Page 7-40 

Water Mains

The Engineer shall have free access to all testing and records pertaining to material to 
be delivered to the job site. The Engineer may elect to be present at any or all material 
testing operations.

The basis of acceptance shall be a certificate of compliance as described in 

Section 1-06.3

, accompanied by two copies of pressure test results of the pipe or 

fittings involved.

7-09.3 

Construction Requirements

7-09.3(1) General

Trench excavation required for the installation of water mains and appurtenances shall 
be unclassified. Material excavated from trenches and piled adjacent to the trench or in 
a Roadway or public thoroughfare shall be piled and maintained so that the toe of the 
slope of the spoil material is at least 2 feet from the edge of the trench. It shall be piled in 
a manner to prevent surface water from flowing into the excavation and in a manner that 
will cause a minimum of inconvenience to public travel. Free access shall be provided to 
all fire hydrants, water valves, and meters; and clearance shall be left to enable the free 
flow of storm water in gutters, conduits, and natural watercourses.

7-09.3(2)  Ungraded Streets

On ungraded streets, when grading is not called for in the Contract, the depth of trench 
excavation shall be as shown on the Plans and as staked.

Where the Plans show the pipe is to be laid above the existing ground surface, an 
embankment fill shall be made and compacted to conform with the section shown on 
the Plans, and the water main trench shall be excavated therein. That portion of the 
embankment below the bottom of the pipe shall be compacted with rollers or mechanical 
compactors under controlled moisture conditions as required under Method B of 

Section 2-03.3(14)C

.

7-09.3(3)  Clearing and Grubbing in Ungraded Streets

On ungraded streets, where clearing and grubbing is not called for in the Contract, 
the area to be excavated or filled shall be cleared and grubbed by the Contractor. This 
Work shall consist of the removal and disposal of logs, stumps, roots, brush, and other 
refuse within 5 feet of the centerline of the pipe. Such material shall be disposed of in 
accordance with the Special Provisions. 

7-09.3(4)  Removal of Existing Street Improvements

Removal of existing street improvements and pavement from driveways and sidewalks 
shall be performed as specified in 

Section 2-02

. Stockpiling of waste materials along the 

trench shall not be allowed.

Water Mains 

7-09

7-09.3(5)  Grade and Alignment

The location of blow off assemblies and combination air release/air vacuum valves are 
shown on the Plans.

The Contractor shall verify the locations and establish the depth of the existing water 
mains at the points where connections are to be made prior to trenching for the pipelines. 
The profile shall be adjusted so no new high spots or low spots are created between the 
connection points to the existing water mains.

The depth of trenching for water mains shall be such as to give a minimum cover of 
36 inches over the top of the pipe unless otherwise specified in the Special Provisions. 
Deeper excavation may be required due to localized breaks in grade, or to install the 
new main under existing culverts or other utilities where necessary. Where the profile of 
the pipeline and the ground surface is shown on the Plans, the pipeline shall be laid to 
the elevation shown regardless of depth. The excavation shall be to such depth that the 
minimum cover over valve operating nuts shall be 1 foot. 

7-09.3(6)  Existing Utilities

Existing utilities of record, except services, are shown on the Plans. These are shown for 
convenience only, and the Engineer assumes no responsibility for improper locations or 
failure to show utility locations on the Plans. 

When utility services occupy the same space as the new water main, the Contractor shall 
complete necessary excavation to fully expose such services. The Contractor shall protect 
said services, and work around them during excavating and pipe laying operations. Any 
damages to services resulting from the Contractor’s operation shall be reported to the 
appropriate utility. Such damage shall be repaired at the Contractor’s expense.

7-09.3(7)  Trench Excavation

The Contractor shall perform excavation of every description and in whatever materials 
encountered to the depth indicated on the Plans or specified in the Special Provisions. 
Excavations shall be made by open cut unless otherwise provided for. Trenches shall be 
excavated to true and smooth bottom grades and in accordance with the lines given by 
the Engineer or shown on the Plans. The trench bottom shall provide uniform bearing and 
support for each length of pipe. 

Bell holes shall be excavated to the extent necessary to permit accurate Work in making 
and inspecting the joints. The banks of the trenches shall be kept as nearly vertical as soil 
conditions will permit, and where required to control trench width or to protect adjacent 
Structures, the trench shall be sheeted and braced. Trench widths to 1 foot above the top 
of the pipe shall not exceed 30 inches maximum or 1½ times the outside diameter of the 
pipe plus 18 inches whichever is greater. Standard excavating equipment shall be adjusted 
so as to excavate the narrowest trench possible.

Page 60 

9-28  Signing Materials and Fabrication  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-174

9-28.1 General  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-174

9-28.2 

Manufacturer’s Identification and Date. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-174

9-28.3 

Corner Radius   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-174

9-28.4 

Extruded Windbeams and “Z” Bar  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-175

9-28.5 

Letter and Spacing Formula . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-175

9-28.6 

Destination Sign Messages  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-175

9-28.7 

Process Colors  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-175

9-28.8 

Sheet Aluminum Signs  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-176

9-28.9 

Fiberglass Reinforced Plastic Signs   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-176

9-28.9(1) 

Mechanical Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-177

9-28.9(2) 

Physical Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-177

9-28.10  Digital Printing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-178

9-28.11 Hardware  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-179

9-28.12  Reflective Sheeting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-179

9-28.12(1) Application   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-183

9-28.12(2) 

Edge Treatment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-183

9-28.12(3) 

Splices and Color Matching   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-183

9-28.13  Demountable Prismatic Reflectorized Message and Borders  . . . . . . . . . . . . . . . . . .

9-184

9-28.14  Sign Support Structures  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-184

9-28.14(1) 

Timber Sign Posts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-184

9-28.14(2) 

Steel Structures and Posts   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-185

9-28.14(3) 

Aluminum Structures  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-185

9-28.15 Vacant  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-185

9-29  Illumination, Signal, Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-186

9-29.1 

Conduit, Innerduct, and Outerduct  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-186

9-29.1(1) 

Rigid Metal Conduit, Galvanized Steel Outerduct, and Fittings  . . .

9-186

9-29.1(2) 

Rigid Metal Conduit Fittings and Appurtenances  . . . . . . . . . . . . . . .

9-186

9-29.1(3) 

Flexible Metal Conduit   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-187

9-29.1(4) 

Non-Metallic Conduit   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-187

9-29.1(5) 

Innerduct and Outerduct   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-188

9-29.1(6) 

Detectable Underground Warning Tape . . . . . . . . . . . . . . . . . . . . . . .

9-190

9-29.1(7) 

Steel Casings  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-190

9-29.1(8) 

Drilling Fluid  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-191

9-29.1(9) Repair  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-191

9-29.1(10) 

Pull Tape . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-191

9-29.1(11) 

Foam Conduit Sealant  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-191

 Contents

9-29.2 

Junction Boxes, Cable Vaults, and Pull Boxes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-191

9-29.2(1) 

Junction Boxes  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-191

9-29.2(2) 

Cable Vaults and Pull Boxes  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-194

9-29.2(3) 

Structure Mounted Junction Box . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-196

9-29.2(4) 

Cover Markings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-197

9-29.2(5) 

Testing Requirements   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-197

9-29.3 

Fiber Optic Cable, Electrical Conductors, and Cable . . . . . . . . . . . . . . . . . . . . . . . . . .

9-200

9-29.3(1) 

Fiber Optic Cable  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-200

9-29.3(2) 

Electrical Conductors and Cable  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-202

9-29.3(3) 

Wire Marking Sleeves  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-203

9-29.4 

Messenger Cable, Fittings  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-204

9-29.5 Vacant  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-204

9-29.6 

Light and Signal Standards . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-204

9-29.6(1) 

Steel Light and Signal Standards   . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-205

9-29.6(2) 

Slip Base Hardware   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-205

9-29.6(3) 

Timber Light Standards, Timber Strain Poles, Timber Service  
Supports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-205

9-29.6(4) Welding  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-206

9-29.6(5) 

Foundation Hardware  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-206

9-29.7 

Luminaire Fusing and Electrical Connections at Light Standard Bases,  
Cantilever Bases, and Sign Bridge Bases . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-206

9-29.7(1) 

Unfused Quick-Disconnect Connector Kits   . . . . . . . . . . . . . . . . . . .

9-206

9-29.7(2) 

Fused Quick-Disconnect Kits  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-207

9-29.8 Vacant  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-207

9-29.9 

Ballast, Transformers   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-208

9-29.9(1) Ballast . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-208

9-29.9(2) Transformers  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-209

9-29.10 Luminaires   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-209

9-29.10(1) 

Conventional Roadway Luminaires  . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-210

9-29.10(2) Vacant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-212

9-29.10(3) Vacant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-212

9-29.10(4) 

Underdeck and Wall Mount Luminaires  . . . . . . . . . . . . . . . . . . . . . . .

9-212

9-29.10(5) 

Sign Lighting Luminaires  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-212

9-29.11  Control Equipment  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-215

9-29.11(1) 

Time Clock Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-215

9-29.11(2) 

Photoelectric Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-215

Page 62 

9-29.12  Electrical Splice Materials  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-215

9-29.12(1) 

Illumination Circuit Splices  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-215

9-29.12(2) 

Traffic Signal Splice Material . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-216

9-29.12(3) 

Splice Enclosures  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-216

9-29.12(3)B  Molded Splice Enclosure  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-216

9-29.12(4) 

Re-Enterable Splice Enclosure  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-216

9-29.12(5) 

Vinyl Electrical Tape for Splices  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-216

9-29.13  Control Cabinet Assemblies   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-216

9-29.13(1) 

Environmental, Performance, and Test Standards for Solid-State 
Traffic Controller Assemblies  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-216

9-29.13(3) 

Traffic Signal Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-218

9-29.13(4) 

Traffic-Signal Controller Software  . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-218

9-29.13(5) 

Flashing Operations  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-222

9-29.13(6) 

Emergency Preemption  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-222

9-29.13(7) 

Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-223

9-29.13(8) 

Generator Transfer Switch   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-223

9-29.13(9) Vacant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-223

9-29.13(10)  NEMA, Type 170E, 2070 Controllers and Cabinets  . . . . . . . . . . . . .

9-224

9-29.13(11)  Traffic Data Accumulator and Ramp Meters  . . . . . . . . . . . . . . . . . . .

9-232

9-29.13(12)  Type 331L ITS Cabinet   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-235

9-29.14 Vacant  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-236

9-29.15  Flashing Beacon Control  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-237

9-29.16  Vehicular Signal Heads, Displays, and Housing  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-237

9-29.16(1) 

Optically Programmed, Adjustable Face, and Programmable  
Array 12-Inch Traffic Signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-237

9-29.16(2) 

Conventional Traffic Signal Heads  . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-240

9-29.16(3) 

Polycarbonate Traffic Signal Heads  . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-242

9-29.16(4) 

Traffic Signal Cover   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-242

9-29.17  Signal Head Mounting Brackets and Fittings  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-242

9-29.18  Vehicle Detector  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-243

9-29.18(1) 

Induction Loop Detectors  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-244

9-29.18(2) 

Magnetometer Detectors  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-244

9-29.19  Pedestrian Push Buttons  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-245

9-29.20  Pedestrian Signals  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-245

9-29.21  Flashing Beacon   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-246

9-29.22 Vacant  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-246

9-29.23 Vacant  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-246

 Contents

9-29.24  Service Cabinets  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-246

9-29.24(1) Vacant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-248

9-29.24(2) 

Electrical Circuit Breakers and Contactors . . . . . . . . . . . . . . . . . . . . .

9-248

9-29.25  Amplifier, Transformer, and Terminal Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-248

9-30  Water Distribution Materials  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-250

9-30.1 Pipe  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-250

9-30.1(1) 

Ductile Iron Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-250

9-30.1(2) 

Polyethylene Encasement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-250

9-30.1(3) Vacant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-250

9-30.1(4) 

Steel Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-251

9-30.1(5) 

Polyvinyl Chloride (PVC)  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-251

9-30.1(6) 

Polyethylene (PE) Pressure Pipe (4 inches and Over) . . . . . . . . . . . .

9-251

9-30.2 Fittings  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-252

9-30.2(1) 

Ductile Iron Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-252

9-30.2(2) Vacant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-252

9-30.2(3) Vacant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-252

9-30.2(4) 

Steel Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-252

9-30.2(5) 

Polyvinyl Chloride (PVC) Pipe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-252

9-30.2(6) 

Restrained Joints   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-253

9-30.2(7) 

Bolted, Sleeve-Type Couplings for Plain End Pipe   . . . . . . . . . . . . . .

9-253

9-30.2(8) 

Restrained Flexible Couplings   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-253

9-30.2(9) 

Grooved and Shouldered Joints  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-253

9-30.2(10) 

Polyethylene (PE) Pipe (4 inches and Over)  . . . . . . . . . . . . . . . . . . . .

9-253

9-30.2(11) 

Fabricated Steel Mechanical Slip-Type Expansion Joints  . . . . . . . . .

9-253

9-30.3 Valves  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-254

9-30.3(1) 

Gate Valves (3 to 16 inches)  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-254

9-30.3(2) Vacant. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-254

9-30.3(3) 

Butterfly Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-254

9-30.3(4) 

Valve Boxes  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-254

9-30.3(5) 

Valve Marker Posts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-254

9-30.3(6) 

Valve Stem Extensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-255

9-30.3(7) 

Combination Air Release/Air Vacuum Valves . . . . . . . . . . . . . . . . . . .

9-255

9-30.3(8) 

Tapping Sleeve and Valve Assembly  . . . . . . . . . . . . . . . . . . . . . . . . . .

9-255

9-30.4 Vacant  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-255

9-30.5 Hydrants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-255

9-30.5(1) 

End Connections   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-255

9-30.5(2) 

Hydrant Dimensions   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-256

9-30.5(3) 

Hydrant Extensions  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-256

9-30.5(4) 

Hydrant Restraints  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

9-256

Water Mains 

7-09

7-09.3(7)C 

Extra Trench Excavation

Changes in grades of the water main from those shown on the Plans, or as provided in the 
Special Provisions, may be necessary because of unexpected utilities, or for other reasons. 
If, in the opinion of the Engineer, it is necessary to adjust, correct, relocate, or in any way 
change the line and grade, such changes shall be made by the Contractor under the terms 
of these Standard Specifications.

When pipeline grade is lowered in excess of 1 foot below the grade indicated on the 
Plans, the Contractor shall make such extra excavation as necessary.

When the pipeline horizontal alignment is changed by more than 1 foot from the line 
indicated on the Plans, after the trench has been excavated, the Contractor shall excavate 
the trench at the changed location and backfill and compact the previous trench.

Additional excavation so required will be classified as extra trench excavation.

7-09.3(8)  Removal and Replacement of Unsuitable Materials

Whenever in excavating the trench for water mains, the bottom of the trench exposes 
peat, soft clay, quicksand, or other unsuitable foundation material, such material shall be 
removed to the depth directed by the Engineer and backfilled with foundation material. 
When determined by the Engineer that silty soils or fine sandy soils are encountered, 
Class C foundation material shall be required. Silty soils or fine sandy soils usually flow in 
the presence of a stream of water. When determined by the Engineer that clay, peat, or 
other soft materials are encountered that become saturated with water, but do not break 
down into fine particles and flow, Class A or Class B foundation material shall be required.

Material removed from the trench that is unsuitable for trench backfill shall be removed 
and hauled to a waste site. If material is not available within the limits of the project 
for backfilling the trench, the Contractor shall furnish trench backfill meeting the 
requirements of Section

 9-03.12(3)

 or 

9-03.19

 as required.

Unsuitable material shall be loaded directly into trucks and hauled to a waste site 
obtained by the Contractor. Stockpiling of unsuitable material at the project site shall not 
be allowed.

7-09.3(9)  Bedding the Pipe

Gravel backfill for pipe zone bedding shall be select granular material free from wood 
waste, organic material, and other extraneous or objectionable materials and shall have a 
maximum dimension of 1½ inches. Gravel backfill for pipe zone bedding shall be placed 
to the depths shown in the 

Standard Plans

. Gravel backfill for pipe zone bedding shall be 

rammed and tamped around the pipe to 95 percent of maximum density by approved 
hand-held tools, so as to provide firm and uniform support for the full length of the 
pipe, valves, and fittings. Care shall be taken to prevent any damage to the pipe or its 
protective coating.

 

 

 

 

 

 

 