|
|
|
Tutorials
· This opens the Bus Field Options dialog (shown below); select the field Bus Voltage to add in the selected position
and click OK.
· The parameter and position are displayed as highlighted in the Insert New Fields dialog. Click OK. Note that the
specified bus field has been added to the oneline diagram.
· Repeat this procedure for the other two buses. If necessary, you may move fields manually with the mouse.
Fields can also be inserted using the Insert > Field option from the main menu or by using the Insert Field buttons on
the Insert Toolbar.
Next, we will insert fields showing the power flow at each end of the transmission line.
·
Select Insert > Field > Line Field or click the Line Field button on the Insert toolbar.
Line fields show information about trans mission lines and transformers. For line fields, flow is always specified at an
end of the transmission line or transformer. The end is normally determined automatically by the insertion point.
·
Left-click near both bus 1 and the transmission line between buses 1 and 2 in the location you want the power
flow text to appear. The Line Field Options dialog (shown below) opens automatically.
·
The Near Bus and Far Bus fields should show 1 and 2 respectively. If they do not, enter the correct values.
·
Select AC Line MW Flow then click OK. The field is displayed on the oneline in the location you specified. Note
that the field can be moved and formatted as previously discussed.
·
Select Insert > Field > Line Field or click the Line Field button on the Insert toolbar.
·
Left-click near both bus 2 and the transmission line between buses 1 and 2 in the location you want the power
flow text to appear. The Line Field Options dialog (shown below) opens automatically.
·
Now the Near Bus and Far Bus fields should show 2 and 1 respectively. If they do not, enter the correct values.
·
Select AC Line MW Flow then click OK.
·
Repeat the procedure to insert AC Line Mvar Flow fields for the two locations.
923
We also desire to monitor the MW and Mvar flows on the lines joining buses 1 and 3 and buses 2 and 3 via the
transformers. The same commands are used as those used to insert fields for the transmission line.
·
Repeat the above steps to insert AC Line MW (and Mvar ) Flow fields on the lines joining buses 1 and 3 and
buses 2 and 3 via the transformers.
·
At this point, your first oneline diagram should resemble the one shown below.
·
Save the case.
924
Tutorials
Tutorial: Solving the Case Page 12 of 13
To solve a case, you must be in run mode:
·
Click on Run Mode button on the Pr ogram Toolbar. Note that, if the case has validation errors, a warning will
appear. You will need to rectify the problems before you can enter Run Mode.
·
Select Simulation > Play to begin the simulation (or press the Play
button on the Run Mode toolbar).
Alternatively, to perform a single Power Flow Solution, click the Single Solution button on the Program Toolbar.
Your case should look similar to the case shown below. If it does, congratulations! You have completed building
your first case.
Try clicking on the load circuit breaker to toggle the load’s status. A solid red circuit breaker indicates that it is closed,
a hollow green box indicates it is open. While the simulation is running, click on the circuit breakers and note the
nearly instantaneous change in system flows. If the Log window is visible, you will get a "backstage" view of what
Simulator is doing. Feel free to close the log. To re-open the log, click the Log
button on the Program Toolbar.
With the load circuit breaker closed, open the circuit breaker between bus 3 and its connected generator. Now open
any of the transmission line or transformer circuit breakers.
Congratulations, you’ve just blacked-out your case!
925
Tutorial: Adding a New Area
Page 13 of 13
Next, we will create a second operating area for the case. Large interconnected systems usually have a number of
control areas, with each control area responsible for the operation of a particular part of the system. Often, a single
control area corresponds to a single owner (such as an investor-owned utility), but it is not unusual for a single control
area to have more than one owner. Control areas are connected to neighboring areas through tie lines. A tie line is a
transmission line that has one end in one control area and the other end in another. The total amount of power flowing
out of a control area is the algebraic sum of the power flowing out on all the area’s tie lines. Each control area is
responsible for procuring enough power to meet its own load plus losses. The control area can get this power either
by generating it itself, or by buying it from another area. This ability to buy and sell power (i.e., power transactions) is
one of the principal advantages of interconnected operation.
To create another control area:
·
Change to Edit Mode . Right click on bus 3 and select Bus Information Dialog from the dropdown menu.
·
Entering a number for an area that does not already exist automatically creates a new area. Enter ‘2’ in the Area
Number field. Enter ‘TWO’ in the Area Name field. Click OK.
·
To verify that the case now has two areas, select Case Information > Case Summary from the main menu. The
Case Information Displays allow you to view the entire case using non-graphical displays. The Case Summary
dialog (shown below) shows the number of buses, generators, lines/transformers, and control areas in the case.
You cannot modify any of these values.
Now we will make sure that both of the control areas are initially set as being on automatic generation control (AGC).
AGC insures that the generation in the area is equal to the load plus losses plus and scheduled transactions.
·
Select Case Information > Areas . The Area display (pictured below) provides a convenient summary of all the
control areas in the case. Similar displays exist for buses, generators, lines/transformers, etc.
926
Tutorials
·
Right-click anywhere on the record for the first area and select the Show Dialog option. The Area Display Dialog
is shown (as below).
·
Change the Area Name to ‘ONE’ and set the AGC Status under Area Control Options to Economic Dispatch
Control. Select SAVE to save this information.
·
Next click on the up arrow next to the right of the Area Number field. This displays the Area Record dialog for the
next area. Set the AGC Status to Economic Dispatch Control, and select OK to save your changes and close
the dialog.
·
Note the AGC Status field in the Area Records Display now shows ED in the AGC Status fields. Close the Area
Records display.
927
Starting with an Existing Case
Starting with an Existing Case
Page 1 of 15
This procedure describes how to create a power system model from an existing power flow file using PowerWorld
Simulator. This procedure was developed for use with version 10.0 of the package. If you have an earlier version,
please contact PowerWorld Corporation at infopowerworld.com for information on upgrading, or visit the website at
This tutorial assumes that you have at least some familiarity with PowerWorld Simulator. If you need a more general
introduction, please see Creating a New Case tutorial.
PowerWorld cases can be easily created from existing power flow cases stored in PTI RAW versions 23-29, GE PSLF
text format (EPC version 11.X), and IEEE common format.
Simulator provides a static model of a power system. The power flow data is a subset of the system model. For some
studies this model is sufficient. For other studies the model needs to be augmented by adjusting: generator cost
information, the reactive capability curve, PowerWorld Simulator case options, interface definitions, injection group
definitions, contingency definitions, the time variation of the load, etc….
To begin, double-click on the PowerWorld Simulator icon. This starts Simulator. In this example we will be building a
case from an existing power flow file.
928
Tutorials
Tutorial: Loading an Existing Power Flow File Page 2 of 15
Once Simulator has been started, set Simulator to Edit Mode by clicking on the Edit Mode button on the Program
Toolbar. Select the File > Open Case from the main menu, or select the Open Case
button on the File Toolbar.
An Open dialog box will appear on the screen. To select a power flow file, click on the Type of File field in the lower
left hand corner of the dialog box. A list of file formats will appear. Choose the appropriate format, and the available
files of the type selected will appear in the box above Type of File . Choose the desired f ile from the list of available
files and select OK. In this example, we will be building a oneline for the 3990 bus MAIN 1998 summer case saved in
PTI version 23 format as mdb98s.raw. When prompted to create a oneline, select ‘yes’. Your display should
immediately turn white. This shows the blank background upon which you will be drawing the oneline diagram for your
case. Onelines are used in power system analysis to represent the actual three-phase power system using a single
line to represent each three phase device. The information from the power flow file is now accessible to Simulator.
929
Tutorial: Case Information Displays Page 3 of 15
Simulator presents many different Case Information Displays to provide a text-based view of the case. For example,
to view or modify the description of the case, select Case Information > Case Description from the main menu. The
Case Description Dialog should appear, showng the text description of the power flow case. In PowerWorld, this
text description may be arbitrarily long.
You can also obtain a case summary by selecting Case Information > Case Summary from the main menu. The
summary dialog will appear. It provides a summary of the case and of the total case load and generation. None of the
fields in this dialog can be changed, as they are intended for informational purposes only.
The Area/Zone Filters information display is another important article. The Area/Zone/Owner Filters feature restricts
the contents of other case information displays to certain areas or zones. This is particularly useful for large cases.
Open the Area/Zone Filters display by selecting Case Information > Area/Zone Filters from the main menu, or use
the Area/Zone/Owner Filters button on the Options/Info Toolbar. As with all Case Information Displays, you can click
on a column heading to sort the list on a particular field; click on that same column heading again to reverse the sort
order. To change a particular area’s area/zone filter status, simply left-click on the area’s area/zone filter status field.
To change the filter status for all areas in the case, right-click on the display to bring up its local menu (all case
information displays have a local menu), and select either Toggle All Yes or Toggle All No. For our example, set all
areas to ‘no’ except WUMS.
Another important text-based display is the Power Flow List. The power flow list shows the complete power flow
information for all areas whose area/zone filter is set to ‘yes’. To display the power flow list, select Case Information
> Power Flow List. The power flow list has other options that can be accessed by right-clicking anywhere on the list.
If you wish to view more details about a particular device, you can do so by holding down the Ctrl key and left-clicking
on the device. To move through the list of buses, you can use the arrow keys or the scroll bar. If you are viewing a
particular bus and you wish to view a bus connected to it, double-click on the line connecting the two buses to view the
flows at the other bus. Note that some of the transmission lines have a circuit identifier of ‘99’. Whenever a ‘99’ is
used for an identifier, it usually means that the transmission line is an equivalent line.
A shorter version of the power flow list can often be more useful. Such a display is offered by the Quick Power Flow
List. The Quick Power Flow List is similar to the power flow list except that it shows flows at individual buses or a set
of buses, regardless of area/zone filter settings. You can view flows at any bus in the case. To display the quick
power flow list, select Case Information > Quick Power Flow List from the main menu, or press the Quick Power
Flow List
button on the Options/Info Toolbar. Identify the buses of interest In the Bus Number field by entering
the number of either a single bus, a set of buses separated by commas, or a range of buses specified using a hyphen.
Again you can double-click to move to a desired bus, or choose Show Object Dialog from the display’s local menu to
see the information dialog for any object.
930
Tutorials
Tutorial: Solving the Case Page 4 of 15
To solve the power flow case we have been using in this example, press the Single Solution button on the Program
Toolbar. You may wish to show the Message Log before you solve the case so as to monitor the solution process.
When you choose to perform a Single Solution, the application automatically switches to Run Mode if it is not already
there. The system has initial mismatches because of voltage truncation in the power flow file. The case should
converge quickly, perhaps in 2 or 3 iterations. After the single solution has been performed, Simulator now has the
solved power flow in memory, and you are ready to build the oneline.
It is not necessary that the power flow case be solved before you create the oneline. However, we recommend that
you solve the existing case first to make sure that it is valid.
931
Tutorial: Building Onelines Page 5 of 15
PowerWorld Simulator makes the power system case easier to analyze by presenting results visually using a oneline
diagram. You do not need to represent every bus in the power flow model on the oneline, for a oneline diagram need
be created only for the desired portion of a system under study. Simulator can automatically link the constructed
oneline diagram to the existing power system model. The following sections of this tutorial will discuss placing various
visual components onto a oneline diagram. In all of the following sections the actions described will relate to the
aforementioned MAIN example.
932
Tutorials
Tutorial: Entering a Bus Page 6 of 15
The most important component of the power system model is the bus. Buses are used to represent junction points in
the power system where a number of devices connect together. To build a oneline diagram, you draw the buses,
attach devices such as generators and loads to the buses, and connect the buses together with transmission lines and
transformers.
To begin entering devices onto the blank oneline, you must first switch to Edit Mode. If you are not already in Edit
Mode, switch back to Edit Mode now. Show the Quick Power Flow List and move it towards the bottom of the screen.
Show bus 39820 by typing that number in the Bus Number field. Select Insert > Bus from the main menu, or click
the Bus
button the Insert Toolbar. Click on the oneline towards the top center to define the point at which the
new bus will be added. The Bus Information Dialog will appear. In the Bus Number field enter 39820. Select Find
by Number to view the bus information. You should see the information appear in the Bus dialog fields that
corresponds with the MAIN power flow case. Select OK to place the bus. The bus should now appear on your
screen.
If it has not already been done for you automatically, add a bus field identifying the new bus’ number immediately to
the left of the new bus. To do this, click on or to the left of the display object that represents bus 39820 and select
Insert > Field, Bus from the main menu. Alternatively, click the Bus Field
button on the Insert Toolbar. The
Bus Field Options Dialog will appear for you to fill out. Designate the type of field as Bus Number and close the dialog.
Simulator will add a text object showing the bus number at the point where you had clicked.
Repeat this procedure to place buses 39881 and 39821 on the oneline, along with their bus numbers.
933
Tutorial: Automatic Line Insertion Page 7 of 15
Transmission lines between buses can be inserted manually by choosing Insert > Transmission Line from the main
menu or pressing the Transmission Line
button on the Insert Toolbar, clicking on the beginning bus, and
tracing a line to the ending bus. Vertices may be defined along the way by clicking the mouse on the diagram where
vertices should appear. However when creating a case from an existing power flow file, you also have the option to
insert transmission line display objects automatically. To do this, select Insert > Auto Insert > Lines from the main
menu in Edit Mode. Accept the default options and click OK. The lines joining the visible buses on the display are
automatically added, along with circuit breakers and pie charts, provided those options are set. Simulator will draw
only transmission lines that link buses that have already been drawn on the oneline diagram. If you add another bus
to the diagram, you can again auto-insert lines, and Simulator will only insert lines that are not already present on the
display.
934
Tutorials
Panning and Zooming Page 8 of 15
Two features of Simulator are indispensable when you have a large, detailed oneline: panning and zooming. To pan
from side to side or up and down, either use the arrow keys or the scrollbars on the sides of the oneline. To zoom in
or out of the oneline, hold the Ctrl key down and press the up arrow to zoom in and the down arrow to zoom out. For
the example, pan up and insert buses 39819 and 39841, again with bus analogs showing their numbers. Again use
Insert > Auto Insert > Lines to add the transmission lines.
935
Tutorial: Adding Background Page 9 of 15
Sometimes you may wish to insert background elements on a oneline such as bodies of water or state lines to convey
geographic location. To show static background elements on the oneline, select Insert > Background Graphic >
Background Line , or click the Background Line button on the Insert Toolbar. Click on the diagram to start the
background line and to add segments. Double click to terminate the background line. If you wish to fill in the area
inside the background line or change the background line’s color, select the background line and choose Format >
Line/Fill from the main menu and make the appropriate choices in the resulting dialog. You may wish to experiment
now with drawing background lines or objects and with adding fill color.
936
Tutorials
Tutorial: Simulating the Case Page 10 of 15
Once you have constructed a oneline diagram showing the area of interest, you can simulate the case. Simulator
cannot only show the magnitude and direction of flows on transmission lines, but it can also animate them. To
configure the animated flows, switch to Edit Mode and choose Options > Oneline Display from the main menu.
Select the Animated Flows Tab of the resulting dialog box. Check the Show Animated Flows check box to enable
the animated flows at run time. This dialog box also allows you to change the size, density, and fill color of the
animated flows for easier visualization. At this point, just click OK. Next, save your case by selecting File > Save from
the main menu or by pressing the Save
button on the File Toolbar. If you have not already saved the case, a
Save As dialog will prompt you to select a name. Both the oneline diagram and the case will use this name.
To perform the simulation, switch to Run Mode and select Simulation > Play or Simulation > Restart from the main
menu. You should now see Simulator modeling the 3990-bus case.
937
Tutorial: Run-time Object Dialogs Page 11 of 15
While the simulation ensues, you might want to view or change some study parameters. To do this, first pause the
simulation so that you will not lose any simulation time while you are viewing or adjusting the parameters. (Note that
you do not have to pause the simulation to tweak parameters. You can adjust anything in the case while the
simulation runs, too.) Then, right-click on any of the objects on the display. This will bring up the run-time dialog for
the object. Many of the parameters on this dialog can be modified, and the new settings will take effect when the
simulation is restarted.
938
Tutorials
Oneline Local Menu Page 12 of 15
Several options are available at run time from the oneline diagram’s local menu. To call up the menu, right-click on an
empty portion of the oneline to display. The local menu will appear. Use it to print the oneline, save it as a metafile, or
copy it to the clipboard. You can also find a particular bus on the oneline, acces s panning and zooming options, set
oneline display options, view information about the power system area in which you clicked, create a contour plot, and
use the difference flows activity, all from the oneline local menu.
939
Tutorial: Area Page 13 of 15
Often, system data is most conveniently displayed by area. To view the Area Records Display, select Case
Information > Areas from the main menu. The resulting display summarizes information about all the areas in the
case. You can sort the entries by clicking on the column labels.
940
Tutorials
Limit Violations Page 14 of 15
You can view a report of limit violations by selecting Case Information, Limit Violations from the main menu. A
display showing bus voltage violations, line/transformer violations and interface violations will appear. If the Use Area
/ Zone Filters on List Displays is checked, then the displayed violations will correspond only to areas whose Shown
field is set to Yes on the Area/Zone/Owner Filters display.
If you wish to see more information on a bus that appears in the violation list, right-click on the bus number and select
Quick Power Flow List from the resulting local menu. If the Case Information Display is set to refresh automatically,
the list of bus voltage violations will update as new violations occur.
941
Other Case Information Displays Page 15 of 15
In addition to the few displays discussed in this tutorial, Simulator offers many other Case Information Displays. In
most cases, you can view information about buses, generators, lines, transformers, loads, and zones simply by right-
clicking on the object in question and choosing the appropriate option from the object’s local menu. The best way to
become more familiar with the displays and the information contained in them is simply to play with a Simulator case
and oneline. Simulator’s interface has been designed to be simple and intuitive. If you run into problems, the On-line
Help should prove helpful.
942
Tutorials
OPF
Tutorial: Solving an OPF
Page 1 of 6
Note: This tutorial was developed using version 11.0 of the package. The OPF option in PowerWorld
Simulator is only available if you have purchased the OPF add-on to the base package. Please contact
PowerWorld Corporation at info@powerworld.com or visit the website at http://www.powerworld.com for details about
ordering the OPF version of Simulator or upgrading to version 11.0.
The PowerWorld Simulator (Simulator) is an interactive power system simulation package designed to simulate high
voltage power system operation. In the standard mode, Simulator solves the power flow equations using a Newton-
Raphson power flow algorithm. With the optimal power flow (OPF) enhancement, Simulator OPF can also solve these
equations using an OPF. In particular, Simulator OPF uses a linear programming (LP) OPF implementation.
The purpose of an OPF is to minimize an objective (or cost) function by changing different system controls taking into
account both equality and inequality constraints which are used to model the power balance constraints and various
operating limits.
In Simulator OPF the LP OPF determines the optimal solution by iterating between solving a standard power and then
solving a linear program to change the system controls to remove any limit violations. See OPF Primal LP for more
details.
943
Tutorial: OPF Three Bus Example
Page 2 of 6
For this tutorial, we will start with a provided three-bus case (B3LP) found in the PowerWorld\Simulator\Sample Cases
directory. Bus 1 is the system slack bus. All buses are connected via 0.1 pu reactance lines, each with a 100 MVA
limit. There is a single 180 MW load at bus 3. The generator marginal costs are:
-
Bus 1: 10
$/MWhr; Range = 0 to 400 MW
-
Bus 2: 12
$/MWhr; Range = 0 to 400 MW
-
Bus 3: 20
$/MWhr; Range = 0 to 400 MW
To begin:
· Load B3LP case.
· Verify the above system specifications by right clicking on each line, bus, and generator and selecting its respective
Line/Bus/Generator Information Dialog from the drop down menu.
· Select Run Mode .
· To be included in the OPF, all required area AGC status fields must be selected to OPF. To set area AGC to OPF:
Select LP OPF > OPF Areas . The OPF Area Records display automatically opens. Verify the AGC Status field is
selected to OPF. If it is not, double click on the field to change its value. Close the OPF Area Records display.
· Select LP OPF > Primal LP to solve the case. Note: line limits are not initially enforced.
Your display should look similar to the following:
B3LP Solved Using LP OPF > Primal LP
Note the line from Bus 1 to Bus 3 is overloaded and that all buses have the same marginal cost.
944
Tutorials
Tutorial: OPF Line Limit Enforcement
Page 3 of 6
·
Select LP/OPF > OPF Areas .
The Branch MVA column specifies whether or not the MVA limits should be enforced for transmission lines and
transformers that have at least one terminal in this area. For a transmission line or transformer to be included in the
OPF constraints, Line/Transformer constraints must not be disabled on the OPF Options Dialog, and the individual
line/transformer must be enabled for enforcement on the OPF Line/Transformer MVA Constraints display.
·
Double click on the Branch MVA field to change the value to YES. Close the OPF Area display
·
Select LP/OPF > Options .
·
The LP OPF Dialog opens automatically. Select the Constraint Options tab then click Disable
Line/Transformer MVA Limit Enforcement to remove the checkmark.
·
Click Solve LP OPF then click OK.
B3LP Solved with Line Limit Enforcement Enabled
The LP OPF re-dispatches to remove the line limit violation. Bus marginal costs have changed from the initial
example. The new bus marginal cost at Bus 3 is 14
$/MWh. To verify this:
·
Increase the load at Bus 3 by 1 MW. Right click on the load, enter "181.0" in the Constant Power / MW Value
field in the Load Options dialog. Click OK.
·
Select LP OPF > Primal LP.
The Total Cost increased to 1935
$/hr from the previous value of 1921
$/hr, a difference of 14
$/hr when Bus 3 load
was increased by 1 MW.
945
Tutorial: OPF LMP Explanation
Page 4 of 6
Explanation of Bus 3 LMP = 14
$/MWh (from previous page):
B3LP Solved with Line Limit Enforcement Enabled
All lines have equal impedance. Power flow in a simple network distributes inversely to impedance of the path.
·
For Bus 1 to supply 1 MW to Bus 3, 2/3 MW will take the direct path from 1 to 3, while 1/3 MW will take the path
from 1 to 2 to 3.
·
Likewise, for bus 2 to supply 1 MW to Bus 3, 2/3 will go from 2 to 3, while 1/3 will go from 2 to 1 to 3.
·
To supply one additional MW to Bus 3, we need the change in power of generator 1 (Pg1) plus the change in
power of generator 2 to equal 1 MW.
Pg1 + Pg2 = 1 MW
·
With the line from 1 to 3 limited, no additional power flows are allowed on it.
(2/3)Pg1 + (1/3)Pg2 = 0
·
Solving the above system of equations results in:
Pg1 = -1 MW and Pg2 = 2 MW
Dcost = S(DPg*LMP) = [(-1 MW)*(10.00
$/MWh) + (2 MW)*(12.00
$MW/h)] = 14.00
$/hr
946
Tutorials
Tutorial: OPF Marginal Cost of Enforcing Constraints
Page 5 of 6
Similar to the bus marginal cost, you can also calculate the marginal cost of enforcing a line constraint. For a
transmission line, this represents the amount of system savings that could be achieved if the MVA rating was
increased by 1.0 MVA.
·
Select LP OPF > OPF Lines and Transformers. The OPF Constraints Records dialog opens.
Note the column displaying MVA Marginal Cost displays 6.0 for the line from Bus 1 to Bus 3. This is determined
based on the following:
·
With no change in system load:
Pg1 + Pg2 = 0
·
If we allow one additional MVA to flow on the line from Bus 1 to Bus 3:
(2/3)Pg1 + (1/3)Pg2 = 1
·
Solving the above system of equations results in:
Pg1 = 3 MW and Pg2 = -3 MW
Dcost = S(DPg*LMP) = [(3 MW)*(10.00
$/MWh) + (-3 MW)*(12.00
$MW/h)] = -6.00
$/hr, a net savings of 6.00
$/hr.
947
Tutorial: OPF Unenforceable Constraints
Page 6 of 6
Next we will consider a case with unenforceable constraints. To begin, increase the load at Bus 3 to 250 MW then run
the LP OPF again:
·
Right-click on the load at Bus 3. Enter 250 in the Constant Power / MW Value field.
·
Select LP OPF > Primal LP.
B3LP with Bus 3 Generator Carrying Load
Note that the transmission lines connecting Bus 3 to the other buses are both at their respective MVA limit and that the
generator at Bus 3 is supplying the load in excess of the transmission line limits. Next we will open the generator at
Bus 3 thereby inserting an unenforceable constraint:
·
Left-click on the red breaker symbol connecting the generator to Bus 3 to open the breaker.
·
Select LP OPF > Primal LP.
B3LP Solved with Unenforceable Constraints
Both constraints cannot be enforced. If a constraint cannot be enforced due to insufficient controls, the slack variable
associated with enforcing that constraint can not be removed from the LP basis.
948
Tutorials
Note the new LMP value for bus 3 exceeds 1000
$/MWh. Marginal cost depends on the arbitrary cost of the slack
variable. This value is specified in the Marginal Violation Cost field of the LP OPF > Options dialog. See OPF
Options dialog for more details.
Additional Example
To see another OPF example select PowerWorld Simulator Add-on Tools > Optimal Power Flow (OPF) >
Examples from the table of contents in the on-line help file.
Contingency Analysis
Tutorial: Contingency Analysis
This tutorial will walk you through the basic commands necessary to insert contingencies and hav e Simulator
automatically analyze the results. Please see Introduction to Contingency Analysis for the necessary background
information regarding the capabilities and uses of the Contingency Analysis tool.
For this tutorial, we will use an existing 7-bus case.
· Open case B7SCOPF from the "Program Files/PowerWorld/Simulator/Sample Cases" directory.
· Ensure Simulator is in Run Mode.
· Select Contingency Analysis from the Tools main menu item. Simulator opens the Contingency Analysis Dialog.
Contingency Analysis Dialog
When you access the contingency analysis tool for the first time, no contingencies are defined, so only the
Contingencies tab is visible. Once you have defined contingencies for your case, all four tabs of the contingency
analysis dialog will be visible (Contingencies, Lines/Buses/Interfaces, Options, and Summary).
949
The next section of the tutorial discusses Defining Contingencies and provides an example of inserting a single
element contingency.
1 2 3 4 5 6 7 8 9 10 11
Next
950
|