Concrete Barrier
6-10
The barrier shall be precast in sections as the
Standard Plans
require. All barrier in the
same project (except end sections and variable length units needed for closure) shall be
the same length. All barrier shall be new and unused. It shall be true to Plan dimensions.
The manufacturer shall be responsible for any damage or distortion that results
from manufacturing.
Only one section less than 20 feet long for single slope barrier and 10 feet long for all
other barriers may be used in any single run of precast barrier, and it shall be at least 8
feet long. It may be precast or cast-in-place. Hardware identical to that used with other
sections shall interlock such a section with adjacent precast sections.
Barrier connection voids for permanent installations of precast single slope barrier shall
be filled with grout.
6-10.3(2) Cast-In-Place Concrete Barrier
Forms for cast-in-place concrete barrier, including traffic barrier, traffic-pedestrian barrier,
and pedestrian barrier on bridges and related Structures, shall be made of steel or exterior
plywood coated with plastic. The Contractor may construct the barrier by the slip-form
method.
The barrier shall be made of Class 4000 concrete that meets the requirements of
Section
6-02
, except that the fine aggregate gradation used for slip-form barrier may be either
Class 1 or 2. The Contractor may use portland cement Type III at no additional expense to
the Contracting Agency.
In addition to the steel reinforcing bar tying and bracing requirements specified in
Section
6-02.3(24) C
, the Contractor may also place small amounts of concrete to aid in holding
the steel reinforcing bars in place. These small amounts of concrete shall be not more
than 2-cubic feet in volume, and shall be spaced at a minimum of 10-foot intervals within
the steel reinforcement cage. These small amounts of concrete shall be consolidated and
shall provide 2 inches minimum clearance to the steel reinforcing bars on the outside face
of the barrier. All spattered and excess mortar and concrete shall be removed from the
steel reinforcing bars prior to slip-form casting.
Barrier expansion joints shall be spaced at 96-foot intervals, and dummy joints shall be
spaced at 12-foot intervals unless otherwise specified in the Contract.
Immediately after removing the forms, the Contractor shall complete any finishing Work
needed to produce a uniformly smooth, dense surface. The surface shall have no rock
pockets and no holes larger than ¼ inch across. The barrier shall be cured and finished in
accordance with
Section 6-02.3(11)A
.
The maximum allowable deviation from a 10-foot straightedge held longitudinally on all
surfaces shall be ¼ inch. For single sloped barrier the maximum allowable deviation from a
straightedge held along the vertical sloped face of the barrier shall be ¼ inch.
At final acceptance of the project, the barrier shall be free from stains, smears, and any
discoloration.