PowerWorld Simulator version 11. Manual - page 9

 

  Главная      Manuals     PowerWorld Simulator version 11. Manual

 

Search            copyright infringement  

 

 

 

 

 

 

 

 

 

 

 

Content      ..     7      8      9      10     ..

 

 

 

PowerWorld Simulator version 11. Manual - page 9

 

 

Determines whether the switched shunt has a fixed value, or whether the amount of reactive power supplied by the
device changes either in discrete steps or continuously in order to maintain its terminal voltage within the voltage
range specified in the Voltage Regulation fields. This field can be changed (except in Viewer). However, for a
switched shunt to be used for automatic control, three fields must be set correctly:
1)
The Control Mode field must be set to either Discrete or Continuous
2)
The corresponding area's Auto Shunts property must be true, and
3)
The case-wide Disable Switched Shunt Control option, which can be set on the Power Flow Solution Tab
of the PowerWorld Simulator Options Dialog, must not be checked.
Note: automatic control of switched shunts is disabled if the voltage regulation high value is not greater
than the low value; they should not be equal unless in the continuous mode.
Note the additional control mode called Bus Shunt (Fixed). This is analogous to the shunt MW and MVAR values
that can also be stored at the bus level. The difference is that bus shunts stored directly with the bus cannot be
turned on and off in the load flow; rather they are always included in the load flow solution. Bus shunts that are
represented as switched shunt objects on Bus Shunt control, however, are mathematically exactly the same and
can be turned on or off. The reason for the differentiation of the Bus Shunt versus normal Fixed control is that the
Bus Shunt control type is intended to identify the difference between a bus shunt and a transformer that MAY have
controllability, but is currently turned of off control by being set to a Fixed value.
Voltage Regulation
When the switched shunt is on automatic control, its reactive power is changed in discrete steps or continuously to
keep the voltage at the regulated bus within the per unit voltage range defined by High Value and the Low Value.
You may modify these values (except in Viewer). When operating in discrete control mode, the amount of reactive
power supplied by this device changes in discrete amounts, therefore the High Value should be greater than the low
value. The necessary voltage range depends upon the size of the switched shunt blocks. The Reg. Value field
shows the current per unit voltage at the regulated bus, while the Target Value is displaying the actual desired
voltage at the regulated bus. The number of the regulated bus is shown in the Reg. Bus # field.
Reg. Bus P.U. Voltage to Mvar Sensitivity
The number in this area is the amount that will be added to the per unit voltage for each 1 Mvar increase by the bus
controlling element.
Switched Shunt Blocks
The amount of shunt admittance is specified in the Switched Shunt Blocks table. The columns in this field
correspond to different blocks of admittance. The first row indicates the number of steps in each block, and the
second row gives the amount of nominal Mvars per step. The switched shunts are always switched in the order
specified in this field. Reactive blocks (negative shunt MVR) should be specified before capacitive blocks (positive
shunt MVR).
Control Options
Single Largest Step
This option only applies when a switched shunt is set on discrete control. If checked the switched shunt will switch
in EITHER all of the available reactor blocks OR all of the capacitor blocks at once when the voltage falls outside
the given range. Whether the reactor or capacitor blocks switch is determined by which limit is violated. A switched
shunt with this option checked will only switch ONCE during a load flow solution, and then remains fixed at the new
output for the remainder of the same solution calculation.
Use Continuous Element
If this option is checked, then Simulator will use a continuous element to fine-tune a discrete controlled switched
shunt by injecting or absorbing additional MVARs to try and obtain the target voltage of the controlled bus.
Minimum and Maximum Susceptance
The minimum and maximum susceptance range for the continuous correction element.
Fault Analysis Parameters
Typically switched shunts are treated as open circuits in the zero sequence data for fault analysis. However, it is
possible to define zero sequence admittance blocks to be used. The blocks work similarly to the load flow Switched
Shunt Blocks discussed above. Usually there will be the same number of blocks in the zero sequence data as in the
load flow data. Simulator will determine how many blocks were switched in for the power flow solution, and then use
the zero sequence block data to calculate the zero sequence admittance for the same number of steps and blocks.
Owners
This tab is used to display or change the generator’s owner information, area information, and zone information
Area Number, Area Name
308
Properties of Simulator Objects
The area number and name to which the generator belongs. Note that you can change the area of the generator to
be different than the area of the terminal bus. If you do so, you will be prompted to confirm that you wish to place
the generator within a different area than that of the bus to which it is electrically connected.
Zone Number, Zone Name
The zone number and name to which the generator belongs. Note that you can change the zone of the generator
to be different than the zone of the terminal bus. If you do so, you will be prompted to confirm that you wish to place
the generator within a different zone than that of the bus to which it is electrically connected.
Owner Number, Owner Name
The owner number and name to which the switched shunt belongs. Note that you can change the owner of the
switched shunt to be different than the owner of the terminal bus. If you do so, you will be prompted to confirm that
you wish to place the switched shunt within a different owner than that of the bus to which it is electrically
connected.
Substation Number, Substation Name
The substation number and name to which the switched shunt belongs. Note that you can change the substation of
the switched shunt to be different than the substation of the terminal bus. If you do so, you will be prompted to
confirm that you wish to place the switched shunt within a different substation than that of the bus to which it is
electrically connected.
309
Zone Properties
Zone Information (Run Mode)
This dialog is used in the Run Mode to view and modify information associated with a zone record. It displays different
information from the Edit Mode version of the zone dialog. To display it from Run Mode, first select Case Information,
Zones from the main menu to bring up the Zone Records Display. Right-click on the zone of interest and choose
Show Dialog. The Run Mode Zone Dialog has the following fields:
Zone Number, Zone Name
Number and name of the associated zone. Use either the combo box or the spin arrows to view the different zones.
Find…
If you do not know the exact zone number you are looking for, you can click this button to open the advanced
search engine.
Labels
To assign alternative identifying labels to the zone, click the Labels button.
The rest of the Run Mode Zone Dialog is divided into three pages of controls:
Information
Load and Generation
Real and reactive load, generation, shunts, losses, and interchange for the zone.
Generation AGC Range
These two fields show the total available MW reserve for generators in the zone that are on AGC and have nonzero
participation factors. In other words, these fields show the total MW by which the generation in the zone can be
increased or decreased using only generation that is presently on-line. The generator status, AGC status, and
participation factor can be changed on the Generator Records Display.
Load Variation Model
As with areas, the load variation within a zone is governed by a load variation schedule, which prescribes a time-
dependent load multiplier to apply to the zone's load.
Load Schedule
This dropdown box identifies the load schedule that is currently associated with the zone. Use the dropdown box to
specify the load schedule to apply to the zone from the list of defined load schedules. It is acceptable not to
associate a load schedule with a zone, in which case the value specified in the Schedule Value field is applied at
all times.
Schedule Value
This field shows the current load multiplier for the zone, which scales all loads in the zone. If no Load Schedule
has been assigned to the zone, this field will display a prefix of 'N'. If the associated load schedule is disabled, the
field will display a prefix of 'D'.
Tie Lines
Zone Tie Lines
The Zone Tie Line Table identifies the flows on all of the zone's ties to other zones.
OPF
Average LMP for Zone
The computed average locational marginal price of all buses contained in the zone.
LMP Standard Deviation
The standard deviation of the locational marginal price for all buses contained in the zone.
Minimum LMP
The minimum locational marginal price of all the buses in the zone.
Maximum LMP
The maximum locational marginal price of all the buses in the zone.
310
Properties of Simulator Objects
Zone Buses, Zone Gens, Zone Loads, Zone Switched Shunts
These pages show the case information display with the buses, generators, loads and switched shunts belonging to
the zone.
Memo
The Memo page of the Zone Information dialog is simply a location to log information about the zone. To log
information about the zone, simply switch to the Memo page on the dialog, and start typing your information or
comments about the zone in the page.
311
General Properties and Information
Labels
Power system equipment such as buses, generators, loads, switched shunts, areas, zones, and interfaces may have
alternative names assigned to them. These alternative names are called labels. Labels allow you to refer to
equipment in the power system model in a way that may be unique to your organization. Labels may thus help clarify
which elements are described by a particular set of data, especially when the short names employed by the power
system model prove cryptic. Furthermore, since labels are likely to change less frequently than bus numbers, and
since a label must, by definition, identify only one power system component, they may function as an immutable key
for importing data from auxiliary files into different cases, even when bus numbering schemes change between the
cases.
Information dialogs corresponding to buses, generators, loads, switched shunts, areas, zones, and interfaces feature a
button called Labels . If you press this button, the device’s Label Manager Dialog will appear. The Label Manager
Dialog lists the labels associated with the device. You can delete a label from the list by selecting it and pressing the
delete key on the keyboard. You may add a label to the device by typing its name in the textbox labeled New Label
and pressing the Add button. You will not be allowed to add a Label that already exists, regardless of whether the
existing label is associated with the current device or some other device. A single power system device may have
multiple labels, but each label may be associated with only one device.
You also may designate a particular label to be the primary label for the device by selecting it from the list and clicking
the Make Primary button. A device’s primary label is the one that can be displayed individually in a Case Information
Display. The other labels associated with a device can be used to import data from auxiliary data files, but they cannot
be viewed individually from Case Information Displays. However, all Case Information Displays can hold a field that
lists all labels assigned to a device as a semicolon-delimited string.
Labels can be used to map data from an auxiliary data file to a power system device. Recall that auxiliary data files
require you to include a device’s key fields in each data record so that data may be mapped to the device. Labels
provide an alternative key. Instead of supplying the bus number to identify a bus, for example, you can supply one of
the bus’s labels. The label will enable Simulator to associate the data with the device associated with that label. This
mechanism performs most efficiently when the primary label is used, but secondary labels will also provide the
mapping mechanism.
Again, it is important to remember this: a single power system device may have multiple labels, but each label may be
associated with only one device. This is the key to enabling data to be imported from an auxiliary file using labels.
312
Properties of Simulator Objects
Area Properties
Area Information
The Area Information Dialog shows information about each area in the system. It displays an area’s load, generation
and losses; the area’s scheduled interchange with other areas; options for controlling the area’s generators,
transformers, and shunts; the flows on its tie lines; and its operating cost information. You may view this dialog by
doing any of the following:
· Right-click in an empty portion of the oneline near a bus in the area of interest to display the oneline's local menu.
Select Area Information Dialog.
· Select Case Information, Areas from the main menu. This displays the Area Display. Right-click on the record
corresponding to the desired area to bring up the display’s local menu, and choose Show Dialog.
· Right-click on an Area/Zone Display Object that represents an area.
The Area Information Dialog contains the following information:
Number
A dropdown box that specifies the area number. Select an area from the dropdown box, or use the spin button to
cycle through the list.
Find By Number
To find an area by its number, type the number in the Number field and click this button.
Name
A dropdown box that specifies the area’s alphabetic identifier, which may be any length in Simulator. When saving
area names to other load flow formats, the names are truncated at the maximum character length supported by that
format.
Find By Name
To find an area by its name, type the name in the Name field and click this button.
Find…
If you do not know the exact area number or name you are looking for, you can click this button to open the
advanced search engine.
Super Area
To associate an area with a particular super area, either select an existing super area from the dropdown box, or
type the name of a new super area.
Area Control Options
Select to change the area’s method of Automatic Generation Control (AGC.)
Labels
To assign alternative identifying labels to the area, click the Labels button.
The rest of the Area Information Dialog is divided into nine pages of controls:
· Information/Interchange
· Options
· Tie Lines
· Simulation Summary
· Scheduled Power Transactions
· OPF
· Area Buses
· Area Gens
· Memo
313
Area Information: Info/Interchange
The Info/Interchange Tab serves as an accounting sheet for flows into and out of an area. It houses the following
controls:
Load, Generation, Shunts, Losses, Interchange
These read-only fields express the total real and reactive load, generation, shunt compensation, losses, and
interchange for the area.
Base Interchange by Area
Base scheduled interchange in MW between the area and all other areas (exporting pow er is positive). Base
Interchange is interchange for which detailed time-dependent schedules are not modeled. See Area Transactions
Modeling<+> for more information on the difference between Base Interchange and Scheduled Interchange.
Use the Base Interchange by Area Table to set the interchange between the area and all other areas. To
prescribe the interchange with a specific area, simply enter the amount of power in MW to export to that area in the
MW Export column. To specify an import, enter a negative value. If the recipient of the power is unknown, you may
enter the net total in the Unspecified MW Interchange field found above the list of base transac tions.
Check the box Only Show Areas with Nonzero Interchange to display only those areas whose interchange is
different from zero.
By default, one interchange record is initially defined between each area. The total interchange between two areas
can be managed using this single record. However, it is now possible to define multiple base interchange records
between the same areas. To do so, you can right-click in the base interchange table and select Insert from the local
menu. This will open the Transaction Dialog, which will allow you to insert a new transaction. Transactions
between the same two areas must have unique transaction ID’s. Once you have multiple transactions defined
between the same two areas, you can choose which transactions are enabled using the Enabled property in the
Base Interchange table. This field is a toggleable field, meaning you can double-click in the field to toggle its value.
To save the changes you make to this table, be sure to click Save Changes or OK. To sort the entries in any
column in the Base Interchange Table, simply left- or right-click on the column title.
The total Base interchange defined for an area will be displayed in the summary field labeled Base in the lower left
corner of the page.
Scheduled
Current scheduled interchange in MW between the area and all other areas, with power exports represented as
positive. In pure power flow studies, Base Transactions are normally used instead of Scheduled Transactions,
because pure power flow studies usually do not require time or cost information. For a discussion of modeling area
transactions covering how to set up scheduled transactions and the difference between this field and base
interchange, see Area Transactions Modeling.
ACE (Area Control Error)
Current area control error (ACE) for the area in MW. Note that, when the constant frequency model is used, ACE =
area generation - area load - area losses - scheduled area interchange.
Tolerance
The MW tolerance is used in enforcing area interchange. When the absolute value of the ACE is less than this
value, Simulator considers the area interchange constraint to be satisfied.
314
Properties of Simulator Objects
Area Information: Options
Report Limit Violations
If checked, limit violations for this area are reported. Limits violations are reported in the Limit Violations List.
Generation AGC Values
These fields indicate the total available AGC range for all the generators in the zone that are specified as being
on AGC and have nonzero participation factors. That is, these fields show the total amount the generation in the
area or zone that can be increased or decreased using the presently on-line generation. This may be referred to as
the spinning reserve. The generator status, AGC status, and participation factor can be changed on the Generator
Records Display.
Load Schedule
Use this dropdown box to specify the load schedule to use for the area. The load schedule prescribes how the load
in the area should vary with time.
Load MW Multiplier Value
This value is used for scaling the area MW load. The base load remains unchanged.
Load MVAR Multiplier
This value is used for scaling the area MVAR load. The base load remains unchanged.
Area Slack Bus Number
Identifies which bus to model as the area’s slack bus.
Automatic Control Options
The Automatic Control Options section provides a convenient mechanism to enable or disable automatic control of
switched shunts and transformers in the area.
Generator MW Limits
Indicates whether or not generator MW limits should be enforced for the area.
Include Loss Penalty Factors in ED
If this box is unchecked, then the economic dispatch for the area is calculated assuming that the area is lossless.
Otherwise, the solution will incorporate losses when computing the economic dispatch. The penalty factors gauge
the sensitivity of the area’s losses to changing injection at specific generators. The option to calculate loss penalty
factors is relevant only when the area operates according to Economic Dispatch Control . Usually, if the system’s
cost curves are relatively flat, the inclusion of losses in the solution will not have much of an effect on the dispatch.
Economic Dispatch Lambda
The lambda value calculated during the economic dispatch computation. This field is valid only when the area is on
economic dispatch control.
Wheeling Charge
The transmission price charged by the area for wheeling power between two other areas as part of a transaction.
Set Participation Factors
Press this button to open the Generator Participation Factors Dialog, which gives you control over how the
participation factor for each generating unit is defined. If you decide not to prescribe participation factors using this
button, Simulator w ill assign participation factors in proportion to the maximum MW rating of each unit. This button
will be enabled only if the area has been set to Participation Factor area control.
315
Area Information: Tie Lines
The tie line grid shows the flow on all of the tie lines for the area. The grid displays the area name, bus number, and
bus name for each terminal of the tie line, with the local area’s terminal listed first. The next column shows the tie
line’s circuit identifier. The next two columns show the real and reactive power flowing from this area to the other
area. The next column gives the status of the tie line as open or closed. The last two columns show the real and
reactive power losses. The Tie Lines display is a Case Information Display, and contains several of the options
available to these types of displays.
316
Properties of Simulator Objects
Area Information: Simulation Summary
Earlier versions of Simulator employed a distinction between Simulation and Study applications. In Study mode,
system economics are essentially ignored. This mode was used to perform pure power flow studies for which
economics were not a concern. The Simulation mode was commonly applied to timed simulations where area costs
were a primary concern. In terms of the user interface, the only difference between the two modes involved which of
the two varieties of Area Information Dialog were presented to the user. As of Simulator 6.0, the application no longer
enforces this dichotomy between Study and Simulation modes. To maintain compatibility with earlier versions,
however, the Simulation Summary tab has been provided to house the contents of the Simulation-mode Area
Information Dialog.
Total Area Cost
Total area cost in $ from the start of the simulation to the current time.
Hourly Cost
Current average hourly cost for the area in $/hour. Select the Graph Button to the right of this field to display the
Hourly Cost Chart for this area.
Lambda
Current incremental cost for the area in $/MWH. This field is only valid if the area is on Economic Dispatch AGC.
Load
Present area load in MW. Select the Graph Button to the right of this field to display the Load and Generation
Chart for this area.
Generation
Current generation for the area in MW. Select the Graph button to the right of this field to display the Load and
Generation Chart for this area.
Losses
Current real power losses in MW for the area. Select the Graph Button to the right of this field to display the Area
Losses Chart for this area.
Sched. Interchange
Current scheduled interchange in MW between the area and all other areas (selling power is positive) beyond the
base value. Select the Graph Button to the right of this field to display the Area MW Transactions Chart for this
area. For a discussion of modeling area transactions, including how to set up scheduled transactions and the
difference between this field and base interchange, see Area Transactions Modeling.
Area Control Error
Current area control error (ACE) for the area in MW. When the constant frequency model is used, ACE = area
generation - area load - area losses - scheduled area interchange. Select the Graph Button to the right of this field
to display the ACE Chart for this area.
Inadvertent
The inadvertent interchange keeps track of how much energy in MWH beyond its requirements the area has
produced. The inadvertent error increases anytime the ACE is positive (indicating the area is producing too much
power), while it decreases anytime the ACE is negative.
Unserved Load
Current amount of area load that is not being served. To account for the economic costs associated with this
unserved load, the area hourly cost is increased by a value equal to the amount of unserved load times the case-
wide cost for unserved load (expressed in $/MWH), which is specified on the Simulation Tab of the PowerWorld
Simulator Options Dialog.
Base Interchange
Base interchange in MW between the area and all other areas, with exports represented as positive. Base
interchange represents real power transactions for which detailed time-dependent schedules and cost information
are not modeled. See Area Transactions Modeling for more information on the difference between Study
Transactions and Scheduled Transactions.
317
Area Information: Scheduled MW Transactions
The Scheduled MW Transactions tab identifies the scheduled transactions in which the area participates. For more
information on this table, please see MW Transactions Display.
318
Properties of Simulator Objects
Area Information: OPF
The OPF Tab contains information regarding the Optimal Power Flow (OPF) solution data for an area. It houses the
following information:
Average LMP for Area
The computed average locational marginal price of all buses contained in the area.
LMP Standard Deviation
The standard deviation of the locational marginal price for all buses contained in the area.
Min/Max LMP
The minimum and maximum locational marginal price of all the buses in the area.
Total Generator Production Cost (Scaled)
The scaled cost includes the Cost Shift and Cost Multiplier. These two values can be defined for each generator,
and allow the user a way to assess changes to the LMP results when a generators cost or "bid" is modified, without
actually changing the original generator cost or bid curve. The scaled cost function for each generator is equal to:
(original cost function + cost shift) * cost multiplier
Total Generator Unscaled Production Cos t
The total unscaled generator production cost, based on the original generator cost or bid curves.
Total Generator LMP Profit
The profit of the generators in the area based on the Locational Marginal Prices (LMPs) determined by the OPF
solution. The profit is determined as:
LMP Price * MW Output - Unscaled Cost Function
Cost of Energy Reference
Specify a reference for determining the cost of energy. The choices are Cost of Increasing Export, Weighted-
Average of Area’s Bus Loads, or Weighted-Average of Injection Group.
Cost of Losses Reference
Specify a reference for determining the cost of losses. The choices are Existing Loss Sensitivities Directly, Area’s
Bus Loads, Injection Group, or a Specific Bus.
319
Area Information: Memo
The Memo page of the Area Information dialog is simply a location to log information about the area. To log
information about the area, simply switch to the Memo page on the dialog, and start typing your information or
comments about the area in the page.
320
Properties of Simulator Objects
Area Field Options
Area field objects are used to show different values associated with areas and the system. This dialog is used to view
and modify the parameters associated with these fields. Note that the area number itself cannot be changed on this
dialog.
Area Number
Area number associated with the field. When you insert fields graphically, this field is automatically set to the area
number associated with the c losest bus on the oneline. With most types of area fields, an Area Number of 0 is valid
and defines the field as showing values for the entire system.
Find…
If you do not know the exact bus number or name you are looking for, you can click this button to open the
advanced search engine.
Total Digits in Fields
Total number of digits to show in the field.
Digits to Right of Decimal
Number of digits to show to the right of the decimal point.
Rotation Angle in Degrees
The angle at which the text is to appear on the oneline diagram.
Other Area Number
Some of the fields, such as MW Flow to Other Area, require that a second area be specified. If applicable, enter
the second (other) area here.
Other Area Transaction ID
Since it is now possible to have more than one base transaction defined between the same two areas, base
transactions must now also have a unique ID to distinguish between transactions among the same two areas. If
you are displaying a field that pertains to the display of the scheduled flow between areas, the ID of the transaction
in question will also need to be entered here.
Delta MW per Mouse Click
This value is used only with the Sched Flow to Other Area field type. When there is a nonzero entry in this field,
and the field type is Sched Flow to Other Area, a spin button is shown to the right of the area field. When the up
spin button is clicked, the flow to the other area is increased by this number of MW; when the down button is
clicked, the scheduled flow is decreased by this amount.
Field Value
Shows the current output for the area field. Whenever you change the Type of Field selection, this field is updated.
For the Sched Flow to Other Area field type only, you can specify a new value in MW. Exports are assumed to be
positive.
Field Prefix
A prefix that can be specified and displayed with the selected value.
Include Suffix
If the Include Suffix checkbox is checked, the corresponding field units will be displayed after the current value.
Otherwise, only the value without units will be shown.
Type of Field
Used to determine the type of area field to show. The following choices are available:
Name
Area name (eight characters maximum). The Area Number field must correspond to a valid area.
Number
Area number (1 - 999). The Area Number field must correspond to a valid area.
MW Load, Mvar Load
If the area number is nonzero, then these fields show Total MW or Mvar load for the area. If the area number is
zero, these fields show the total load in the entire system.
MW Generation, Mvar Generation
321
If the Area Number is nonzero, then these fields show Total MW or Mvar generation for the area. If the Area
Number is zero, these fields show the total generation in the entire system.
MW Losses, Mvar Losses
If the Area Number is nonzero, then these fields show Total MW or Mvar losses for the area. If the Area Number is
zero, these fields show the total losses in the entire system.
ACE (MW)
Area Control Error in MW for the area. The Area Number field must correspond to a valid area.
Hourly Cost ($/hr)
If the Area Number is nonzero, then this field shows the hourly cost for the area. If the Area Number is zero, these
fields show the hourly cost for the entire system.
Total Cost ($)
If the Area Number is nonzero, this field shows the total cost incurred by the area since the beginning of the
simulation. If the Area Number is zero, this field shows the total cost incurred throughout the system since the
beginning of the simulation.
MW Flow to Other Area, Mvar Flow to Other Area
Total MW or Mvar flow from the area specified in the Area Number field to the area specified in the Other Area
Number field. The Area Number field must correspond to a valid area. If the Other Area Number field is zero, this
field shows the area’s total MW or Mvar exports.
Sched. Flow to Other Area
Scheduled MW transaction from the area specified in the Area Number field to the area specified in the Other Area
Number field, and with the Transaction ID given in the Other Area Transaction ID field. The Area Number field must
correspond to a valid area. If the Other Area Number field is zero, this field shows the area’s total scheduled MW
transactions. If the Delta per Mouse Click value is nonzero, you can use the spin arrows on the oneline to change
this value. A lso, you may directly enter a new value in the Field Value field.
Select OK to save changes and close the dialog or Cancel to close dialog without saving your changes.
Load Schedule Multiplier
Indicates the current value of the multiplier applied to the zone’s loads. See Load Variation Dialog for more detail.
AGC Status
Displays the AGC status of the area.
Select a Field
Choose from all possible information fields that can be displayed for areas.
322
Properties of Simulator Objects
Super Area Properties
Super Area Information Dialog
The Super Area Information Dialog displays information pertaining to Super Area Display. It summarizes the super
area's real and reactive load and generation, scheduled transactions, and constituent areas. It also allows you to
manage the list of areas to include in the super area and to designate how its generation should be controlled. To
display the Super Area Information Dialog, right-click on the Super Area Records Display and select Show Dialog
from the resulting local menu.
The Super Area Information Dialog has the following fields:
Area in Super Area
Name
The list of all super areas that have been defined in the case are listed in this dropdown box. Select one of the
super areas to display its information, or type a new name in the box and click Add New to define the new super
area.
Rename
Click this button to change the name of the super area specified in the Name field.
Delete
Click this button to delete the super area specified in the Name field.
Areas in Super Area
Lists the areas contained in the super area. Right-click on a row and select Remove to remove the area from the
super area.
Super Area Control Options
Specify the type of generation control to employ for the s uper area. The super area may be removed from area
control or employ Participation Factor or Economic Dispatch control. See Area Control for details on these types of
generation control.
An additional type of control available to Super Areas is to Use Area Participation Factors. If the super area is set
to participation factor control, and this option is NOT checked, then the generators within the super area respond by
redispatching to meet the entire super area generation change based on their own participation factors.
However, if this option IS checked, then an additional level of participation control complexity is added for the super
area. First, the total super area generation change is divided across each area forming the super area, according to
the participation factors of the AREAS, as set in the grid on this dialog. Once the total generation change has been
determined for each area within the super area, then the generators within each individual area are dispatched
using area participation factor control to meet each specific area's determined generation change.
New Area Name
Use the dropdown box to select an area to add to the super area. Click the Add New Area by Name to add the
selected area to the super area.
New Area #'s
Enter in a list of area numbers separated with dashes or commas and click Add New Areas by Number button to
add the areas to the Super Area
Summary Information
Total Scheduled Transactions
Lists the total scheduled import or export for the super area. It is computed by summing the scheduled interchange
for all areas comprising the super area. Exports are positive.
Total ACE
The total area control error for the super area. It is calculated by summing the ACE for all areas comprising the
super area.
Lambda
The marginal cost associated with the super area. Lambda is valid only for super areas that are on economic
dispatch control.
Tolerance
The Area Control Error tolerance observed f or the super area during a load flow solution.
323
Load, Generation, Shunts, Losses, Interchange
The Load and Generation section of the Super Area Information Dialog accounts for the real and reactive power
flows into, out of, and within the super area. Each quantity is computed by summing over the areas comprising the
super area.
Hourly Cost
Current average hourly cost for the super area in $/hour.
OPF
The OPF Tab contains information regarding the Optimal Power Flow (OPF) solution data for a super area. It houses
the following information:
Average LMP for Area
The computed average locational marginal price of all buses contained in the area.
LMP Standard Deviation
The standard deviation of the locational marginal price for all buses contained in the area.
Min/Max LMP
The minimum and maximum locational marginal price of all the buses in the area.
Total Generator Production Cost (Scaled)
The scaled cost includes the Cost Shift and Cost Multiplier. These two values can be defined for each generator,
and allow the user a way to assess changes to the LMP results when a generators cost or "bid" is modified, without
actually changing the original generator cost or bid curve. The scaled cost function for each generator is equal to:
(original cost function + cost s hift) * cost multiplier
Total Generator Unscaled Production Cost
The total unscaled generator production cost, based on the original generator cost or bid curves.
Total Generator LMP Profit
The profit of the generators in the area based on the Locational Marginal Prices (LMPs) determined by the OPF
solution. The profit is determined as:
LMP Price * MW Output - Unscaled Cost Function
Cost of Energy Reference
Specify a reference for determining the cost of energy. The choices are Cost of Increasing Export, Weighted-
Average of Area’s Bus Loads, or Weighted-Average of Injection Group.
Cost of Losses Reference
Specify a reference for determining the cost of losses. The choices are Existing Loss Sensitivities Directly, Area’s
Bus Loads, Injection Group, or a Specific Bus.
324
Properties of Simulator Objects
Super Area Field Information
Super area field objects are used to show different values associated with super areas. This dialog is used to view
and modify the parameters associated with these fields. Note that the super area name itself cannot be changed on
this dialog.
Super Area Name
Select the name of the super area for which you are inserting or viewing information of a super area field.
Find…
If you do not know the exact super area name you are looking for, you can click this button to open the advanced
search engine.
Total Digits in Field
Total number of digits to show in the field.
Digits to Right of Decimal
Number of digits to show to the right of the decimal point.
Field Value
Shows the current output for the super area field. Whenever you change the Type of Field selection, this field is
updated.
Field Prefix
A prefix that can be specified and displayed with the selected value.
Rotation Angle in Degrees
The angle at which the text will appear on the diagram.
Include Suffix
If the Include Suffix checkbox is checked, the corresponding field units will be displayed after the current value.
Otherwise, only the value without units will be shown.
Type of Field
Used to determine the type of super area field to show. The following choices are available:
Name
Super area name (eight characters maximum). The super area name field must correspond to a valid super area.
MW Load, Mvar Load
Total MW or Mvar load for the super area.
MW Generation, Mvar Generation
Total MW or Mvar generation for the super area.
MW Losses, Mvar Losses
Total MW or Mvar losses for the super area.
ACE (MW)
Area Control Error in MW for the super area. The super area name field must correspond to a valid super area.
MW Exports
Total MW exports for the super area.
Hourly Cost ($/hr)
The hourly cost for the super area.
AGC Status
Displays the AGC status of the super area.
MW Marginal Cost ($ / MWhr)
MW marginal cost for the super area.
325
Load Variation Properties
Load Variation Dialog
The Load Variation Dialog allows you to define and to modify load variation profiles. These profiles can then be
assigned to specific areas or zones using either the Options tab of the Area Information Dialog or Zone Information
Dialog or the corresponding case information display.
Load profiles, or schedules, are piecewise linear prescriptions of how the load multiplier of any area or zone
associated with the profile should vary over time. Per the Load Modeling discussion, all loads are subject both to a
case load multiplier and to the load multiplier of their corresponding area or zone. The Load Variation Dialog provides
control over both these parameters.
The Case Load Multiplier entry allows you to specify the load multiplier to apply to all loads in the case. The nominal
value of this parameter is 1.0. Please see Load Modeling for further details.
The next section of the dialog, entitled Schedule , enables you to define the load variation. The Name dropdown box
lists all the load variations that have been defined thus far. If you are creating a new load variation, simply ignore the
Name box; you will have the opportunity to assign a name to your new profile when you click Save Record As .
The Time Scale dropdown box controls the granularity of the schedule.
Check the Disable option to deactivate a currently defined schedule. Any area or zone associated with a disabled
schedule will not have its load controlled by that schedule. The option to disable a schedule can be particularly useful
when you want to try several different load profiles for a particular area in subsequent simulations.
The Current Value text box indicates the current value of the profile’s prescribed load multiplier. This is a read-only
field.
Simulator recognizes three types of load profiles: daily, weekly, and weekday/weekend. Define the load schedule as
one of these classes by selecting one of the choices listed under Schedule Type . Daily load profiles specify how load
is to vary over the course of a single day. If the simulation stretches over multiple days, the same load variation will be
modeled for each subsequent day if the active load profile is of type daily. A weekly load profile is actually a
composite of 7 daily load profiles. It allows you to specify load multipliers for each hour of each day of the week. If the
simulation occurs over multiple weeks, the same weekly load variation will be modeled for each subsequent week if
the active load profile is of type weekly. Finally, a weekday/weekend load profile gives you the flexibility to specify
different load profiles for weekdays and weekend days. If all weekdays exhibit the same load variations, specifying a
weekday/weekend schedule will require less work than specifying a weekly schedule, since a weekly schedule
requires you to enter a profile for each day of the week. Use a weekly profile if you want to model the variations in
load peaks and shoulders exhibited by different days of the week.
Following the Schedule Type option is a table listing pairs of time points and load multiple values. This table defines
the schedule for the load variation. If no schedule has been defined, a default schedule is shown with all values equal
to 1.0. If unmodified, the default schedule is automatically deleted. If you do not wish to model a schedule, simply
leave the default schedule without making any modifications.
The schedule table has a local menu that can be invoked by clicking the right mouse button. To insert a new point,
choose Insert Time Point from the local menu, or press the Insert Time Point button. To delete an existing time point,
right click on the record’s Load Scale field and choose Delete Time Point, or press the Delete Time Point button. To
see a plot of the load profile as it is currently defined, press the Show Graph button. To modify the load multiplier at a
particular time, simply edit the corresponding Load Scale field.
Note that you can also edit the load profile from the graph that appears when you click Show Graph. Click on the plot
of the profile to reveal its vertices. The vertices represent the time points listed in the table. When you move the
mouse over a vertex, it becomes a crosshair pointer. When the mouse is in this state, you can move the vertex
around the plot area to modify both the time and the load scale parameters associated with that point. You may
discover and even modify the load scale associated with a vertex by right clicking the mouse when the pointer is a
crosshairs. You may introduce a new time point by holding the CTRL key down and then selecting the curve with the
left mouse button at the point in time where you want to define the new load scale. You can delete a vertex by holding
down CTRL as you select the vertex with the left mouse key. You can adjust the scale of either axis by right-clicking
on the axis. Finally, you may move the entire load profile up or down the load scale or along the time axes by
selecting the curve somewhere other than at a vertex. When you are done modifying the load variation using the plot,
you may close it.
To save the changes you have made to the load profile, click Save Record. To save the load profile to a new
schedule, click Save Record As . Finally, to close the Load Variation Dialog without saving your changes, click
Cancel.
326
Properties of Simulator Objects
Interface Properties
Interface Information
The Interface Dialog is used to create, modify, or delete interface records in both the Edit and Run Modes. This dialog
has the following controls:
Interface Name
An alphanumeric identifier for the interface of up to 24 characters. Use the dropdown box or the spin button to
navigate through the list of existing interface records.
Interface Number
A numeric identifier for the interface, between 1 and 32,767.
Add New Interface
Click the Add New Interface button to define a new interface from the Interface Dialog. When you click this button,
the Interface Name field and Interface Elements table are cleared, requiring you to enter a new name and new
elements.
Delete Interface
Select this button to delete the currently displayed interface. Once the interface record has been deleted, the
Interface Name field displays the previous interface record, if any. If there are not previously defined interface
records, Simulator will close the dialog.
Interface Limits
Specify the possible limits for net interface flow. As for transmission lines and transformers, up to eight distinct
limits can be specified for interfaces. Which limit set is used can be controlled from the Limits Tab of the
PowerWorld Simulator Options Dialog or the Line and Transformer Limit Violations Display.
Direction for Flow Monitoring
This area allows the user to change the flow monitoring direction. Clicking on the interface in the Interface
Elements area will bring up the Interface Elements Dialog. This is where the default direction is set. To keep this
default direction, choose FROM à TO, to change this direction, choose TO à FROM, and to monitor both
directions, choose Both Directions.
Non-contingent MW Flow
Indicates the present net flow through the interface elements, not including affects of contingencies, in MW.
Contingent MW Flow
The amount of flow that would be added to the interface flow if the contingency defined with the interface were to
occur, in MW.
Total MW Flow
The sum of the non-contingent MW flow and Contingent MW flow, for the total MW flow considered on the interface,
in MW.
PTDF Value (%)
The Power Transfer Distribution Factor for the interface, if calculated.
Interface Elements
The Interface Elements Table lists each element comprising the interface. If Simulator is in Run Mode, the table will
also show the present flow through each element. To edit or delete an existing element in the table, click on it to bring
up the Interface Element Dialog. Use the Interface Element Dialog to modify or delete the element.
Insert New Element
Click the Insert New Element Dialog to add a new element to the interface using the Interface Element Dialog.
Click OK to save any changes you have made and to close the Interface Information Dialog. Click Save to save
your changes but to leave the dialog open so that you can view and modify other interface records. Click Cancel to
close the dialog without s aving your latest change.
Element Identifiers
Choose whether to show the interface descriptions using the interface names, the interface numbers, or a
combination of both.
OPF
327
The OPF page will only be visible if you have the Optimal Power Flow add-on for PowerWorld Simulator. This page
contains interface information relating to performing an OPF solution.
Enforce Interface Flow Limit
If checked, the Interface limit will be checked for enforcement during an OPF solution.
Treat Limit as Equality Constraint
If checked, the OPF routine will try and maintain the flow on the interface at its limit value. Otherwise the limit will
be treated as the maximum for an inequality constraint.
Limit Marginal Cost
The incremental cost of maintaining the flow on the Interface at its limit value.
MW Flow on Interface
The actual MW flow on the interface.
Present MW Limit
The currently defined limit for the interface.
Percentage of Limit
The MW flow on the interface as a percentage of the limit.
Flow Limit Unenforceable
This field cannot be changed by the user. If the OPF solution cannot maintain the limit on the interface and reach a
solved state, then this box will be checked by Simulator and the Interface limit will be violated.
328
Properties of Simulator Objects
Interface Element Information
The Interface Element Dialog is used to redefine or to add the individual elements comprising an interface. Individual
lines or transformers, inter-area ties, inter-zone ties, line contingencies, DC lines, injection groups, generators, and
loads may make up an interface. The Interface Element Dialog allows you to add all three varieties of interface
elements to an interface.
The Interface Element Dialog comes in two very similar forms, depending upon how it was invoked. The dialog may
be called from the Interface Information Dialog by clicking on either the Interface Elements Table or the Insert New
Element button.
The Interface Element Dialog contains the following controls:
Element Type
Specifies the type of interface element being investigated or added. Interface elements can be any line or
transformer or, more specifically, they can be groups of lines and transformers that tie two areas or two zones
together. Interfaces can also contain line contingencies, DC lines, generators, loads, and injection groups.
When the selection for Element Type changes, the available Element Identifiers change to allow you to pick the
appropriate elements of that type.
Element Identifiers
Depending upon the Element Type selection, different element identifiers are required to designate the element to
add to the interface. You can search through the list of identifiers to find the particular elements you w ish to include.
Note that the flow direction on transmission line, transformer, and DC line elements will be dependent on which end
of the line you choose as the near bus. The flow will always be measured in the direction of near bus to far bus.
The flow will be positive when flowing from near to far, and negative when flow from far to near. In addition, line
elements also have an additional setting labeled Monitor Flow at To End. This determines which magnitude of
flow should be reported. If checked, the flow at the To end of the line will be reported, otherwise the flow magnitude
at the From end is used.
Insert
If you came to the Interface Element Dialog by pressing the Insert New Element button on the Interface Information
Dialog, only the Insert, Cancel, and Help buttons will be available. Click the Insert button to add the element you
have just defined to the list of elements comprising the interface. After you click Insert, the dialog will disappear,
and the Interface Elements table on the Interface Information Dialog will contain the element you just added.
Replace, Delete
If you arrived at the Interface Element Dialog by clicking on an element in the Interface Elements Table of the
Interface Information Dialog, the Replace , Delete , Cancel, and Help buttons will be visible. Click Replace to
modify the interface element according to your specifications on this dialog. Click Delete to remove the element
from the interface definition.
Cancel
Click Cancel to close the Interface Elements Dialog without saving your changes.
329
Interface Field Information Dialog
Interface field objects are used to show the different values associated with interface records. This dialog is used to
view and modify the parameters associated with these fields. The dialog has the following fields:
Interface Name
Case insensitive name of an existing interface (12 characters maximum).
Find…
If you do not know the exact interface name you are looking for, you can click this button to open the advanced
search engine.
Total Digits in Field
Total number of digits to show in the field.
Digits to Right of Decimal
Number of digits to show to the right of the decimal point.
Rotation Angle in Degrees
The rotation angle at which the text field should be displayed.
Anchored
If checked, the interface field is anchored to its associated interface display object.
Include Suffix
If the Include Suffix checkbox is checked, the corresponding field units will be displayed after the current value.
Otherwise, only the value without units will be shown.
Type of Field
Type of field to show for the interface record. Interface fields may show the interface's name, its MW Limit, MW
Flow, percent loading, or any other interface specific field available by clicking the Select a field option and choosing
a field from the drop-down list.
330
Properties of Simulator Objects
Interface Pie Chart Information Dialog
Interface Pie Chart objects are used to graphically show the percentage flow associated with interface records. This
dialog is used to view and modify the parameters associated with these fields. The dialog has the following fields:
Interface Name
Case-insensitive name of an existing interface (12 characters maximum).
Size
Size of the pie chart. Note that the pie chart's size and color can be set to change automatically when the
interface's loading is above a specified limit. Please see Oneline Display Options for details.
Percent (read-only)
In Run Mode, this field shows the current percentage loading for the interface; if the MVA rating is zero, the
percentage is defined as zero, as well.
MW Rating
MW limit for the interface, using the current limit set for the case.
Anchored
If checked, the interface pie chart object is anchored to its associated interface.
331
Automatically Inserting Interfaces in Case
The Inserting Interfaces Dialog is used to insert a group of interfaces. Only interfaces between adjacent areas or
adjacent zones can be inserted automatically; single-branch interfaces between buses must be inserted with line
insertion options. Adjacent areas or zones are those that share at least one tie line. To reach this field, go to Case
Information > Interfaces and then right-click on the display to bring up the submenu. From the submenu choose
Auto Insert Interfaces. This dialog is NOT brought up through the menu item Insert > Auto Insert > Interfaces,
which is for inserting interface objects on an oneline diagram.
The Inserting Interfaces Dialog sports the following fields:
Type of Interfaces to Insert
Select the type of interfaces to insert. Area-to-area interfaces join adjacent areas, while zone-to-zone interfaces
join adjacent zones. The name of the new interface defaults to "Area1- Area2" or "Zone1-Zone2" with an Optional
Prefix.
Optional Prefix
This field allows you to specify an optional prefix of up to three characters. Use this prefix to avoid duplicating
names, particularly when some of the areas or zones have the same name.
Delete Existing Interfaces
If this option is checked, then all existing interfaces are deleted before inserting the new interfaces. By default, this
option is checked. If this option is not checked, the existing interfaces are not deleted. However, new interfaces will
automatically overwrite any existing interfaces having the same name.
Only Insert Between Areas/Zones with Area/Zone Filters Set
If this option is checked, the set of potential areas or zones for inserting interfaces is limited to those for which the
area/zone filter setting is Yes .
Limits
Simulator can either calculate an interface rating based on the ratings of the components included in the interface,
or the user can specify a set of ratings to be used for the interface. If neither of these options is used to set an
interface limit, then by default, the interface limits are left as 0, indicating no limit has been applied.
Insert Interfaces
Click this button to insert the interface records into the case.
Cancel
Closes the dialog without modifying the list of interfaces.
332
Properties of Simulator Objects
Nomogram Information Dialog
The Nomogram Dialog is used to create, modify, or delete nomogram records in both the Edit and Run Modes.
Nomograms are used for combining a pair of interface objects for the purpose of monitoring a combined flow
restriction on the two interfaces together.
This dialog has the following controls:
Nomogram Name
An alphanumeric identifier for the nomogram.
Interface A
The first interface forming the interface pair. To add the interface from scratch in the nomogram dialog, click on the
Insert New Element button. In this manner you will be creating the interface from the individual elements, the
same as creating an interface on the interface dialog. If you already have an interface defined, and wish to clone
the elements of that interface for this nomogram, use the button labeled Clone Elements From to find the interface
and copy the element definition.
Interface B
The second interface forming the interface pair. To add the interface from scratch in the nomogram dialog, click on
the Insert New Element button. In this manner you will be creating the interface from the individual elements, the
same as creating an interface on the interface dialog. If you already have an interface defined, and wish to clone
the elements of that interface for this nomogram, use the button labeled Clone Elements From to find the interface
and copy the element definition.
Nomogram Breakpoints
This section is used for defining the limit boundaries for the interface. The limit boundaries are defined by inserting
nomogram breakpoints. These breakpoints correspond to a pair of MW flow s on each interface. In other words,
you define the amount of flow allowed on Interface B when interface A is at a certain amount. Typically you will
have a flow limit on Interface B that is constant for a certain range of flow in interface A. However, at some point as
the flow on Interface A increases, the limit of flow on Interface B can start to decrease due to desired flow limit
restrictions of the combined interfaces. At some point, the limit of Interface A would reach a maximum amount and
remain constant, and the range of flow on interface B would be fairly small due to the heavy loading in Interface A.
To build this Nomogram Limiting Boundary, begin by right-clicking in the Nomogram Breakpoints list and choose
Insert Point. Note that the boundary definition must be a convex piecewise linear curve. You would typically being
by defining the flow limit allowed on Interface B when the flow on interface A is small or zero. Then define
breakpoints where the limit on B decreases as the flow on A increases. Eventually you will define a point where the
flow on A reaches a limit as the flow on B continues to decrease towards zero. In short, the nomogram limiting
boundary is actually a combination of boundary limits that are scaled combinations of the individual interface limits.
See the image below for an example of a nomogram limiting boundary.
333
334
Text-Based Information Displays
Chapter 8: Text-based Information Displays
This chapter describes the case information displays. The case information displays are used to display information
about the case, regardless of whether or not it is shown on the onelines.
The following material is included:
· Fundamentals
· Summary Displays
· Area and Zone Displays
· Bus Displays
· Substation Displays
· Generator Displays
· Load Displays
· Line and Transformer Displays
· Switched Shunt Displays
· Interface Displays
· Injection Group Displays
· Island Displays
· Transaction Displays
· Limit Violation Displays
· Ownership Displays
· Load Flow Displays
Fundamentals
Case Information Displays
Simulator offers several Case Information Displays that provide a convenient, spreadsheet-like view of the power
system and its components and are available regardless of whether the case has an associated oneline diagram or
not. The Case Information menu item provides a link to these displays. Case information displays are available for
buses, bus mismatches, generators, generator costs, ac lines, transformers, transformer impedance correction tables,
dc lines, interfaces, areas, zones, schedules, and many other types of objects. Other screens, such as the
Area/Zone/Owner Filters and Limit Violations displays to name a couple, also fall into the category of case information
displays. There are many different characteristics associated with the Case Information Displays, as discussed in the
following topics:
Colors and Cell Styles
Using Cell Handles
Local Menu Options
Sorting Records
Configuring the Case Information Displays
Finding Records
335
Case Information Displays
Configuring the Case Information Displays
The content and format of all case information displays can be controlled through the Display / Column Options dialog.
This dialog can be viewed by clicking Display/Column Options from the case information display’s local menu.
To reset all case information display properties to their default settings, including column and data field associations,
click the Reset All to Default Values button.
To save your changes and close the dialog box, click OK. To save your changes without closing the dialog box, click
Save. To undo the changes you have specified and close the dialog box, click Cancel. Finally, click Help to view the
corresponding help screen.
Column Options
Available Fields
This list contains all the fields available for addition to the respective case information display. You may select
several entries from this list by holding down the Shift and Control keys. Hold down the control key to select several
individual fields. Hold down the Shift key to select all fields between two successive mouse clicks. You may then
add multiple fields to the Shown fields (see Add below).
Show these fields in this order
This list contains the fields which are presently shown on the respective case information display. You may select
several entries from this list by holding down the Shift and Control keys. Hold down the control key to select several
individual fields. Hold down the Shift key to select all fields between two successive mouse clicks. You may then
remove multiple fields (see Remove below) or move the order of fields (see Move below).
Column Width
Enter a new value to adjust the physical width of the column. This will affect all fields selected in the Show these
fields list.
Total Digits
The number of digits to use when displaying values in the column (including the decimal point.) This will affect all
fields selected in the Show these fields list.
Decimal Places
Number of total digits to the right of the decimal point. This will affect all fields selected in the Show these fields list.
< Remove (Removing Columns)
Click the < Remove button to remove the fields that are currently selected in the Show these fields list. You may
also click on the selected fields in the Show these fields list and drag and drop the fields on the Available fields.
Add > (Inserting Columns)
Click the Add > button to add all selected available fields to the end of the Show these fields list. You may also
click on the selected Available fields and drag and drop the field on the Show these fields list. When drag/dropping
the fields, all selected fields will be inserted just before the field that the mouse is over when you drop the fields.
Once you have added fields you may then utilize the
Move Up, Move Down (Moving Columns)
If you selected a block of fields in the Show these fields list, you may change the order of the list by clicking on the
Move Up or Move Down button.
Highlight Key Fields
Checking this option will highlight the key fields for the type of object displayed in the case information display
presently being modified. The fields highlighted in Yellow in the two lists are either the Primary key fields
(numbered) or the Secondary key fields (lettered). Note that some key fields, usually the Circuit ID, are both
numbered and lettered, meaning they are used as both Primary or Secondary key fields. Either ALL numbered key
fields OR all lettered key fields must be included in the list of shown columns if you intend to export the data to
either Excel or a text file, modify it, and paste it back into Simulator.
The fields highlighted in Green are the fields that would be necessary in Excel or an auxiliary file in order to create
NEW objects of the type displayed when pasting from Excel or reading in an auxiliary file. If all of the green
highlighted fields are not present in the external source, Simulator will not be able to create new objects that may be
defined in that source, and will only paste information for objects that already exist in the present case.
Frozen Columns
The number of columns that are fixed and do not scroll when you scroll left or right in the display. Frozen columns
will have a background color of gray instead of white. The number of frozen columns is 1 by default.
336
Text-Based Information Displays
Display Options
Automatically Refresh
Check this box to ensure that data presented by the case information displays always reflects the current state of
the system. Generally, you will want to have the case information displays refresh automatically. However, for
large systems, having several automatically refreshing case information displays open simultaneously may hamper
program performance.
Use Area / Zone Filters
Check this box to restrict the case information display’s record set to cover only those areas and zones specified by
the area/zone/owner filters. If this box is unchecked, all records, regardless of zone or area, will be displayed. (The
area/zone filters option obviously does not apply to the Area/Zone Filters information display.)
Advanced Filter
Clicking this button will open the Advanced Filters Dialog, which will allow more detailed filtering on the display.
Use Custom Font / Row Height
If checked, then the Row Height and Custom Font specifications will be used. Changing either the Row Height or
Custom Font properties will cause this box to become checked automatically. If you wish not to apply your custom
specifications to the active case information display, uncheck this box; the default font and row height settings, as
defined under the Case Information Displays tab of the PowerWorld Simulator Options dialog box, will be reapplied.
Row Height
Defines the height of the rows of the case information display.
Change Custom Font
Defines the font with which to display the records.
Set as Default
Sets the current Font and Row Height as the defaults.
Auto Size all Column Widths
Constrains all field widths to contain the widest data elements in each column.
337
Case Information Displays: Local Menu Options
All case information displays have a set of local menu options. The local menu can be brought up at any time by right
clicking on case information display. The following local menu options are common to most case information displays.
Additionally, many local menus of case information displays have specific menu options that are only available for the
type of object being displayed.
Find
Use the Find local menu option to retrieve a record pertaining to a particular element. Choosing Find from the local
menu will open the Find Dialog Box, which may be used to find records pertaining to an element identified by either
number or name.
Search for Text
Use the Search for Text local menu option to find text inside the Case Information display. Choosing Search for
Text from the local menu will open the Search for Text Dialog, which may be used to find the specified text in a list
display.
Contour Column
Use the Contour Column local menu option to contour a column of the list display. Choosing Contour Column from
the local menu will open the Contour Column Dialog.
Display/Column Options
The contents and format of the information display can be controlled using the Case Information Display Dialog.
See Configuring the Case Information Displays for more details.
Show Dialog
Selecting the Show Dialog option will invoke a dialog box containing more detailed information and settings
regarding the corresponding system object. For example, clicking Show Dialog from the local menu of a Bus Case
Information Display will bring up the Bus Information Dialog.
Quick Power Flow List
Use the Quick Power Flow List local menu option to invoke Simulator's Quick Power Flow List tool.
Bus View Oneline
Use the Bus View Oneline local menu option to bring up the Bus View Display, which illustrates how the selected
bus is connected to the rest of the system.
Copy All
The Copy All menu option copies the entire record set contained in the case information display to the Windows
clipboard, from which it can be copied into other programs such as Excel for further analysis. See Copying
Simulator Data to and from Other Applications for more details.
Copy Selection
The Copy Selection menu option copies the records selected in the case information display to the Windows
clipboard, from which the selection can be copied into other programs such as Microsoft Excel for further analysis.
See Copying Simulator Data to and from Other Applications for more details.
Send All to Excel
The Send All to Excel menu option copies the entire record set contained in the case information display and
automatically sends it to Excel. The first time this option is selected, Simulator will start a new instance of Excel on
your machine and paste the data on the first sheet. Subsequent calls to Send to Excel will continue to add sheets
and paste data to this instance of Excel, until the Excel instance is closed manually by the user.
Send Selection to Excel
The Send Selection to Excel menu option copies the selected record set in the case information display and
automatically sends it to Excel. The first time this option is selected, Simulator will start a new instance of Excel on
your machine and paste the data on the first sheet. Subsequent calls to Send to Excel will continue to add sheets
and paste data to this instance of Excel, until the Excel instance is closed manually by the user.
Copy / Send Special
The Copy / Send Special menu option will open the a dialog that allows the user to set a few custom options before
completing the data copy. The user can choose to copy all or a selection, and to copy the data either to the
Windows clipboard or send it directly to Excel. In addition, the user can choose whether to use the normal column
headings or variable names as column identifiers. Lastly, the user can specify whether or not to include a row
containing the type of object the data represents (Object Name) and a row containing the column headers for each
column of data. Note that for pasting the information back into Simulator, the Object Name and Column Heading
338
Text-Based Information Displays
rows must be contained with the data to be pasted. If you have changed the settings on this dialog and wish to
make them the case default settings, click on the Make Default for all Copy Actions button.
Paste
Select Paste from the local menu to copy a record set from the Windows clipboard into the case information display.
See Copying Simulator Data to and from Other Applications for more details.
Print
You can print the contents of most of the case information displays by selecting Print from the local menu.
Save As
This option will save the contents of the case information display to an external file.
Auxiliary File
This option allows saving all the contents of the case information display to an auxiliary file.
Auxiliary File (Only Selection)
This option allows saving the selected record set in the case information display to an auxiliary file.
CSV (Comma Delimited)
This option allows sav ing all the contents of the case information display to a comma delimited file.
CSV (Only Selection)
This option allows saving the selected record set in the case information display to a comma delimited file.
HTML
You can save the entire table or selected records to an HTML file for viewing from an Internet browser. For
more information, see Saving Case Information Display Contents as HTML Tables.
Bitmap
This option allows saving the case information display into a Bitmap picture file.
JPeg
This option allows saving the case information display into a JPEG picture file.
Load
This option will load the contents of an external file to the case information display.
Auxiliary File (Any Data)
This option allows loading an auxiliary file containing any data.
Auxiliary File (Only Specific Data)
This option allows loading an auxiliary file containing only data related to the current case information display.
Advanced Filter
Allows the user to custom filter the information in the display based on desired criteria. See Advanced Filtering for
more information.
Advanced Sort
Allows the user to custom sort the information in the display based on desired criteria.
Define Expression
Allows you to define Custom Expressions that are functions of other fields.
Get Column Metrics
This option allows you to compute the metrics for the selected column. Choosing Get Column Metrics from the
local menu will bring the Grid Metrics Dialog. This option is only available for columns whose content is numeric.
Refresh Display
Select this option to update the currently displayed data to match the present state of the system.
Why is this field or line disabled?
This option will display a message showing the reason why the field is disabled. This option will be enabled only if
the field is actually disabled.
Help
Display context-sensitive help for the case-information display.
Form Control
This menu option allows to control the case information display.
Close
Closes the case information display.
339
Make Top Left of Form Visible
Makes the top or the left of the case information display visible, if either the top or the left are not visible.
Shift Form Up
Moves the case information display up so the bottom of the case information display can be visible.
Maximize
Maximizes the size of the case information display.
Unmaximize (Re store)
Restores the size of the case information display.
Minimize
Minimizes the size of the case information display.
340
Text-Based Information Displays
Case Information Displays: Colors and Cell Styles
The case information displays distinguish data field types by text color and cell style. Most of the entries on the case
information display are colored using the following color convention. These colors can be customized using the Case
Information Displays tab on PowerWorld Simulation Options Display , which can be invoked by selecting Options >
Solution/Environment from the main menu.
There are three types of data fields:
Standard Fields
Fields that cannot be modified directly from the case information display are colored black
by default.
Enterable Fields
Fields that can be modified are colored navy blue by default. When selected, a cell
containing an enterable field will display a tiny filled square in its bottom right corner. This box is called a cell.
Toggleable Fields
Fields whose values can be toggled are colored green by default. The values contained
in toggleable fields are modified by left-clicking on them. Like cells in enterable fields, cells in toggleable fields
display a cell handle when selected.
Besides indicating field type, color coding is also used to highlight violations of branch flow, generator MW or MVR
output, and bus voltage constraints. Fields that are either at a limit or violating a limit are colored red by default. This,
too, is configurable from the Case Information Displays tab on PowerWorld Simulation Options Display .
341
Case Information Displays: Using Cell Handles
When selected, cells corresponding to enterable and toggleable fields exhibit a small filled square in their bottom right
corner called a cell handle. The cell handle may be used to propagate the value of the selected cell to other cells in
the same field.
Suppose we have selected a toggleable or enterable cell and that we wish to copy its value to other records. Call this
cell the source cell and its value the source value. To copy the source value to another record or records, perform the
following steps:
· Drag the mouse onto the cell handle until the pointer becomes a crosshair.
· With the mouse pointer showing as a crosshair, click and hold the left mouse button.
· With the left mouse button depressed, drag the mouse up or down from the source cell to select a group of records
to which to c opy the source value. These destination cells will display a yellow background when selected in this
manner.
· When you have finished selecting the destination cells, release the left mouse button.
· A message box will appear asking whether you want to change the values of the destination cells to the source
value. Answer Yes to complete the copy.
342
Text-Based Information Displays
Case Information Displays: Sorting Records
You can sort the entries on the case information displays by just about any field. To sort the records by a particular
column, left-click on the column’s heading. Left-click the column’s heading again to reverse the sort order.
To sort the records by the absolute value of a field, hold down the shift key as you left-click on the field’s heading.
Simulator also has a more advanced sorting tool, which can be accessed by selecting Advanced Sort from the local
menu. Advanced sort allows you to sort information based on values in more than one column of data. Advanced sort
also allows you to sort based on the absolute value of numerical fields and by case sensitivity for string fields.
343
Case Information Displays: Finding Records
The Find Dialog is used to find the device of the specified type on the different Case Information displays. The Find
Dialog is available on most case information displays from the local menu, which can be invoked by right-clicking in
the grid.
Different Find dialogs exist for Areas, Buses, Interfaces, Lines and Zones. Note that the Bus Dialog is used to locate
all bus objects, such as generators, loads, switched shunts and the bus itself. In general, the format of each dialog is
similar, allowing you to find the desired object using either its number or name. The only exception is interfaces, for
which no name is defined. The basics of the Find dialog are explained in the Find Dialog Basics help topic.
344
Text-Based Information Displays
Filtering
Area/Zone/Owner Filters
The Area/Zone/Owner Filters Display, invoked by clicking Case Information > Area/Zone/Owners Filters from the
main menu or the corresponding button on the Options/Info Toolbar, allows you to filter the information shown on the
case information displays and other dialogs by area, zone or owner. For small cases, you will usually not need to use
this filtering capability, but it can be essential for large cases. The filters display lists each area, zone and owner in the
case, the number of buses in each, the range of bus numbers contained in each, and whether or not information about
that area, zone or owner should be displayed. In order for a device to be displayed, its area, zone and owner Shown
property must be set to yes.
You can switc h between displaying the filters for the case areas or the zones by clicking on the associated tab.
The Filters list is itself a case information display and therefore shares many of the same local menu options and
characteristics. Using the local menu, you can search for an area, zone or owner by number or by name, copy
records to and from other applications, and send the records to a printer. You can inspect an area, zone or owner by
selecting Show Dialog from the local menu, which invokes the Area Information , Zone Information or Owner
Information Dialogs. You can also change the format and content of the filters display by selecting the Display
Column/Options item from the local menu. The records can be sorted by any of its component fields simply by clicking
the corresponding column’s heading.
The display’s only enterable field is the one entitled Shown, which may assume only the values Yes and No. For
example, if the Area/Zone/Owner Filters setting for an area is No, then any case information display configured to
enforce area/zone/owner filters will omit the area’s elements from the resulting record set. You can specify whether a
particular case information display enforces filters using the display’s Display/Column Options Dialog.
Double-click on a cell in the Shown field to toggle its value. Use the cell handle to propagate a particular value to
multiple areas, zones or owners, or use the Toggle All Yes or Toggle All No local menu options to set the values of all
area, zone or owner records.
345
Advanced Filtering
Simulator has always had the ability to filter data by Area and by Zone. This is known as Area/Zone/Owner Filtering.
Simulator also contains the ability to perform custom filtering on case information displays as well. Advanced Filtering
is accessed by right-clicking on a Case Information Display and choosing Advanced Filter from the local menu. This
brings up the Advanced Filters Dialog, which allows you to custom filter the information in the display. Advanced
Filters are stored with your Power System Case.
A Case Information Display will have the phrase "(advanced filter)" in its caption if an Advanced Filter has been
applied to it. To remove a filter from a Case Information Display, bring up the Advanced Filters Dialog and and click
on Remove . Note that Remove does NOT delete the filter, but just stops using it to filter the data. You can always
remove the filter temporarily and then come back into the Advanced Filters Dialog and reapply the filter. If you want to
Delete a filter, you must bring it up in the Advanced Filters Dialog and click on Delete .
346
Text-Based Information Displays
Advanced Filters Dialog
When you open this dialog, you will only see filters that have been defined f or the type of object you are trying to filter
(e.g. Bus, Generator, Interface, etc…). You can choose a filter from the Filter Name drop-down box showing the list of
filters available, or you can create a new filter. To make a new filter, simply click on Save As to save a copy of the
present filter under a new name and then specify the properties of the filter as discussed below. When you have
specified the filter as you wish, click Filter.
Note that advanced filters are stored with the case file when the case is saved. In addition, the filters can be exported
to a Simulator Auxiliary File for storage and import into other cases. A list of all advanced filters defined for a case can
be viewed in the Advanced Filters case information display.
To create an Advanced Filter you must specify the following things:
Filter Name
A string that describes your filter so that you can call it up from other forms in the future.
Condition 1, Condition2, etc…
Describes the conditions of your filter. To define a condition
· Specify the field you are filtering. By default, the fields in the drop-down list are limited to the fields presently
shown as columns in the display. If you wish to choose from a list of all fields for the object, change the radio
button setting to Show All Fields .
· Specify the comparison operation such as "between" or "greater than".
· Specify the values the field is compared to. Depending on the comparison operation, either one or two values
are needed.
· Select ABS to use the absolute value of the field value in the comparison operation.
Note: The comparison operation "within integer range list" uses the same format as described in Entering a Range
of Numbers.
Note: To add or delete conditions click on the Add>> or Delete… button
Logical Comparison
The following describes how the Filter uses the Conditions which are specified
· AND means that all conditions should be true
· Not AND is the opposite of AND (i.e. any one of the conditions can be false)
· OR means that any one of the conditions can be true
· Not OR is the opposite of OR (i.e. all of the conditions must be false)
For advanced logical comparisons within the same filter, refer to the important note below.
Pre-Filter using Area/Zone Filters
When this box is checked, data is filtered first by the Area/Zone/Owner Filters and then by the Advanced Filter,
therefore the data must meet both filters in order to be shown. When this box is unchecked, the Area/Zone/Owner
Filters are ignored.
Enable Field to Field Comparisons
When this box is checked, it is possible to compare two fields. In order to do so, select Field and click on Find to
select the second field to be compared.
Important Note : once you choose a condition comparison type, that type is used for all conditions in the filter.
Therefore if you wish to use the AND condition, all conditions you define will be applied using AND. There is a way to
combine different conditions within the same filter. This is accomplished by allowing nested filters. In other words,
one condition of a filter can be that another filter is met. To refer to one filter from within another, set the Field of the
condition to the last item in the list, labeled "_UseAnotherFilter". Then choose whether the condition is to meet the
filter or Not meet the filter, then choose the f ilter (which must have been previously defined) from the drop down list of
the third box, or by clicking the Find button.
347
Advanced Filters Display
The Advanced Filters Display is a Case Information Display available from the Case Information > Other >
Advanced Filters menu option. The purpose of this display is to list any advanced filters you have defined for the
current case. Each record will list the name of the filter, the type of object the filter is for, filter logic, and whether or not
a pre-filter was used. Advanced filters cannot be created or deleted manually from this display, but they can be saved
to an auxiliary file or loaded from an auxiliary file by right-clicking on the display and choosing the appropriate Save As
or Load option from the popup menu.
348

 

 

 

 

 

 

 

Content      ..     7      8      9      10     ..