PowerWorld Simulator version 11. Manual - page 4

 

  Главная      Manuals     PowerWorld Simulator version 11. Manual

 

Search            copyright infringement  

 

 

 

 

 

 

 

 

 

 

 

Content      ..     2      3      4      5     ..

 

 

 

PowerWorld Simulator version 11. Manual - page 4

 

 

Creating, Loading, and Saving Simulator Cases
5
Delta - Wye
6
Grounded Wye - Delta
7
Delta - Grounded Wye
8
Delta - Delta
Switched Shunt
SSHUNT busnum numblocks Bzer1 Bzer2 …
where
busnum
terminal bus number,
numblocks
number of different zero sequence admittance blocks,
Bzer#
zero sequence susceptance for each admittance block, maximum of 8.
Mutual Impedance
MUTIMP from1 to1 ckt1 from2 to2 ckt2 RM XM start1 end1 start2 end2
where
from1, to1
from and to bus numbers of the first mutually coupled branch,
ckt1
circuit identifier of the first mutually coupled branch,
from2, to2
from and to bus numbers of the second mutually coupled branch,
ckt2
circuit identifier of the second mutually coupled branch,
RM, XM
zero sequence mutual resistance and reactance,
start1, end1
start and end locations of the section of the first line affected by the mutual
coupling, with each point represented as a percentage of the total line length
(between 0 and 1),
start2, end2
start and end locations of the section of the second line affected by the mutual
coupling, with each point represented as a percentage of the total line length
(betw een 0 and 1).
103
Exporting Onelines in Different Graphic Formats
Simulator can export oneline diagrams and other graphical displays as bitmaps, metafiles, or jpegs. Select File >
Export Oneline from the main menu. A save file dialog appears where the dropdown menu for files type offers three
choices: JPEG, BITMAP, METAFILE. Select the file type and choose he name before clicking the save button.
Exporting an image as a jpeg also requires you to set the compression ratio for the picture. See Saving Images as
Jpegs for more information.
104
Creating, Loading, and Saving Simulator Cases
Saving Images as Jpegs
Simulator can save oneline diagrams, bus view displays, and strip charts as jpeg images. To save a oneline diagram
or bus view display as a jpeg, select File > Export Oneline from the main menu. This brings up the save file dialog
where y ou can specify file type from the dropdown menu. Choose jpeg, type the file name, and press save. This
brings up the resolution screen where you decide the picture's resolution. Adjust the resolution control to specify the
compression ratio at which to save the diagram as a jpeg. The greater the resolution you specify, the larger the
resulting file will be. Click Save to save the image or click Cancel to terminate the process without saving the image
as a jpeg.
To save a strip chart as a jpeg image, right-click on the background of the strip chart and select Save As Jpeg from
the resulting local menu. Specify the compression/resolution in the Jpeg Options Dialog. Click Cancel to terminate
the process, or click Save to save the jpeg to a file whose name you specify.
105
Saving Admittance Matrix and Jacobian Information
The Save Ybus or Power Flow Jacobian Dialog is used to store the power system bus admittance matrix (Ybus)
and/or the power f low Jacobian in a text format that can be easily read into other programs such as MATLAB“. This
dialog is primarily designed for users doing power system analysis research. The dialog has the following fields.
Ybus in MATLAB Format
Filename for Saving Ybus
Enter the name of the file in which to store the Ybus data. The Ybus data is stored using the MATLAB sparse
matrix format in the matrix Ybus . If the Include Bus Voltages field is checked, then the bus voltages are also
stored, but in the vector V.
Save Ybus in MATLAB Format
Click this button to save the Ybus.
Power Flow Jacobian in MATLAB Format
Jacobian Save File
Enter the name of the file in which to store Jacobian data. The Jacobian is stored using the MATLAB sparse matrix
format in the matrix Jac.
Jacobian ID Save File
Enter the filename to store the text identifier information. This information is used to translate the bus numbering
convention used in the Jacobian and Ybus files with the actual bus number and name in the case.
File Type
Choose the type of MATLAB file you wish to save as. The MATLAB .M Format is the more common text format
used for directly loading MATLAB information. The Text for MATLAB Ascii is for use with MATLAB’s ability to
read Ascii files. The Ascii file type can be read into MATLAB much faster than the traditional .M files.
Jacobian Form
Select Rectangular to store the rectangular form of the Jacobian, or Polar to store the polar form of the Jacobian.
Save Jacobian
Click this button to save the Jacobian and object identifier information.
106
Building a Oneline Diagram
Chapter 4: Building a Oneline Diagram
The oneline objects provide a key means of interacting with the power flow simulation. This chapter provides a
reference on how to insert each of the different types of objects shown on the oneline diagram, and an overview of
Edit Mode. Note that when you are using the Simulator, you can obtain context sensitive help for oneline objects by
positioning the cursor on the desired object and pressing the F1 key.
The following material is included:
· Edit Mode Overview
· Areas, Zones and Owners
· Buses
· Substations
· Generators
· Loads
· Transmission Lines
· Transformers
· Series Capacitors
· Switched Shunts
· Interfaces
· Oneline Links
· Background Objects and Text
107
Overview
Edit Mode Overview
The Edit Mode is used to create and/or modify cases and onelines. You can use the Edit Mode to create a case from
scratch or to modify existing power flow cases stored in PowerWorld PWB or AUX files, in the PTI Raw data format,
GE PSLF EPC data format, or the IEEE Common Format. New users may wish to view step-by-step tutorials on either
Creating a New Case from Scratch
Creating Onelines for an Existing Power Flow Case.
To enter the Edit Mode, select the Edit Mode button on the Program Toolbar, or choose File > Switch to Edit Mode
(will only be visible if you are in Run Mode) from the file menu.
A powerful capability of the Simulator is its ability to create or modify a case by graphically placing/editing display
objects on a oneline diagram. These display objects consist of both power system devices, such as buses,
generators, and transmission lines; and additional objects that show various system parameters, provide descriptive
text, or function as a static background.
Simulator’s oneline diagrams illustrate the current state of the components of the power system. Most display objects
correspond to records in the underlying power system model, but not all records in the power system model need to
have an associated display object. In fact, for large system models, it may be that most of the system will not be
illustrated. In such cases, you will want to devote more detail to the more critical areas of the system so as not to
clutter the view. Furthermore, it is possible to associate more than one oneline with a single power flow case, and a
single oneline may be associated with multiple cases. This great flexibility can prove to be a big time-saver. Please
see Relationship Between Display Objects and the Power System Model for a more thorough discussion.
108
Building a Oneline Diagram
Edit Mode General Procedures
In order to simplify the process of graphically constructing a power flow case, Simulator’s drawing interface obeys the
following conventions for most objects:
Inserting a New Object
· Select the type of the object you wish to add from the Insert MenuInsert_Menu<+>.
· Left-click on the location on the display where you would like to position the object.
· Once the object is placed, Simulator displays a dialog box that allows you to specify various options for the object.
· If desired, use the Format Menu to change the appearance of the object once it has been placed.
Moving or Resizing an Existing Object
· Select the object by clicking on the object with the left mouse button. Handles are displayed around the object to
indicate it has been selected.
· To move the position of the object, place the mouse anywhere on the object except at a handle location. Then drag
the object around the screen by holding the left mouse button down.
· To change the size of an object using the mouse, first select the object. Then place the mouse on one of the
object’s resizing handles. The cursor will change to either a horizontal, vertical or diagonal two-headed arrow
shape. Then drag the mouse to change the object’s size. Text/field objects cannot be resized; rather, you should
change their font size. You can also specify the size of most objects using their dialog boxes.
Viewing/Modifying Object Parameters
· To view and/or change the options associated with an object, right-click on the object. This either displays the
object’s dialog box directly, or it display’s the objects local menu, from which you can elect to see the object’s dialog
box.
Selecting Several Objects to Modify Their Appearance
Hold down the Shift key while clicking objects on the screen to select several objects at once. You may then
change the objects’ attributes, such as Font, Line/Fill, etc., by choosing Display/Size from the Format Menu. To
move the objects that are selected, click and hold down the left mouse button on any of the selected objects, drag
the selected objects to a new location, and release the mouse button to place them.
To select a set of objects that meet some given criteria, choose Select by Criteria from the Edit Menu. As an
example, you can use Select By Criteria to select all the 345 kV transmission lines in a case.
You can also use the Rectangle Selector button on the Edit Toolbar to select all objects in a particular region of the
oneline.
Changing An Object’s Screen Appearance
Use the Format Menu to change the screen appearance of either a selection of objects or the entire display.
109
Insert Menu
The Insert Menu contains the key selections for creating or modifying the oneline diagram, and hence the associated
case. The options on this menu are only available in Edit Mode with an existing or new oneline diagram for the
currently loaded case file open. Most of the insert activities are accessible from the Insert Toolbar, as well.
The insert menu provides a convenient means of inserting new objects into the case by graphically placing them on
the oneline diagram. The user can also use the insert menu to insert fields, background objects, text, pictures or links.
See Case Information Display for details on modifying data that is not necessarily shown on the oneline.
110
Building a Oneline Diagram
Oneline Display Options
The Oneline Display Options Dialog allows you to customize the appearance of the presently selected oneline
diagram. To view this dialog, either select Options > Oneline Display from the main menu or choose Oneline
Display Options from the oneline’s local menu . Please see the Oneline Display Options Dialog help for Run Mode
and Edit Mode for more information.
111
Anchored Objects
While in Edit Mode, Simulator allows certain objects to be attached, or anchored, to another object, called the anchor.
When an object that functions as an anchor is moved, all objects that are anchored to it will move with it. This feature
can be very useful when you move objects around the oneline diagram in Edit Mode.
Anchoring has the property of "stacking" in Simulator. In other words, one object is anchored to another, which is in
turn anchored to yet another. The best way to describe this is by example. A generator text field can be anchored to
a generator. The generator, in turn, can be anchored to its terminal bus. If you move the terminal bus, both the
generator and its anchored fields also move with the bus. However, if you just move the generator itself, only the
generator fields will move with it. The bus and all other objects anchored directly to the bus remain in their original
location.
There are several types of anchored objects:
Buses
Loads, generators, switched shunts, bus fields, interfaces, transformers, transmission lines and voltage gauges may
be anchored to their associated bus. When the anchor bus is moved, these anchored objects will move with it.
Substations
Similar to buses, any loads, generators, switched shunts, substation fields, interfaces, transformers, and
transmission lines may be anchored to their associated buses. When the anchor substation is moved, these
anchored objects will move with it.
Generators
Generator fields may be anchored to their associated generator. When the anchor generator is moved, these
anchored objects will move with it.
Loads
Load fields may be anchored to their associated load. When the anchor load is moved, these anchored objects will
move with it.
Switched Shunts
Switched shunt fields may be anchored to their associated switched shunt. When the anchor switched shunt is
moved, these anchored objects will move with it.
Area/Zone Objects
Interfaces can be anchored to either area/zone objects or buses.
Lines and Transformers
Circuit breakers, line flow pie charts, and line analogs may be anchored to their associated line/transformer. When
the line/transformer is moved, these anchored objects will move with it.
Interfaces
Interface fields and interface pie charts can be anchored to their associated interface.
112
Building a Oneline Diagram
Inserting and Placing Multiple Display Fields
Simulator provides a convenient method of adding display fields to a variety of oneline display objects and placing
them in default positions relative to the display object. Unlike the field placement implemented by selecting Insert >
Fields from the main menu, the method described here allows you to place multiple fields around a display object in a
single operation. This option is available for several different types of objects, including buses, generators, lines and
transformers, shunts, and loads. The option can always be accessed by right clicking the display object of interest and
selecting the Add New Fields to … option from the resulting local menu. This brings up the Insert New Fields
around Selected Objects Dialog. This dialog is divided into several tabs by object type. Only tabs that correspond
to the type of objects you have selected will be available.
The tabs for inserting and placing multiple display fields for the various display objects (buses, generators,
lines/transformers, shunts, and loads) are virtually identical in content. The tab illustrates the possible locations of the
display fields for the various orientations of the display object. For example, since buses may be oriented either
horizontally or vertically, the dialog shows how each of the eight possible bus fields would be positioned for each of the
two orientations. Generators, loads, and shunts each hav e four possible orientations, so the dialog identifies the
locations for the possible fields for each of the four orientations. Transmission lines and transformers can assume
only one orientation, and the dialog will thus show the possible field locations for that single orientation.
Each field location is identified on the illustrations with a label of the form Pos #. In order to modify the settings, move
your mouse over the position on the dialog you want to change and click. This will bring up the appropriate Field
Options Dialog such as the Bus Field Options, Generator Field Options, Load Field Options, Switched Shunt Field
Options, or the Line Field Options. Simply select the field you want and choose OK. If you would like to set a default
field to "none", click Remove Field instead of OK.
Click OK to implement your choices for field additions and placement, or click Cancel to discard the changes.
This help topic has gone over how to add new fields to existing display objects. It should be noted from this discussion
that all objects have an associated set of default fields that will be added to the oneline when the objects are originally
inserted. You may redefine the default fields selecting Options > Default Drawing Values from the main menu and
modifying the Default Drawing Options Dialog.
113
Areas, Zones and Owners
Area/Zone/Super Area Display Objects
Areas and zones may be represented on Simulator oneline diagrams. This feature may prove particularly useful for
illustrating how the areas and zones comprising the system are interconnected. Not only can Simulator depict bus-to-
bus connections, but it can also show area-to-area and zone-to-zone connections through the use of area and zone
display objects and interface objects. Since multiple oneline diagrams can be associated with a single power flow
case, you may find it useful to construct two oneline diagrams for your model: one showing the system at the bus
level, and the other representing the areas or zones that make up the model as blocks tied together by area-area or
zone-zone interface objects.
Edit Mode
To add an area or zone display object to a oneline, choose Insert > Area/Zone/Super Area from the main menu or
click the Area/Zone button on the Insert Toolbar. Then, click the left mouse on the oneline to indicate where you
would like to place the new area or zone object. The Area/Zone/Super Area Display Options Dialog will appear.
Supply the requested information and click OK to finish adding the area or zone or Cancel to abort the operation. If
you choose OK, the new area or zone display object will appear on the oneline diagram at the location you chose.
When you select an area or zone display object, it will display its sizing handles. Use the sizing handles to resize
the area or zone display object as desired.
Area or zone objects may be connected together by interface objects.
It is important to note that this discussion covers how to add area or zone display objects only, not area or zone
records. Area or zone records cannot be added graphically. Instead, area or zone records are added to the model
whenever a bus is assigned to an area or zone that does not already exist. The procedure we have discussed here
can be used only to represent a pre-existing area or zone graphically on a oneline. It cannot be used to add an
area or zone to a case model.
114
Building a Oneline Diagram
Area/Zone/Super Area Display Options Dialog
When you insert an area or zone display object on a oneline diagram, Simulator opens the Area/Zone/Super Area
Display Options dialog. This dialog is used to control various display and identity attributes of the area or zone display
object. The dialog contains the following fields:
Number
This dropdown box lists the number of all areas (if you are inserting an area object), zones (if you are inserting a
zone object), or super areas (if you are inserting a super area object) in the case. Use this control to associate the
display object with the correct area, zone, or super area.
Name
If you would prefer to search through areas, zones, and super areas by name rather than by number, use the Name
dropdown box to see a list of names of all the areas or zones in the case.
Show Record Type Prefix
Check this box if you wish to place the prefix Area, Zone or Super Area before the name/number caption in the
object.
Prefix Text
Specify additional prefix text to be added before the Record Type prefix.
The remainder of the choices presented on the Area/Zone/Super Area Display Options dialog pertain to the object's
display appearance.
Style
Choose whether the display object should appear as a rectangle or as an ellipse.
Caption
Indicate how the display object should be identified to the user: by name, number, or both.
Width, Height
The dimensions of the new display object.
Click OK to save your selections and add the object to the oneline, or choose Cancel to terminate the addition.
115
Owner Display Objects
Owner objects may now be displayed on a Simulator oneline diagram. This can be useful for building a diagram on
which you also want to include summary objects by owner, in w hich information about the generation and load of the
owner are indicated with the object.
To insert an Owner object, select Insert > Owner from the main menu. Then left-click on a oneline diagram in the
location where the owner object should be placed. This will open the Owner Display Options dialog, which will allow
you to choose the owner information to display, and set parameters for the displayed object.
116
Building a Oneline Diagram
Owner Display Options Dialog
When you insert an owner display object on a oneline diagram, Simulator opens the Owner Display Options dialog.
This dialog is used to control various display and identity attributes of the owner display object. The dialog contains
the following fields:
Number
The owner number.
Name
The owner name.
Show Record Type Prefix
Check this box if you wish to place the prefix Owner before the name/number caption in the object.
Prefix Text
Specify additional prefix text to be added before the Owner prefix.
The remainder of the choices presented on the Owner Display Options dialog pertain to the object's display
appearance.
Style
Choose whether the display object should appear as a rectangle or as an ellipse.
Caption
Indicate how the display object should be identified to the user: by name, number, or both.
Width, Height
The dimensions of the new display object.
Click OK to save your selections and add the object to the oneline, or choose Cancel to terminate the addition.
117
Area Fields on Onelines
Area fields are used to show various values associated with a particular area of the power system. Right clicking on
the area field displays the Area Field Dialog.
Edit Mode
To enter a new area field, first select Insert > Fields > Area Fields from the main menu, or click the Area Fields
button on the Insert Toolbar. Then, click on or near a bus in the area for which you want to add a field. This calls up
the Area Field Dialog. Verify that the area number is correct. By default, this value is the number of the area
associated with the closest bus. Enter the total number of digits the field should display as well as the number of
digits to the right of the decimal point. Depending on what the field is designed to display, you may need to enter an
additional area number. Finally, select the field type. Click OK to save the field or Cancel to abort the operation.
To modify the parameters of an existing area field, position the cursor anywhere on the area field and right-click.
This again brings up the Area Field Dialog. Use the Format > Display / Zoom Levels main menu option to change
various display attributes for the area field, including its font and background color. Finally, you can use the Format
> Oneline Display > Default Font option to change the font for all fields on the display.
118
Building a Oneline Diagram
Zone Fields on Onelines
Zone field objects are used to show different values associated with zones and the system. This dialog is used to view
and modify the parameters associated with these fields. Note that the zone number itself cannot be changed on this
dialog. To reach this dialog, go to Insert > Field > Zone Field in Edit Mode.
Zone Number
Zone number associated with the field. When you insert fields graphically, this field is automatically set to the zone
number associated with the closest bus on the oneline. With most types of zone fields, an Zone Number of 0 is
valid and defines the field as showing values for the entire system.
Find…
If you do not know the exact zone number you are looking for, you can click this button to open the advanced
search engine.
Total Digits in Fields
Total number of digits to show in the field.
Digits to Right of Decimal
Number of digits to show to the right of the decimal point.
Other Zone Number
Some of the fields, such as MW Flow to Other Zone , require that a second area be specified. If applicable, enter
the second (other) zone here.
Delta per Mouse Click
This value is used only with the Sched Flow to Other Zone field type. When there is a nonzero entry in this field,
and the field type is Sched Flow to Other Zone , a spin button is shown to the right of the zone field. When the up
spin button is clicked, the flow to the other zone is increased by this number of MW; when the down button is
clicked, the scheduled flow is decreased by this amount.
Field Value
Shows the current output for the zone field. Whenever you change the Type of Field selection, this field is
updated.
For the Sched Flow to Other Zone field type only, you can specify a new value in MW. Exports are assumed to be
positive.
Field Prefix
An optional string that precedes the field value.
Rotation Angle in Degrees
The angle at which the text is to appear on the oneline diagram.
Include Suffix
If the Include Suffix checkbox is checked, the corresponding field units will be displayed after the current value.
Otherwise, only the value without units will be shown.
Type of Field
Used to determine the type of zone field to show. The two choices available are Name and Number.
Name
Zone name (eight characters maximum). The Zone Number field must correspond to a valid zone.
Number
Zone number (1 - 999). The Zone Number field must correspond to a valid area.
MW Load, Mvar Load
If the zone number is nonzero, then these fields show Total MW or Mvar load for the zone. If the zone number is
zero, these fields show the total load in the entire system.
MW Generation, Mvar Generation
If the Zone Number is nonzero, then these fields show Total MW or Mvar generation for the zone. If the Zone
Number is zero, these fields show the total generation in the entire system.
MW Shunts, MVR Shunts
If the Zone Number is nonzero, then these fields show Total MW or Mvar shunt compensation for the zone. If the
Zone Number is zero, these fields show the total shunt compensation in the entire system.
119
MW Flow to Other Zone, Mvar Flow to Other Zone
Total MW or Mvar flow from the zone specified in the Zone Number field to the zone specified in the Other Zone
Number field. The Zone Number field must correspond to a valid zone. If the Other Zone Number field is zero, this
field shows the zone's total MW or Mv ar exports.
MW Losses, MVAr Losses
If the Zone Number is nonzero, then these fields show Total MW or Mvar losses for the zone. If the Zone Number
is zero, these fields show the total real or reactive losses in the entire system.
Load Schedule Multiplier
Indicates the current value of the multiplier applied to the zone's loads. See Load Variation Display for more detail.
Select OK to save changes and close the dialog or Cancel to close dialog without saving your changes.
120
Building a Oneline Diagram
Super Area Fields on Onelines
To display certain information about a super area, such as MW Load or MVAR losses, ins ert a super area field. This
can be done in Edit Mode through Insert > Fields > Super Area Field. This will bring up the Super Area Field
Information. From here you can choose which super area to describe, how many digits in the field, and how many
digits to the right of the decimal. There are also 12 different field options to choose from. If a field value is not defined,
question marks will be shown.
121
Owner Fields on Onelines
Owner field objects are used to show different values associated with owners. This dialog is used to view and modify
the parameters associated with these fields. To insert an Owner field, click on Insert > Field > Owner Field from the
main menu.
Owner Number
Owner number associated with the field. When you insert fields graphically, this field is automatically set to the
owner number associated with the closest bus on the oneline.
Find by Number
To switch to a different owner in the field options dialog, you can enter the number in the Owner Number field, and
press the Find by Number button to update the dialog with information for the new owner.
Owner Name
Name of the owner whose information is presently being displayed in the dialog.
Find by Name
To switch to a different owner in the field options dialog, you can enter the name in the Owner Name field, and
press the Find by Name button to update the dialog with information for the new owner.
Total Digits in Fields
Total number of digits to show in the field.
Digits to Right of Decimal
Number of digits to show to the right of the decimal point.
Field Prefix
An optional string that precedes the field value.
Rotation Angle in Degrees
The angle at which the text is to appear on the oneline diagram.
Field Value
Shows the current output for the owner field. Whenever you change the Type of Field selection, this field is
updated.
Include Suffix
If the Include Suffix checkbox is checked, the corresponding field units will be displayed after the current value.
Otherwise, only the value without units will be shown.
Type of Field
Used to determine the type of owner field to show. You can choose from one of the six default fields, or click on the
Find Field… button to choose from a list of all available owner fields.
122
Building a Oneline Diagram
Buses
Bus Display Objects
In power system analysis, the term "bus" is used to refer to the point where a number of electrical devices, such as
lines, loads or generators, join together. On the oneline diagram, buses are usually represented with either a thick
horizontal line or a thick vertical line. The bus thickness and color can be customized.
Right-clicking on the bus will display its local menu. The local menu offers you the chance to view the corresponding
Bus Dialog, the Quick Power Flow List, and the Bus View Display. When the application is in Edit Mode, the local
menu will also allow you to add bus fields to the bus and to insert any undrawn buses connected to the selected bus.
Bus Fields are often placed close to the bus to indicate its voltage magnitude, voltage angle, and other relevant
information.
Edit Mode
To add a new bus to the case, follow this simple procedure:
· Select Insert > Bus from the main menu, or select the Bus button on the Insert Toolbar. This prepares
Simulator to insert a new bus.
· Left-click on the oneline background at the location where you want to plac e the new bus. This invokes the Bus
Option Dialog.
· Use the Bus Option Dialog Box to specify the number, name, size, thickness, orientation, area, zone, and
nominal voltage of the bus, as well as the load and shunt compensation connected to it. Every bus must have
a unique number.
· Click OK on the Bus Option Dialog to finish creating the bus and to close the dialog. If you do not wish to add
the bus to the case, click Cancel.
If you are simply adding a symbol to the oneline diagram for a bus that has already been defined in the case, many
of the parameters you are asked to specify in step three will be filled in for you.
To modify the parameters for an existing bus, position the cursor on the bus and right-click to invoke the bus' local
menu. From the local menu, choose Bus Information Dialog to view the associated Bus Dialog. You may change
any of the parameters specified there. When a bus' number is changed, the bus numbers associated with all of the
devices attached to that bus are also automatically changed. To renumber a number of buses simultaneously,
please see Options, Bus Renumbering Dialog.
To modify any aspect of a bus' appearance, first select the bus, and then click Format > Display/Size from the
main menu. You can change the length of the bus (but not its thickness) by dragging the bus' resizing handles.
To delete an existing bus, use either the Edit > Cut command to preserve a copy of the bus on the Windows
clipboard, or Edit > Delete to remove the bus without copying it to the clipboard. You will be asked whether you
want to remove both the display object and its associated bus record, or merely the display object, leaving the bus
in the power flow model. If you will never be deleting a record from the power system model, you may also choose
the option labeled Always Delete Objects Only. Be careful when deleting existing buses with attached devices. An
error will occur during validation if you do not also delete the attached devices or attach them to other buses.
123
Bus Fields on Onelines
Bus field objects are used primarily to indicate various quantities associated with bus devices. Furthermore, some bus
field types, which are distinguished by an integrated spin button, may be used to change bus device properties.
Run Mode
For bus fields with an associated spin button, clicking on the up/down arrows will change the value of the
associated field.
Right clicking on a bus field gives you the option to open the Bus Field Dialog or the Bus Information Dialog.
Edit Mode
Simulator offers two options for adding bus fields to a oneline in Edit Mode. If you need to enter only a single field,
the easier approach may be to choose Insert > Field > Bus Field from the main menu or the Bus Field button from
the Insert Toolbar and then select the bus to which you want to add the field. This invokes the Bus Field Dialog.
Enter the bus number associated with the device (the default is the closest bus to the field), the total number of
digits to show, and the number of digits to the right of the decimal point. Specify the ID field when working with
fields related to generators or loads. Next, select the type of field to show. To show load/capacitor/generator
values, the corresponding device must, of course, be attached to the bus. The Setpoint Generator MW type should
be selected only for cases that employ the uniform frequency option. For generator actual MW and Setpoint MW
types and load MW and Mvar fields, specify a nonzero value in the Delta per Mouse Click to design a bus field with
an integrated spin control. The Gen AGC Status field is used to display the automatic generation control status of
the generator. The user can toggle this status in Simulator by clicking on the field. Likewise, the Gen AVR Status
field is used to display the automatic voltage regulation status of the generator. Again the user can toggle this
status by clicking on the field.
The second approach for adding new bus fields entails right-clicking the bus and selecting Add New Fields Around
Bus from the resulting local menu. Please see Inserting and Placing Multiple Display Fields for more details.
To modify the parameters of an existing bus field, position the cursor anywhere on the object and right-click. This
brings up the Bus Field Dialog. Choose Font, Line/Fill, or Display/Size from the Format menu to change various
display attributes of the field, including its font and background color.
124
Building a Oneline Diagram
Voltage Gauges
Voltage gauges provide a way to visualize the voltage of a bus relative to its high- and low -voltage alarm limits. A
gauge looks very much like a thermometer. As the temperature changes, the height of the mercury in the
thermometer moves up and down. One reads the temperature measured by the thermometer by noting the marking
that matches the top of the mercury. Voltage gauges in Simulator work the same way. A voltage gauge has three
markings on its side, eac h of which identifies a key per-unit voltage level. Specifically, these three markings locate the
minimum, maximum, and target per-unit voltages. Often, the target voltage level is the nominal voltage, but this is not
a requirement. Inside the gauge is a filled region. The default color of the filled region is blue, but this can be
changed. When you create the voltage gauge, you associate it with a bus, and you specify its fill color and its
minimum, maximum, and target voltage levels. Once the gauge has been placed on a display, it will reveal changes in
its associated bus’s voltage by varying the height of its filled region. This tool was introduced to provide an alternative
to voltage contours to show the variation of voltage across a region. Contouring can reveal the variation of only a
single quantity at a time. For example, it is impossible to contour bus voltage magnitude and bus voltage phase angle
simultaneously. Voltage gauges are helpful because they allow you to show the voltage profile superimposed on a
contour of some other quantity.
To add a voltage gauge to a display, switch to Edit Mode and select Insert > Gauges > Bus from the main menu.
The cursor will become a crosshairs. Click on the oneline diagram where you would like the new voltage gauge to
appear. The Voltage Gauge Options Dialog will appear. Use this dialog to define the minimum, maximum and target
voltages for the voltage gauge, as well as its fill color and whether it should be anchored to its associated bus. After
you click the "OK" button, the Voltage Gauge Options Dialog will close, and the new voltage gauge will appear.
Once a gauge has been placed on the oneline, the height of its filled region will change as the voltage of its associated
bus changes. To modify any of the characteristics of the gauge, such as its key voltage levels, fill color, and anchor
setting, simply right-click on the bus voltage gauge to open the Voltage Gauge Options Dialog again.
125
Voltage Gauge Options Dialog
The Voltage Gauge Options Dialog is used to define and configure a bus voltage gauge. A bus voltage gauge is
associated with a particular bus and reveals the bus’s voltage relative to specified minimum, maximum, and target per-
unit voltage levels. The height of the colored column in the voltage gauge indicates the bus’s voltage relative to these
markings.
The dialog sports the following controls:
Number, Name, and Find
Use the Number and Name dropdown boxes to identify the bus to which you want the gauge to correspond. Select
a bus number from the Number dropdown box to identify the bus by number, and a bus name from the Name
dropdown box to identify a bus by name. It may be more convenient to press the Find to open the Find Dialog,
which allows you to spec ify a bus by either name or number using wildcards. When you first open the Bus Voltage
Gauge Dialog, the bus name and number will correspond to the bus object that was closest to the point where you
clicked.
Minimum, Target, and Maximum
Use these three spin edit boxes in the Voltage levels group box to specify the minimum, maximum, and target per-
unit voltage levels. These settings determine where on the gauge its three markings will be drawn.
The Minimum and Maximum value will be taken from the Limit Monitoring settings for the current bus, unless you
uncheck the option "Set Limits According to Current Limit Monitoring Settings ".
Fill color
The Fill color box reveals the color that will be used to paint the filled region of the gauge. Click on the Fill color box
to open a Color Dialog, which you may then use to specify a different color.
Anchored
A bus voltage gauge is said to be anchored if, when you move its associated bus object, it moves with it. Check the
Anchored check box to ensure that the gauge wll move with its associated bus. Otherwise, when you move its
associated bus object, the gauge will stay in its current position.
OK, Help, and Cancel
Click OK to finalize your settings. This will create a new voltage gauge object if you are trying to create one from
scratch, or it will modify the appearance and settings of an existing one if you have chosen to modify one that has
already been defined. Click Cancel to dispose of your changes. Click the Help button to reveal this help text.
126
Building a Oneline Diagram
Substations
Substation Display Objects
Substations in Simulator define a group of buses that are closely connected. Each bus can belong to either one
substation or no substation (called unassigned). By default in Simulator, all buses are not assigned to a substation.
This is done because all traditional text file power flow formats do not include information regarding a bus' substation.
Substations are represented on the oneline as a rectangle with the name of the substation inside it. Other information
about the substation is also displayed on the rectangle:
· The upper left corner displays a generator symbol if generation exists in the substation.
· The upper right corner displays a load symbol if load exists in the substation.
· The lower right corner displays a shunt symbol if shunts exist in the substation.
· The lower left corner displays the number of buses inside the substation.
· The lower middle displays the maximum voltage level in the substation.
You can also customize the size, colors, and font name and style of a substation object. Note however that the font
size of the substation object is automatically changed by Simulator as you change the size of the rectangle.
Right-clicking on the substation will display its local menu. The local menu offers you the chance to view the
corresponding Substation Information Dialog and the Substation View Display.
127
Substation Fields on Onelines
To display certain information about a super area, such as MW Load or MVAR losses, insert a super area field. This
can be done in Edit Mode through Insert > Fields > Super Area Field. This will bring up the Super Area Field
Information. From here you can c hoose which super area to describe, how many digits in the field, and how many
digits to the right of the decimal. There are also 12 different field options to choose from. If a field value is not defined,
question marks will be shown.
128
Building a Oneline Diagram
Generators
Generator Display Objects
Generators are represented on the oneline as circles with a "dog bone" rotor inside. Multiple generators at a bus are
allowed, with each being distinguished by a unique character identifier.
Each generator symbol (except that corresponding to the slack) is equipped with a circuit breaker that can be used to
change the status of the generator. You may toggle the generator status by clicking on the circuit breaker.
Furthermore, the angular position of the dog bone rotor can indicate the "angle" of the voltage at the generator
terminal if desired.
Generator fields are often placed close to the generator on the oneline to indicate the generator's MW/Mvar output.
Run Mode
When animation is active, the default flow of the arrows emerging from the generator is proportional to its MW
output. You can customize the appearance of this flow using the Animated Flows Tab of the Oneline Display
Options Dialog.
Right clicking on the generator brings up the generator submenu. This menu is used to display a variety of
information about the generator, including
· Generator Information Dialog
· Input-output curve
· Fuel cost curve
· Incremental cost curve
· Heat-rate curve
· Reactive capability curve
Edit Mode
To add a new generator to the case, select Insert > Generator from the main menu, or click the Generator button
on the Insert Toolbar. Then, place the cursor on the bus where you would like to attach the generator, and click
with the left mouse button. This calls up the Generator Dialog. The bus number is automatically determined from
the bus to which you attached the generator. The ID field contains a an alphanumeric ID used to distinguish
multiple generators at a bus. The default is '1'.
Enter the size, the thickness of the lines (in pixels) used to display the device, orientation, and other parameters for
the generator. Each generator automatically contains a switch for connecting or disconnecting the device in
Simulator. Select OK to add the generator. If you do not want to add the generator to the case, select Cancel.
To modify the parameters for an existing generator, position the cursor on the generator and right-click. This again
brings up the Generator Dialog. You can then change any parameter (be careful in renumbering an existing
generator). Use the Format Menu commands to change the color, line thickness, and other display parameters.
129
Generator Fields on Onelines
Generator field objects are used primarily to indicate various quantities associated with generation devices.
Furthermore, some generator field types, which are distinguished by an integrated spin button, may be used to change
generation device properties.
Run Mode
For generator fields with an associated spin button, clicking on the up/down arrows will change the value of the
associated field.
Right clicking on a generator field gives you the option to open the Generator Field Dialog or the Generator
Information Dialog.
Edit Mode
Simulator offers two options for adding generator fields to a oneline in Edit Mode. If you need to enter only a single
field, the easier approach may be to choose Insert > Field > Generator Field from the main menu or the
Generator Field button from the Insert Toolbar and click near generator for which you want to add the field. This
invokes the Generator Field Dialog. Enter the bus number associated with the device (the default is the bus
associated to the closest generator to the field), the ID field, the total number of digits to show, and the number of
digits to the right of the decimal point. Next, select the type of field to show. The Setpoint Generator MW type
should be selected only for cases that employ the uniform frequency option. For generator actual MW and Setpoint
MW types and load MW and Mvar fields, specify a nonzero value in the Delta per Mouse Click to design a bus field
with an integrated spin control. The Gen AGC Status field is used to display the automatic generation control status
of the generator. The user can toggle this status in Simulator by clicking on the field. Likewise, the Gen AVR
Status field is used to display the automatic voltage regulation status of the generator. Again the user can toggle
this status by clicking on the field.
The second approach for adding new generator fields entails right-clicking the bus and selecting Add New Fields
Around Generator from the resulting local menu. Please see Inserting and Placing Multiple Display Fields for more
details.
To modify the parameters of an existing generator field, position the cursor anywhere on the object and right-click.
This brings up the Generator Field Dialog. Choose Font, Line/Fill, or Display/Size from the Format menu to
change various display attributes of the field, including its font and background color.
130
Building a Oneline Diagram
Loads
Load Display Objects
Simulator models aggregate load at each system bus. Multiple loads at a bus are allowed. Each load object on the
oneline comes equipped with a circuit breaker. The status of the load corresponds to the status of its circuit breaker. A
circuit breaker is closed if it appears as a filled red square, and it is open if it appears as a green square outline. In
Run Mode, you may toggle the status of the load by clicking on its associated circuit breaker.
Load fields are often placed close to the loads on the oneline to indicate their MW/Mvar value.
Run Mode
When animation is active, the flow of the arrows into the load is proportional to its current MW load. You can
customize the appearance of this flow using the Animated Flows Tab of the Oneline Display Options Dialog.
Right clicking on a load (bus) field gives you the option to open the Load Field Dialog or the Load Dialog.
Edit Mode
To add a new load to the case, select Insert > Load from the main menu, or click the Load button on the Insert
Toolbar. Then, select the bus to which you want to attach the load with the left mouse button. This calls up the
Load Dialog. The bus number is automatically determined from the bus to which you attached the load. The ID field
contains a two-character ID used to distinguish multiple loads at a bus. The default ID is 1.
Enter the size, the thickness of the lines [in pixels] used to display the device, the orientation, and the base MW and
Mvar load values for the device. Usually, only the Constant Power fields are specified as nonzero. The Constant
Current and Constant Impedance fields are used to specify loads that vary with voltage. Constant current loads
vary proportionally with bus voltage, while constant impedance loads vary with the square of the voltage. Specify
the constant current and constant impedance values assuming one per-unit voltage.
Select OK to add the load. If you do not want to add the load to the case, select Cancel.
To modify the parameters for an existing load, position the cursor on the load and right-click. Select Load
Information Dialog from the local menu to invoke the Load Dialog. You can then change any parameter as desired.
You can select Format > Display/Size from the main menu to change the drawing parameters of the load.
131
Load Fields on Onelines
Load field objects are used primarily to indicate various quantities associated with load devices. Furthermore, some
load field types, which are distinguished by an integrated spin button, may be used to change load device properties.
Run Mode
For load fields with an associated spin button, clicking on the up/down arrows will change the value of the
associated field.
Right clicking on a load field gives you the option to open the Load Field Dialog or the Load Information Dialog.
Edit Mode
Simulator offers two options for adding load fields to a oneline in Edit Mode. If you need to enter only a single field,
the easier approach may be to choose Insert > Field > Load Field from the main menu or the Load Field button
from the Insert Toolbar and then select the load to which you want to add the field. This invokes the Load Field
Dialog. Enter the bus number associated with the device (the default is the bus associated to the closest load to the
field), the ID field, the total number of digits to show, and the number of digits to the right of the decimal point. Next,
select the type of field to show.
The second approach for adding new generator fields entails right-clicking the bus and selecting Add New Fields
Around Load from the resulting local menu. Please see Inserting and Placing Multiple Display Fields for more
details.
To modify the parameters of an existing load field, position the cursor anywhere on the object and right-click. This
brings up the Load Field Dialog. Choose Font > Line/Fill, or Display/Size from the Format menu to change
various display attributes of the field, including its font and background color.
132
Building a Oneline Diagram
Transmission Lines
Transmission Line Display Objects
Transmission lines are represented on the onelines using multiple segment lines drawn between buses. Transmission
lines may be equipped with circuit breakers that can be used to change the line's status. You can also add pie charts
and line fields to transmission lines to indicate how heavily loaded the line is. The appearance of transmission lines,
including line thickness and color, may also be customized.
Run Mode
Simulator's animation feature can be used to indicate the magnitude of the flow on the transmission line, either in
MW or in terms of the line's percentage loading. You can customize the line flow animation using the Animated
Flows Options on the Oneline Display Options Dialog.
Right-clicking on a transmission line displays the line's local menu, from which you can choose to inspect the
Line/Transformer Dialog.
Edit Mode
To add a new transmission line to the case, first select the Insert > Transmission Line command, or click the AC
Transmission Line button on the Insert Toolbar. Then place the cursor on the first bus for the transmission line
(the "from" bus) and click the left mouse button. Add more segments to the line by moving the cursor and clicking
with the left mouse button. To complete adding a new line, place the cursor on the second bus for the line (the "to"
bus) and double-click with the left mouse button. This calls up the Line/Transformer Dialog. The "from" and "to"
bus numbers are set automatically provided the line starts and ends on existing buses. If there is just one line
between the buses, the circuit number should be "1." For multiple lines between buses, you must give each a
unique circuit number. Enter the thickness of the lines [in pixels] used to display the transmission line. Enter the
per unit (100 MVA base) resistance, reactance, total charging susceptance (that is B not B/2) for the line, and an
MVA rating. Select OK to add the line. If you do not want to add the line to the case, select Cancel.
To modify the parameters for an existing line, position the cursor anywhere on the line and right-click. This brings
up the Line/Transformer Dialog, which you can use to change various line parameters. Choose Format >
Display/Size from the main menu to change the drawing parameters of the line.
To change the shape of the line, first left-click on the line to select it. This causes handles to appear at each vertex.
You can then move any vertex clicking and holding the left mouse button down on the vertex, dragging it to a new
location, and then releasing the mouse button. To remove a vertex, hold down the CTRL key and then click the
vertex you would like to delete. To add a vertex, hold down the CTRL key and then click on the line where you
would like to add a vertex.
133
Line Fields on Onelines
Line field objects are used to show values associated with lines, transformers and dc transmission lines.
Run Mode
Right clicking on the line field gives you the option to open the Line Field Dialog or the Line Information Dialog.
Edit Mode
To enter a new line field, select Insert > Fields > Line Field from the main menu or the Line Fields button on the
Insert Toolbar and select the line, transformer, or dc line to which you want to add the field. The Line Field Dialog
will open. Enter the near and far bus number associated with the device (the default values for these fields
correspond to the device on which you clicked) and the circuit number of the device. The field will display the flow
value at the near end of the device. Enter the total number of digits to show on the screen and the number of digits
to the right of the decimal point. Finally, select the desired field type.
To modify the parameters of an existing line field, position the cursor anywhere on the object and right-click. This
again brings up the Line Field Dialog. Select Format > Display/Size from the main menu to change many of the
line field's display attributes. Choose Format > Oneline Display > Default Font to change the font for all fields on
the display.
Another way to add line fields to the oneline entails right-clicking the line and selecting Add New Fields Around Line
from the resulting local menu. Please see Inserting and Placing Multiple Display Fields for more details.
134
Building a Oneline Diagram
Circuit Breakers on Onelines
Circuit breakers are used to open or close transmission lines and transformers. They are also used to place
generators, loads and switched shunts in or out of service. Closed circuit breakers are show n as solid red squares,
while open circuit breakers are shown as a green square outline. Circuit breakers cannot be placed on dc
transmission lines. To change the status of a breaker, left-click on the breaker while in run mode.
In PowerWorld Simulator, a circuit breaker directly controls the status of its associated display object. One breaker is
shown on the line connecting a generator, load, or shunt to its associated bus. Two breakers are shown by default on
transmission lines and transformers. Opening either of the line's circuit breakers opens the transmission line or
transformer, you do not have to open circuit breakers at both ends of the line.
Edit Mode
By default, when you add a new display object to a oneline diagram, the necessary circuit breakers are
automatically added at each end of the branch.
To add a new circuit breaker to the oneline, select Insert > Circuit Breaker from the main menu and then click the
line to which you want to add the breaker. The Circuit Breaker Options Dialog will appear with the from and to bus
numbers, and the circuit number automatically set to identify the line you selected. Specify the size for the switch
and its initial status, as well as whether it will be anchored to the line so that it will move with the line. Click OK to
add the circuit breaker, or click Cancel to abort the process. To add more circuit breakers to the line, simply repeat
this procedure.
To modify the parameters for an existing breaker, position the cursor anywhere on the device and right-click. This
invokes the Circuit Breaker Options Dialog, from which you can change many of the breaker's parameters.
Additional display settings for the circuit breaker can be accessed by selecting Format > Display/Size from the
main menu.
You can toggle the status of Transmission Line and Transformer circuit breakers while in Edit Mode by right-clicking
on the associated line or transformer and selecting Open Line or Close Line from the local menu.
Run Mode
Circuit Breaker status can be toggled in Run Mode by Left-Clicking on a breaker to place its associated object either
in or out of service. If the simulation is currently running, any effects of changing a circuit breaker’s status are
immediately shown on the oneline.
135
Line Flow Pie Charts on Onelines
The line flow pie charts are used to indicate the percentage MVA, MW, or Mvar loading of a transmission line or a
transformer. The degree to which the pie chart is filled shows how close the device is to its limit (provided the device
has a nonzero limit). A line flow pie chart becomes completely filled when the device's flow meets or exceeds 100% of
its rating.
Use the Pie Chart Options tab of the Oneline Display Options Dialog to customize various attributes of all pie charts.
The tab allows you to define a warning level at which the size and color of the pie charts will change to a size and
color you specify. The tab also allows you define a limit percent as well as the size and color to which to change the
pie charts when their corresponding devices violate their limits. You can also specify whether the pie charts should
reveal total power flow (MVA), real power flow (MW), or reactive power flow (MVR). The oneline display options dialog
can be invoked either by selecting Options > Oneline Display from the main menu or by right-clicking on the
background of the oneline diagram and selecting Oneline Display Options from the resulting local menu.
Right clicking on the pie chart displays the Line Flow Pie Chart Options Dialog. This dialog allows you to view the from
and to bus numbers and the circuit number of the line/transformer associated with the pie chart. You can change the
pie chart's size and the MVA rating of the line/transformer associated with the pie chart.
Edit Mode
To enter a new line flow pie chart, select Insert > Line Flow Pie Chart from the main menu or click the Line Flow
Pie Chart button on the Insert Toolbar and click on the line or transformer to which you want to add the pie chart.
This opens the Line Flow Pie Chart Options Dialog box. Enter the near and far bus number associated with the
device (these fields default to the terminal bus numbers of the device on which you clicked), the circuit number of
the device, and the desired size of the pie chart. The field will display the flow value at the near end of the device.
Enter the size of the device. Select OK to insert the line flow pie chart. Otherwise, select Cancel.
To modify the parameters of an existing line flow pie chart, position the cursor anywhere on the object and right-
click. This again brings up the Line Flow Pie Chart Options Dialog box.
136
Building a Oneline Diagram
Line Flow Gauges
Line flow gauges provide a way to visualize the flow of a transmission line or transformer relative to its thermal rating.
A gauge looks very much like a thermometer. As the temperature changes, the height of the mercury in the
thermometer moves up and down. One reads the temperature measured by the thermometer by noting the marking
that matches the top of the mercury. Line flow gauges in Simulator work the same way. A line flow gauge has two
markings on its side, one for the designated minimum flow, and one for the designated maximum flow (the branch's
rating). Inside the gauge is a filled region. The default color of the filled region is blue, but this c an be changed.
When you create the line flow gauge, you associate it with a transmission element, and you specify its fill color and its
minimum and maximum flow levels. Once the gauge has been placed on a display, it will reveal changes in its
associated branch's flow by varying the height of its filled region. This tool was introduced to provide an alternative to
line flow pie charts.
To add a line flow gauge to a display, switch to Edit Mode and select Insert > Gauges > Line from the main menu.
Click on the oneline diagram where you would like the new line flow gauge to appear. The Line Flow Gauge Options
Dialog will appear. Use this dialog to define the minimum and maximum flows for the line flow gauge, as well as its fill
color and whether it should be anchored to its associated transmission element. After you click the "OK" button, the
Line Flow Gauge Options Dialog will close, and the new line flow gauge will appear.
Once a gauge has been placed on the oneline, the height of its filled region will change as the flow of its transmission
element changes. To modify any of the characteristics of the gauge, such as its key flow levels, fill color, and anchor
setting, simply right-click on the line flow gauge to open the Line Flow Gauge Options Dialog again.
137
Line Flow Gauge Options Dialog
The Line Flow Gauge Options Dialog is used to define and configure a Line Flow gauge. A line flow gauge is
associated with a particular line and reveals the line’s flow relative to specified minimum and maximum thermal flow
levels. The height of the colored column in the line flow gauge indicates the line’s flow relative to these markings.
The dialog sports the following controls:
Number, Name, and Find
Use the Number and Name dropdown boxes, in addition to the Circuit field, to identify the terminal buses to which
the branch desired corresponds. It may be more convenient to press the Find button to open the Find Dialog,
which allows you to specify the line by either bus names or numbers using wildcards. When you first open the Line
Flow Gauge Dialog, the bus names and numbers will correspond to the transmission line object that was closest to
the point where you clicked.
Minimum and Maximum
Use these two spin edit boxes in the MW Rating values group box to specify the minimum and maximum flow
levels. These settings determine where on the gauge its two markings will be drawn.
The Minimum and Maximum value will be taken from the Limit Monitoring settings for the current transmission line,
unless you uncheck the option "Set Limits According to Current Limit Monitoring Settings".
Anchored
A line flow gauge is said to be anchored if, when you move its associated line object, the gauge moves with it.
Check the Anchored check box to ensure that the gauge will move with its associated line. Otherwise, when you
move its associated line object, the gauge will stay in its current position.
OK, Help, and Cancel
Click OK to finalize your settings. This will create a new line flow gauge object if you are trying to create one from
scratch, or it will modify the appearance and settings of an existing one if you have chosen to modify one that has
already been defined. Click Cancel to dispose of your changes.
138
Building a Oneline Diagram
DC Transmission Line Display Objects
DC transmission lines are represented on the onelines using multiple segment lines drawn between two buses. The
line thickness and color of dc transmission lines can be customized using Format > Display Appearance from the
main menu. Line fields are often placed close to dc transmission lines on the oneline to indicate the power flow
through the device.
Note that, unlike ac transmission lines, dc transmission lines cannot be equipped with circuit breakers.
Run Mode
Simulator's animation feature can be used to indicate the magnitude of the flow on the dc transmission line, either in
MW or in terms of the line's percentage loading. You can customize the line flow animation using the Animated
Flows Options on the Oneline Display Options Dialog.
Right-clicking on a dc transmission line displays the line's local menu, from which you can choos e to inspect the DC
Transmission Line Dialog.
Edit Mode
To add a new dc transmission line to the case, first select Insert > DC Transmission Line from the main menu, or
click the DC Transmission Line from the Insert Toolbar. Then place the cursor on the bus you desire to be the
rectifier bus for the line and click the left mouse button. Add more segments to the line by moving the cursor and
clicking with the left mouse button. To complete the new line, place the cursor on the second bus for the line, which
will serve as the inverter bus, and double-click the left mouse button. This calls up the DC Transmission Line
Dialog. If you successfully selected the rectifier and inverter buses, their numbers will be automatically filled in for
you when the dialog opens.
The DC Transmission Line Record Dialog has four separate pages: Line Parameters, Rectifier Parameters, Inverter
Parameters, and Actual Flows. The separate pages can be ac cessed using the tabs shown at the top of the dialog.
These pages are used to set the modeling parameters associated with the dc lines.
To modify the parameters for an existing dc transmission line, position the cursor anywhere on the line and right-
click. This will provide access to the corresponding DC Transmission Line Dialog, from which you can modify any of
the dc line's parameters. Select Format > Display Appearance from the main menu to change the color and/or
line thickness of the dc line.
To change the shape of the line, first left-click on the line to select it. This causes handles to appear at each vertex.
You can then move any vertex by clicking and holding the left mouse button down, dragging the vertex to a new
location, and releasing the mouse button. To remove a vertex, hold down the CTRL key and then click the vertex
you would like to delete. To add a vertex, hold down the CTRL key and then click on the line w here you would like
to add a vertex.
139
Multi-section Line Display Objects
Multi-section lines are represented on the onelines using a line segment with intermediate or "dummy" bus
representations. These objects are not the same as a normal transmission line. They do display animated flows in
run mode, but do not have pie charts, circuit breakers, or text fields currently associated with the objects.
Run Mode
Simulator's animation feature can be used to indicate the magnitude of the flow on the transmission line, either in
MW or in terms of the line's percentage loading. You can customize the line flow animation using the Animated
Flows Options on the Oneline Display Options Dialog.
Right-clicking on a multi-section line displays the Multi-section Line Information Dialog.
Edit Mode
Unlike transmission lines and transformers, multi-section lines CANNOT be inserted in a case by adding the mult-
section line graphically. Therefore, when inserting a multi-section line object, the data for the object must already
exist in the case. To insert the multi-section line object, first select Insert > MS Transmission Line command from
the Insert menu. Then place the cursor on the first bus for the transmission line (the "from" bus) and click the left
mouse button. Add more segments to the line by moving the cursor and clicking with the left mouse button. To
complete adding a new line, place the cursor on the second bus for the line (the "to" bus) and double-click with the
left mouse button. Completing the multi-section line opens the Multi-section Line Information dialog. At the bottom
of this dialog are display options for the line, such as line pixel thickness, symbol size (for the series capacitor
representations, if any,) anchored, and options for drawing the buses.
To change the shape of the line, first left-click on the line to select it. This causes handles to appear at each vertex.
You can then move any vertex clicking and holding the left mouse button down on the vertex, dragging it to a new
location, and then releasing the mouse button. To remove a vertex, hold down the CTRL key and then click the
vertex you would like to delete. To add a vertex, hold down the CTRL key and then click on the line where you
would like to add a vertex.
140
Building a Oneline Diagram
Transformers
Transformer Display Objects
Transformers are represented as transmission lines with two opposing coils drawn on one of the segments. The
transformer's line thickness, color, and symbol segment can be customized using the Edit Mode. Optionally, circuit
breakers and pie charts can be placed on the transformer. Clicking on the circuit breakers changes the status of the
transformer.
Line fields are often placed close to transformers on the oneline to indicate the power flow through the device.
Transformer fields are often placed close to transformers on the oneline to indicate and control their tap positions.
See Transformer Modeling for details on modeling either LTC or phase shifting transformers.
Run Mode
Simulator's animation feature can be used to indicate the magnitude of the flow through the transmission line, either
in MW or in terms of the transformer's percentage loading. You can customize the line flow animation using the
Animated Flows Options on the Oneline Display Options Dialog.
Right-clicking on a transformer displays the line's local menu, from which you can choose to inspect the
Line/Transformer Dialog.
Edit Mode
New transformers are inserted in much the same way as transmission lines. To add a new transformer to the case,
first select Insert > Transformer from the main menu, or click the Transformer button on the Insert Toolbar. Then
place the cursor on the first bus for the transformer (the from bus) and click the left mouse button. Add more
segments to the transformer by moving the cursor and clicking with the left mouse button. To complete the new
transformer, place the cursor on the transformer's other terminal (the to bus) and double-click with the left mouse
button. This calls up the Line/Transformer Dialog. The from and to bus numbers for the transformer should have
been set automatically. If there is just one transformer between the buses, the circuit number should be "1." For
multiple transformers between buses, you must give each a unique circuit number. Enter the thickness of the lines
[in pixels] used to display the transformer, the number of the line segment in which you would like the transformer
symbol drawn, and the size of the transformer symbol.
Enter the per unit (100 MVA base) resistance, reactance and charging susceptance for the transformer, and an
MVA rating. Enter the off-nominal tap ratio and the phase shift angle in degrees. (For a transformer without tap or
phase control, the off-nominal tap should be 1.0 and the phase shift angle should be 0 degrees.)
Select the appropriate Automatic Control Option. If the transformer does not have tap control, select No Automatic
Control (this is the default). Select AVR (Automatic Voltage Regulation) if the transformer changes its tap ratio to
control the voltage at user specified regulation bus. Select Reactive Power Control if the transformer changes its
tap ratio to control the reactive power through the transformer. Finally, select Phase Shift Control if the transformer
changes its phase shift to control the MW flow through the transformer. If you need any of the last three options,
select the Automatic Control Options button to set the parameters associated with the automatic control.
For AVR control, enter the number of the bus whose voltage is to be controlled, the allowable range for the
controlled voltage (in per unit), the minimum and maximum tap ratios (typical values are 0.9 and 1.1), and the step
size for the discrete changes in the tap ratio (typical value is 0.00625).
For reactive power control, the control variable is always the reactive power measured at the from bus (i.e., the
tapped side) of the transformer. Positive flow is assumed to be going through the transformer to the to bus . Enter
the minimum and maximum allowable flows, the minimum and maximum tap ratios (typical values are 0.9 and 1.1),
and the step size for the discrete changes in the tap ratio (typical value is 0.00625).
For phase shift control, the MW flow through the transformer is the controlled value. Enter the bus number of the
terminal whose flow is controlled, the allowable range for the controlled flow (positive flow is assumed to be into the
transformer at the terminal entered in the previous field), the minimum and maximum phase angles (typical values
are -30° and 30°), and the step size in degrees (typical v alues are between 1° and 2°).
Select OK to save the values and return to the Transformer Options Dialog; otherwise select Cancel.
If you would like the transformer to be initially modeled as being on automatic control at the start of the case, select
the Automatic Control Active checkbox.
If you do not want to add the transformer to the case, select Cancel.
To modify the parameters for an existing transformer, position the cursor anywhere on the device and right-click.
This brings up the local menu from which you can choose to view the Line/Transformer Dialog. Use the
Line/Transformer Dialog to adjust many of the transformer's electrical properties. Select Format > Display
Appearance to change the transformer's color and/or line thickness.
See Transformer Modeling for details on modeling either LTC or phase shifting transformers.
141
Transformer Fields on Onelines
Transformer fields are used to show field values specific to transformers, such as tap position, phase angle, and more.
Run Mode
If there is a spin control integrated with the field, you can click on the spinner to change the field's value by the
associated Delta Per Mouse Click.
Right clicking on the transformer field gives the option to display the Transformer Field Dialog or the
Line/Transformer Information Dialog.
Edit Mode
To enter a new transformer field, select Insert > Fields > Transformer Field from the main menu or the
Transformer Field button on the Insert Toolbar, and then click on the transformer object to which you want to add
the new field. This calls up the Transformer Field Dialog. Enter the from and to bus numbers associated with the
device (the default values for these fields correspond to the transformer on which you clicked), and the circuit
number of the device. Enter the total number of digits that the field should display, as well as the number of digits to
the right of the decimal point. Finally, specify what the field should display: the off-nominal tap ratio, the off-nominal
tap position, or the phase shift angle in degrees.
To modify the parameters of an existing transformer field, position the cursor anywhere on the object and right-click
to bring up the Transformer Field Dialog. Use the Format > Display Appearance main menu option to change
various display attributes for the transformer field, including its font and background color. Finally, you can use the
Format > Oneline Display > Default Font option to change the font for all fields on the display.
142
Building a Oneline Diagram
Series Capacitors
Series Capacitor Display Objects
Series capacitors are represented as transmission lines with two opposing parallel bars drawn on one of the
segments. The series capacitor’s line thickness, color and symbol segment can be customized using the Edit Mode.
If the series capacitor branch is operating, but the series capacitor status is set to Bypassed, a low impedance
segment will be drawn around the series capacitor symbol to indicate the capacitor has been bypassed. The capacitor
status of Bypassed or In Service can be toggled in run mode if the Series Capacitor Status field is displayed on the
oneline diagram. When a left-click is registered on the Series Capacitor Status field when in Run Mode, the capacitor
status is toggled. Note that this is not the same as the overall branch status of Open or Closed.
Optionally, circuit breakers and pie charts can be placed on the series capacitor. Clicking the circuit breakers changes
the branch status of the series capacitor.
Run Mode
Simulator's animation feature can be us ed to indicate the magnitude of the flow through the series capacitor, either
in MW or in terms of the transformer's percentage loading. You can customize the line flow animation using the
Animated Flows Options on the Oneline Display Options Dialog.
Right-clicking on a transformer displays the line's local menu, from which you can choose to inspect the
Line/Transformer Dialog.
Edit Mode
New series capacitors are inserted in much the same way as transmission lines. To add a new series capacitor to
the case, first select Insert > Series Capacitor from the main menu, or click the Series Capacitor button on the
Insert Toolbar. Then place the cursor on the first bus for the series capacitor (the from bus) and click the left mouse
button. Add more segments to the series capacitor by moving the cursor and clicking with the left mouse button.
To complete the new series capacitor, place the cursor on the series capacitor's other terminal (the to bus) and
double-click with the left mouse button. This calls up the Line/Transformer Dialog. The from and to bus numbers
for the series capacitor should have been set automatically. If there is just one branch between the buses, the
circuit number should be "1." For multiple branches between buses, you must give each a unique circuit number.
Enter the thickness of the lines [in pixels] used to display the series capacitor, the number of the line segment in
which you would like the series capacitor symbol drawn, and the size of the series capacitor symbol.
Enter the per unit (100 MVA base) resistance, reactance and charging susceptance for the series capacitor, and an
MVA rating. On the Series Capacitor tab, check the box labeled Is Series Capacitor to indicate that the branch
model is a series capacitor device.
If you do not want to add the series capacitor to the case, select Cancel. Otherwise click OK to add the series
capacitor to the case.
To modify the parameters for an existing series capacitor, position the cursor anywhere on the device and right-
click. This brings up the local menu from which you can choose to view the Line/Transformer Dialog. Use the
Line/Transformer Dialog to adjust many of the series capacitor's electrical properties. Select Format >
Display/Size to change the series capacitor's color and/or line thickness.
See Series Capacitor Information for more details on modeling series capacitors.
143

 

 

 

 

 

 

 

Content      ..     2      3      4      5     ..