaction with bridge approach slabs. 

6-13.3(3)  Excavation and Foundation Preparation

Excavation shall conform t

Section 2-09.3(3)

. Foundation soils found to be unsuitable 

shall be removed and replaced in accordance with 

Section 2-09.3(1)C.

 The foundation 

for the Structure shall be graded level for a width equal to or exceeding the length of 
reinforcing as shown in the structural earth wall Working Drawings and, for walls with 
geogrid reinforcing, in accordance with 

Section 2-12.3

. Prior to wall construction, the 

foundation, if not in rock, shall be compacted as accepted by the Engineer.

At the foundation level of the bottom course of precast concrete facing panels and 
concrete blocks, an unreinforced concrete leveling pad shall be provided as shown in 
the Plans. The leveling pad shall be cured a minimum of 12 hours and have a minimum 
compressive strength of 1,500 psi before placement of the precast concrete facing panels 
or concrete blocks.

Page 6-282 

Structural Earth Walls

6-13.3(4)  Precast Concrete Facing Panel and Concrete Block Fabrication

Concrete for precast concrete facing panels shall meet the following requirements:
1.  Have a minimum 28-day compressive strength of 4,000 pounds per square inch, 

unless otherwise specified in the Special Provisions for specific proprietary wall 
systems. If Self-Consolidating Concrete is used, the concrete shall conform to 
Sections 

6-02.3(27)B

 and 

6-02.3(27)C

.

2.  Contain a water-reducing admixture meeting AASHTO M194 Type A, D, F, or G.
3.  Be air-entrained, 6 percent 

±

 1½ percent.

4.  Have a maximum slump of 4 inches, or 6 inches if a Type F or G water reducer 

is used.

Concrete for dry cast concrete blocks shall meet the following requirements:
1.  Have a minimum 28-day compressive strength of 4,000 psi.
2.  Conform to ASTM C1372, except as otherwise specified.
3.  The lot of blocks produced for use in this project shall conform to the following 

freeze-thaw test requirements when tested in accordance with ASTM C1262. 
Minimum acceptable performance shall be defined as weight loss at the conclusion 
of 150 freeze-thaw cycles not exceeding 1 percent of the block’s initial weight for a 
minimum of four of the five block specimens tested.

4.  The concrete blocks shall have a maximum water absorption of 1 percent above the 

water absorption content of the lot of blocks produced and successfully tested for 
the freeze-thaw test specified in item 3 above.

Precast concrete facing panels and concrete blocks will be accepted based on successful 
compressive strength tests, WSDOT “Approved for Shipment” stamp or tag, and visual 
inspection at the jobsite. The precast concrete facing panels and concrete blocks shall be 
considered acceptable regardless of curing age when compressive test results indicate 
that the compressive strength conforms to the 28-day requirements and when the visual 
inspection is satisfactorily completed. Fabrication of precast concrete facing panels and 
blocks shall conform to 

Section 6-02.3(28)

. Testing of dry cast concrete blocks shall 

conform to ASTM C140.

All precast concrete facing panels shall be 5 feet square, except:
1.  for partial panels at the top, bottom, and ends of the wall; and
2.  as otherwise shown in the Plans.

Structural Earth Walls  

6-13

All precast concrete facing panels shall be manufactured within the following tolerances:

1.  All dimensions ± 3/16 inch.

2.  Squareness, as determined by the difference between the two diagonals, shall not 

exceed ½ inch.

3.  Surface defects on smooth formed surfaces measured on a length of 5 feet shall not 

exceed ⅛ inch. Surface defects on textured-finished surfaces measured on a length 
of 5 feet shall not exceed 5/16 inch.

All concrete blocks shall be manufactured within the following tolerances:
1.  Vertical dimensions shall be ± 

1/16

 inch of the Plan dimension, and the rear height 

shall not exceed the front height.

2.  The dimensions of the grooves in the top and bottom faces of the concrete blocks 

shall be formed within the tolerances specified by the proprietary wall manufacturer, 
for the fit required for the block connectors.

3.  All other dimensions shall be ± ¼ inch of the Plan dimension.

Tie attachment devices, except for geosynthetic reinforcement, shall be set in place to the 
dimensions and tolerances shown in the Plans prior to casting.

The forms forming precast concrete facing panels, including the forms for loop pockets 
and access pockets, and the forms forming the concrete blocks, shall be removed in 
accordance with the recommendations of the wall manufacturer, without damaging the 
concrete.

The concrete surface for the precast concrete facing panel shall have the finish shown 
in the Plans for the front face and an unformed finish for the rear face. The rear face of 
the precast concrete facing panel shall be roughly screeded to eliminate open pockets of 
aggregate and surface distortions in excess of ¼ inch.

The concrete surface for the front face of the concrete block shall be flat, and shall be a 
conventional “split face” finish in accordance with the wall manufacturer’s Specifications.The 
concrete surface of all other faces shall be Class 2 in accordance with 

Section 6-02.3(14)B

The finish and appearance of the concrete blocks shall also conform to ASTM C1372. The 
color of the concrete block shall be concrete gray, unless otherwise shown in the Plans.

The date of manufacture, production lot number, and the piece-mark, shall be clearly 
marked on the rear face of each precast concrete facing panel, and marked or tagged on 
each pallet of concrete blocks.

All precast concrete facing panels and concrete blocks shall be handled, stored, and 
shipped in accordance with Sections

 6-02.3(28)G

 and 

6-02.3(28)H

 to prevent chipping, 

cracks, fractures, and excessive bending stresses.

Precast concrete facing panels in storage shall be supported on firm blocking located 
immediately adjacent to tie strips to avoid bending the tie strips.

Page 6-284 

Structural Earth Walls

6-13.3(5)  Precast Concrete Facing Panel and Concrete Block Erection

The precast concrete facing panels shall be placed vertically. During erection, precast 
concrete facing panels shall be handled by means of a lifting device set into the upper 
edge of the panels.

Concrete blocks shall be erected in a running bond fashion in accordance with the wall 
manufacturer’s field construction manual, and may be placed by hand. The top surface 
of each course of concrete blocks, including all pockets and recesses, shall be cleaned 
of backfill and all extraneous materials prior to connecting the reinforcing strips or 
geosynthetic reinforcing, and placing the next course of concrete blocks. Concrete blocks 
receiving geosynthetic reinforcement shall be connected as specified in the Special 
Provisions. Cap block top courses shall be bonded to the lower course of concrete blocks 
as specified below. All other concrete blocks shall be connected with block connectors or 
pins placed into the connector slots.

Precast concrete facing panels and concrete blocks shall be placed in successive 
horizontal lifts as backfill placement proceeds in the sequence shown in the structural 
earth wall Working Drawings as approved by the Engineer.

External bracing is required for the initial lift for precast concrete facing panels.

As backfill material is placed behind the precast concrete facing panels, the panels shall 
be maintained in vertical position by means of temporary wooden wedges placed in the 
joint at the junction of the two adjacent panels on the external side of the wall.

Reinforcing shall be placed normal to the face of the wall, unless otherwise shown in the 
Plans or directed by the Engineer. Prior to placement of the reinforcing, backfill shall be 
compacted.

Geosynthetic reinforcing shall be placed in accordance with 

Section 2-12.3

 and as follows:

1.  The Contractor shall stretch out the geosynthetic in the direction perpendicular 

to the wall face to remove all slack and wrinkles, and shall hold the geosynthetic 
in place with soil piles or other methods as recommended by the geosynthetic 
manufacturer, before placing backfill material over the geosynthetic to the specified 
cover.

2.  The geosynthetic reinforcement shall be continuous in the direction perpendicular to 

the wall face from the back face of the concrete panel to the end of the geosynthetic 
or to the last geogrid node at the end of the specified reinforcement length. 
Geosynthetic splices parallel to the wall face will not be allowed.

At the completion of each course of concrete blocks and prior to installing any block 
connectors or geosynthetic reinforcement at this level, the Contractor shall check the 
blocks for level placement in all directions, and shall adjust the blocks by grinding or 
rear face shimming, or other method as recommended by the structural earth wall 
manufacturer’s representative and as approved by the Engineer, to bring the blocks into a 
level plane.

Structural Earth Walls  

6-13

For concrete block wall systems receiving a cap block top course, the cap blocks shall be 
bonded to the lower course either with mortar conforming to 

Section 9-20.4(3)

or with 

an adhesive capable of bonding the concrete block courses together.

6-13.3(6)  Welded Wire Faced Structural Earth Wall Erection

The Contractor shall erect the welded wire wall reinforcement in accordance with the wall 
manufacturer’s field construction manual. Construction geotextile for wall facing shall be 
placed between the backfill material within the reinforced zone and the coarse granular 
material immediately behind the welded wire wall facing, as shown in the Plans and the 
structural earth wall Working Drawings. Geosynthetic reinforcing, when used, shall be 
placed in accordance with Sections

 2-12.3

 and 

6-13.3(5)

.

6-13.3(7) Backfill

Backfill placement shall closely follow erection of each course of welded wire mats 
and backing mats, precast concrete facing panels, or concrete blocks. Backfill shall be 
placed in such a manner as to avoid any damage or disturbance to the wall materials or 
misalignment of the welded wire mats and backing mats, precast concrete facing panels, 
or concrete blocks. Backfill shall be placed in a manner that segregation does not occur. 
Construction equipment shall not operate directly on the wall reinforcement. A minimum 
backfill thickness of 6 inches over the reinforcement shall be required prior to operation 
of vehicles or equipment.

The Contractor shall place wall backfill over geosynthetic reinforcement, or construction 
geotextile for wall facing, in accordance with 

Section 2-12.3

.

Misalignment or distortion of the precast concrete facing panels or concrete blocks due to 
placement of backfill outside the limits of this Specification shall be corrected in a manner 
acceptable to the Engineer.

The moisture content of the backfill material prior to and during compaction shall be 
uniformly distributed throughout each layer of material. The moisture content of all 
backfill material shall conform to Sections

 2-03.3(14)C

 and 

2-03.3(14)D

.

Backfill shall be compacted in accordance with Method C of 

Section 2-03.3(14)C

, except 

as follows:
1.  The maximum lift thickness after compaction shall not exceed 10 inches.
2.  The Contractor shall decrease this lift thickness, if necessary, to obtain the specified 

density.

3.  The Contractor shall not use sheepsfoot rollers or rollers with protrusions for 

compacting backfill reinforced with geosynthetic layers, or for compacting the first 
lift of backfill above the construction geosynthetic for wall facing for each layer 
of welded wire mats. Rollers shall have sufficient capacity to achieve compaction 
without causing distortion to the face of the wall in accordance with the tolerances 
specified in 

Section 6-13.3(1)

.

Page 6-286 

Structural Earth Walls

4.  The Contractor shall compact the zone within 3 feet of the back of the wall facing 

panels without causing damage to or distortion of the wall facing elements (welded 
wire mats, backing mats, construction geotextile for wall facing, precast concrete 
facing panels, and concrete blocks) by using a plate compactor. No soil density tests 
will be taken within this area.

5.  For wall systems with geosynthetic reinforcement, the minimum compacted backfill 

lift thickness of the first lift above each geosynthetic reinforcement layer shall be 
6 inches.

At the end of each day’s operation, the Contractor shall shape the last level of backfill to 
permit runoff of rainwater away from the wall face. In addition, the Contractor shall not 
allow surface runoff from adjacent areas to enter the wall construction site.

6-13.3(8)  Guardrail Placement

Where guardrail posts are required, the Contractor shall not begin installing guardrail 
posts until completing the structural earth wall to the top of wall elevation shown in the 
Plans. The Contractor shall install the posts in a manner that prevents movement of the 
precast concrete facing panels or concrete blocks, and prevents ripping, tearing, or pulling 
of the wall reinforcement.

The Contractor may cut welded wire reinforcement of welded wire faced structural 
earth walls to facilitate placing the guardrail posts, but only in the top two welded wire 
reinforcement layers and only with the permission of the Engineer in a manner that 
prevents bulging of the wall face and prevents ripping or pulling of the welded wire 
reinforcement. Holes through the welded wire reinforcement shall be the minimum 
size necessary for the post. The Contractor shall demonstrate to the Engineer prior to 
beginning guardrail post installation that the installation method will not rip, tear, or pull 
the wall reinforcement.

The Contractor shall place guardrail posts between the reinforcing strips, reinforcing 
mesh, and tie strips of the non-geosynthetic reinforced precast concrete panel or 
concrete block faced structural earth walls. Holes through the reinforcement of 
geosynthetic reinforced walls, if necessary, shall be the minimum size necessary for the 
guardrail post.

6-13.3(9)  SEW Traffic Barrier and SEW Pedestrian Barrier

The Contractor, in conjunction with the structural earth wall manufacturer, shall design 
and detail the SEW traffic barrier and SEW pedestrian barrier in accordance with 

Section 

6-13.3(2)

 and the above ground geometry details shown in the Plans. The barrier Working 

Drawings and supporting calculations shall be Type 2E and shall include, at a minimum, 
the following:
1.  Complete details of barrier cross section geometry, including the portion below 

ground, and accommodations necessary for bridge approach slabs, PCCP, drainage 
facilities, underground utilities, and sign support, luminaire pole, traffic signal 
standard, and other barrier attachments.

Structural Earth Walls  

6-13

2.  Details of the steel reinforcement of the barrier, including a bar list and bending 

diagram in accordance with 

Section 6-02.3(24)

, and including additional 

reinforcement required at sign support, luminaire pole, traffic signal standard, and 
other barrier attachment locations.

3.  Details of the interface of, and the interaction between, the barrier and the top 

layers of structural earth wall reinforcement and facing.

4.  When the Plans specify placement of conduit pipes through the barrier, details of 

conduit pipe and junction box placement.

SEW traffic barrier and SEW pedestrian barrier shall be constructed in accordance with 
Sections 

6-02.3(11)A

 and 

6-10.3(2)

, and the details in the Plans and in the structural earth 

wall Working Drawings as approved by the Engineer. The moment slab supporting the 
SEW traffic or pedestrian barrier shall be continuously wet cured for 3 days in accordance 
with 

Section 6-02.3(11)

.

6-13.4 Measurement

Structural earth wall will be measured by the square foot of completed wall in place. The 
bottom limits for vertical measurement will be the bottom of the bottom mat, for welded 
wire faced structural earth walls, or the top of the leveling pad (or bottom of wall if no 
leveling pad is present) for precast concrete panel or concrete block faced structural earth 
walls. The top limit for vertical measurement will be the top of wall as shown in the Plans. 
The horizontal limits for measurement are from the end of the wall to the end of the wall.

Gravel borrow for structural earth wall including haul will be measured by the cubic yard 
in place determined by the limits shown in the Plans.

SEW traffic barrier, and SEW pedestrian barrier will be measured as specified in 

Section 6-10.4

 for cast-in-place concrete barrier.

6-13.5 Payment

Payment will be made for each of the following Bid items when they are included in the 
Proposal:

“Structural Earth Wall”, per square foot.
The unit Contract price per square foot for “Structural Earth Wall” shall be full 
payment for all costs to perform the Work in connection with constructing structural 
earth walls, including leveling pads and copings when specified.
“Gravel Borrow for Structural Earth Wall incl. Haul”, per cubic yard.
The unit Contract price per cubic yard for “Gravel Borrow for Structural Earth Wall 
incl. Haul” shall be full payment for all costs to perform the Work in connection 
with furnishing and placing backfill for structural earth wall, including hauling and 
compacting the backfill, and furnishing and placing the wall-facing backfill for welded 
wire-faced structural earth walls.
“SEW Traffic Barrier”, per linear foot.

Page 6-288 

Structural Earth Walls

“SEW Pedestrian Barrier”, per linear foot.
The unit Contract price per linear foot for “SEW ___ Barrier” shall be full pay for 
constructing the barrier on top of the structural earth wall, except that when these 
Bid items are not included in the Proposal, all costs in connection with performing 
the Work as specified shall be included in the unit Contract price per square foot for 
“Structural Earth Wall”.

Geosynthetic Retaining Walls 

6-14

6-14 

Geosynthetic Retaining Walls

6-14.1 Description

This Work consists of constructing geosynthetic retaining walls, including those shown in 
the 

Standard Plans

.

6-14.2 Materials

Materials shall meet the requirements of the following sections:
 Cement 

9-01

 

Aggregates for Concrete 

9-03.1

 

Sand 

9-03.13(1)

 

Gravel Borrow for Structural Earth Wall 

9-03.14(4)

 

Polyurethane Sealant 

9-04.2(3)

 

Closed Cell Foam Backer Rod 

9-04.2(3)A

 

Anchor Rods and Associated Nuts, Washers, and Couplers 

9-06.5(4)

 

Reinforcing Steel 

9-07

 

Welded Wire Reinforcement 

9-07.7

 

Grout 

9-20.3(4)

 

Construction Geosynthetic 

9-33

Anchor plate shall conform to ASTM A36, ASTM A572 Grade 50, or ASTM A588.

The requirements specified in 

Section 2-12.2

 for geotextile shall also apply to 

geosynthetic and geogrid materials used for permanent and temporary geosynthetic 
retaining walls.

Other materials required shall be as specified in the Special Provisions.

6-14.3 

Construction Requirements

Temporary geosynthetic retaining walls are defined as those walls and wall components 
constructed and removed or abandoned before the Physical Completion Date of the 
project or as shown in the Plans. All other geosynthetic retaining walls shall be considered 
as permanent.

6-14.3(1)  Quality Assurance

The Contractor shall complete the base of the retaining wall excavation to within plus or 
minus 3 inches of the staked elevations unless otherwise directed by the Engineer. The 
Contractor shall place the external wall dimensions to within plus or minus 2 inches of 
that staked on the ground. The Contractor shall space the reinforcement layers vertically 
and place the overlaps to within plus or minus 1 inch of that shown in the Plans.

Page 6-290 

Geosynthetic Retaining Walls

The completed wall(s) shall meet the following tolerances:

Permanent 

Wall

Temporary 

Wall

Deviation from the design batter and horizontal alignment for the 

face when measured along a 10-foot straightedge at the midpoint of 

each wall layer shall not exceed:

3 inches

5 inches

Deviation from the overall design batter per 10 feet of wall height 

shall not exceed:

2 inches

3 inches

Maximum outward bulge of the face between backfill reinforcement 

layers shall not exceed:

4 inches

6 inches

6-14.3(2) Submittals

The Contractor shall submit Type 2E Working Drawings consisting of detailed plans 
for each wall. The Working Drawing submittal shall include all details, dimensions, and 
cross sections necessary to construct the wall based on the wall geometry and design 
parameters specified in the Plans, including at a minimum, the following:
1.  Detailed wall plans, with plan and elevation views for each wall, showing the actual 

lengths proposed for the geosynthetic reinforcing layers and the locations of each 
geosynthetic product proposed for use in each of the geosynthetic reinforcing layers.

2.  Detailed cross sections showing the geosynthetic reinforcing layers, fascia 

connection dowels or anchor rods, and fascia formwork connection or support 
details located within or adjacent to the wall backfill.

3.  The Contractor’s proposed wall construction method, including proposed forming 

systems, types of equipment to be used, proposed erection sequence and details of 
how the backfill will be retained during each stage of construction.

4.  Manufacturer’s Certificate of Compliance, samples of the retaining wall geosynthetic 

and sewn seams for the purpose of acceptance as specified.

5.  Details of geosynthetic retaining wall corner construction, including details of the 

positive connection between the wall sections on both sides of the corner.

6.  Details of terminating a top layer of retaining wall geosynthetic and backfill due 

to a changing retaining wall profile.

Acceptance of the Contractor’s proposed wall construction details and methods shall not 
relieve the Contractor of their responsibility to construct the walls in accordance with the 
requirements of these Specifications.

6-14.3(3)  Excavation and Foundation Preparation

Excavation shall conform t

Section 2-09.3(3)

. Foundations soils found to be unsuitable 

shall be removed and replaced in accordance with 

Section 2-09.3(1)C.

The Contractor shall direct all surface runoff from adjacent areas away from the retaining 
wall construction site.

Geosynthetic Retaining Walls 

6-14

6-14.3(4)  Erection and Backfill

The Contractor shall begin wall construction at the lowest portion of the excavation and 
shall place each layer horizontally as shown in the Plans. The Contractor shall complete 
each layer entirely before beginning the next layer.

Geotextile splices shall consist of a sewn seam or a minimum 1-foot overlap. Geogrid 
splices shall consist of adjacent geogrid strips butted together and fastened using hog 
rings, or other methods acceptable to the Engineer, in such a manner to prevent the 
splices from separating during geogrid installation and backfilling. Splices exposed at the 
wall face shall prevent loss of backfill material through the face. The splicing material 
exposed at the wall face shall be as durable and strong as the material to which the 
splices are tied. The Contractor shall offset geosynthetic splices in one layer from those in 
the other layers such that the splices shall not line up vertically. Splices parallel to the wall 
face will not be allowed, as shown in the Plans.

The Contractor shall stretch out the geosynthetic in the direction perpendicular to the 
wall face to ensure that no slack or wrinkles exist in the geosynthetic prior to backfilling.

For geogrids, the length of the reinforcement required as shown in the Plans shall be 
defined as the distance between the geosynthetic wrapped face and the last geogrid 
node at the end of the reinforcement in the wall backfill.

The Contractor shall place fill material on the geosynthetic in lifts such that 6 inches 
minimum of fill material is between the vehicle or equipment tires or tracks and the 
geosynthetic at all times. The Contractor shall remove all particles within the backfill 
material greater than 3 inches in size. Turning of vehicles on the first lift above the 
geosynthetic will not be permitted. The Contractor shall not end dump fill material 
directly on the geosynthetic without the prior permission of the Engineer.

The Contractor shall use a temporary form system to prevent sagging of the geosynthetic 
facing elements during construction. A typical example of a temporary form system and 
sequence of wall construction required when using this form are detailed in the Plans. Soil 
piles or the geosynthetic manufacturer’s recommended method, in combination with the 
forming system shall be used to hold the geosynthetic in place until the specified cover 
material is placed.

The Contractor shall place and compact the wall backfill in accordance with the wall 
construction sequence detailed in the Plans and Method C of 

Section 2-03.3(14)C

except as follows:
1.  The maximum lift thickness after compaction shall not exceed 10 inches
2.  The Contractor shall decrease this lift thickness, if necessary, to obtain the specified 

density.

3.  Rollers shall have sufficient capacity to achieve compaction without causing 

distortion to the face of the wall in accordance with 

Section 6-14.3(1)

.

4.  The Contractor shall not use sheepsfoot rollers or rollers with protrusions.

Page 6-292 

Geosynthetic Retaining Walls

5.  The Contractor shall compact the zone within 3 feet of the back of the wall facing 

panels without causing damage to or distortion of the wall facing elements (welded 
wire mats, backing mats, construction geotextile for wall facing, precast concrete 
facing panels, and concrete blocks) by using a plate compactor. No soil density tests 
will be taken within this area.

6.  For wall systems with geosynthetic reinforcement, the minimum compacted backfill 

lift thickness of the first lift above each geosynthetic reinforcement layer shall be 
6 inches.

The Contractor shall construct wall corners at the locations shown in the Plans, and 
in accordance with the wall corner construction sequence and method in the Working 
Drawing submittal. Wall angle points with an interior angle of less than 150 degrees shall 
be considered to be a wall corner. The wall corner shall provide a positive connection 
between the sections of the wall on each side of the corner such that the wall backfill 
material cannot spill out through the corner at any time during the design life of the wall. 
The Contractor shall construct the wall corner such that the wall sections on both sides of 
the corner attain the full geosynthetic layer embedment lengths shown in the Plans.

Where required by retaining wall profile grade, the Contractor shall terminate top layers 
of retaining wall geosynthetic and backfill in accordance with the method in the Working 
Drawing submittal. The end of each layer at the top of the wall shall be constructed 
in a manner that prevents wall backfill material from spilling out the face of the wall 
throughout the life of the wall. If the profile of the top of the wall changes at a rate of 
1:1 or steeper, this change in top of wall profile shall be considered to be a corner.

6-14.3(5)  Guardrail Placement

The Contractor shall install guardrail posts as shown in the Plans after completing the 
wall, but before the permanent facing is installed. The Contractor shall install the posts in 
a manner that prevents bulging of the wall face and prevents ripping, tearing, or pulling 
of the geosynthetic reinforcement. Holes through the geosynthetic reinforcement shall 
be the minimum size necessary for the post. The Contractor shall demonstrate to the 
Engineer prior to beginning guardrail post installation that the installation method will not 
rip, tear, or pull the geosynthetic reinforcement.

6-14.3(6)  Permanent Facing

The Contractor shall apply a permanent facing to the surface of all permanent 
geosynthetic retaining walls as shown in the Plans. Shotcrete facing, if shown in the Plans, 
shall conform to 

Section 6-18

. Concrete fascia panel, if shown in the Plans, shall conform 

to 

Section 6-15.3(9)

, if cast-in-place, and shall conform to 

Section 6-02.3(28)

, if precast.

 

 

 

 

 

 

 

Content      ..     37      38      39      40     ..